TypeSoft starter for three-phase loads, with control unit and pump algorithm, DC Brake, Soft Brake, Jog, Bluetooth
10.10 Temperature riseThe panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit ratingIs the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibilityIs the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical functionThe device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistanceMeets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosuresMeets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heatMeets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effectsMeets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiationMeets the product standard's requirements.
10.2.5 LiftingDoes not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impactDoes not apply, since the entire switchgear needs to be evaluated.
10.2.7 InscriptionsMeets the product standard's requirements.
10.3 Degree of protection of assembliesDoes not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distancesMeets the product standard's requirements.
10.5 Protection against electric shockDoes not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and componentsDoes not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connectionsIs the panel builder's responsibility.
10.8 Connections for external conductorsIs the panel builder's responsibility.
10.9.2 Power-frequency electric strengthIs the panel builder's responsibility.
10.9.3 Impulse withstand voltageIs the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating materialIs the panel builder's responsibility.
Fitted with:Display
Motor overload protection
Internal bypass
ClassAdjustable (5,10,15,20,30)
Climatic proofing5 to 95% Relative Humidity
Connection to SmartWire-DTIn the
Rated impulse withstand voltage (Uimp)6000 V
AltitudeMax 4000 m (Above 1000 m for detailed derating use S711 Select Software)
Number of inputs5 (2 fixed, 2 programmable, 1 thermistor)
Ambient operating temperature - max60 °C
Ambient operating temperature - min-25 °C
Ambient storage temperature - max70 °C
Ambient storage temperature - min-40 °C
Assigned motor power at 200/208 V, 60 Hz, 3-phase60 HP
Assigned motor power at 220/230 V, 60 Hz, 3-phase75 HP
Assigned motor power at 460/480 V, 60 Hz, 3-phase150 HP
Assigned motor power in-delta at 220/230 V, 60 Hz100 HP
Assigned motor power in-delta at 460/480 V, 60 Hz200 HP
Assigned motor power in-delta at 575/600 V, 60 Hz300 HP
Equipment heat dissipation, current-dependent Pvid945 W
Heat dissipation capacity Pdiss0 W
Heat dissipation per pole, current-dependent Pvid0 W
Mains voltage - max632.5 V
Output voltage250 V AC (relay outputs)
Number of outputs3 Relay Outputs (1 fixed, 2 programmable)
Screwdriver size17 mm M10, Terminal screw, Main cables
0.6 x 3.5 mm or PH0, Terminal screws, Control circuit cables
Rated operational voltage (Ue) - min200 V
Rated operational voltage (Ue) at AC - max575 V
Rated power three-phase motor, inline, at 230 V60 kW
Rated power three-phase motor, inline, at 400 V110 kW
Rated power three-phase motor, inside delta, at 230 V90 kW
Rated power three-phase motor, inside delta, at 400 V160 kW
Static heat dissipation, non-current-dependent Pvs120 W
Voltage rating - max575 V
Application- 3-phase motors: Yes
- Soft starting of three-phase asynchronous motors
ProtectionOptional terminal cover for Finger and back-of-hand proof, Protection against direct contact
Assigned motor power at 575 V_ 60 Hz_ 3-phase200 HP
Mounting positionAs required
Drop-out voltage0 - 16 V, DC operated
Degree of protectionIP00
NEMA Other
Current consumption2800 mA, Control circuit, Digital inputs
FunctionsSingle direction
Torque control
DC-Brake
Soft-Brake
Forward & reverse jog
Delay time0 - 180 s, Soft start function, Ramp times; 0 - 240 s, Soft stop function, Stop times
Overload cycleAC-53b: 3.5-20:580
Pick-up voltage19.2 - 28.8 V DC
Radio interference classClass A (IEC 60947-4-2)
InterfacesModbus RTU (built-in)
Bluetooth (built-in)
Kickstart600% (Kickstart current)
Max. 2000 ms (Kickstart Duration)
Rated control voltage (Uc)24 V DC (-20 %/+20 %)
Supply frequency50/60 Hz, fLN, Main circuit
Terminal capacity (stranded)1 x (95 - 240) mm², Main cables
1x (1 - 2.5) mm², Control circuit cables
Rated control supply voltage (Us) at DC - max24 VDC
Rated control supply voltage (Us) at DC - min24 VDC
Rated insulation voltage (Ui)600 V
Rated operational current (Ie) at AC-113 A
Rated operational current (Ie) at AC-53210 A
Rated operational current (Ie) at AC-53, in-delta315 A
Rated operational current for specified heat dissipation (In)210 A
Rated operational power at 220/230 V, 50 Hz60 kW
Rated operational power at 400 V, 50 Hz110 kW
Rated operational power at 500 V, 50 Hz150 kW
Rated operational power in-delta at 220/230 V, 50 Hz90 kW
Rated operational power in-delta at 400 V, 50 Hz160 kW
Rated operational power in-delta at 500 V, 50 Hz220 kW
Rated operational voltage (Ue) - max575 V
Shock resistance15 g, Mechanical
Suitable forBranch circuits, not as BCPD, (UL/cUL)
Tightening torque0.5 Nm, Screw terminals, Control circuit cables
40 Nm, Main cables
Short-circuit protection rating250NHG2B or NZMH2-A3208T, Type "1" coordination, Main conducting paths
170M5009 "Type 2" coordination, Main conducting paths
Start voltageMax. 600% FLA, Min. 100% FLA, Soft start function
Startup classCLASS 20 (heavy starting duty 3 x Iₑ for 45 s)
CLASS 10 (star-delta replacement)
CLASS 30 (6 x Iₑ for 30 s)
Terminal capacity (flexible with ferrule)1 x (95 - 240) mm², Main cables
1x (1 - 2.5) mm², Control circuit cables
Terminal capacity (solid)1 x (95 - 240) mm², Main cables
1x (1 - 2.5) mm², Control circuit cables
Terminal capacity (solid/stranded AWG)1 x (3/0 - 500), Main cables
1x (28 - 12) , Control circuit cables