Product name
Eaton XIOC Communication module
Product Length/Depth
100 millimetre
Product height
95 millimetre
Product width
30 millimetre
Product weight
0.145 kilogram
Certifications
CSA-C22.2 No. 142-M
CSA File No.: 012528
UL Category Control No.: NRAQ
UL508
UL
CSA
UL File No.: E135462
EN 50178
IEC/EN 61131-2
CSA Class No.: 2252-01
CE
CSA-C22.2 No. 0-M
Product Type
Communication module
Catalog Notes
MODBUS Master/Slave
Modes of operation:
RS232C, RS485, RS422
Serial interface
SUCOM-A
Suconet-K slave
Transparent mode
Cable type
RTS, CTS, DTR, DSR, DCD
Current consumption
275 mA (Ie), Interfaces
275 mA, max. internal current consumption, Interface modules
Resistance
500 g/⌀ 50 mm ±25 g (impact resistance)
Type
Communication module
RS232, RS 422, RS485, Interfaces
Used with
XC100/200 (expandable with up to 15 XI/OC modules)
Ambient conditions, mechanical
Shock resistance
15 g, Mechanical, Shock duration 11 ms
Vibration resistance
57 - 150 Hz ± 1.0 mm
10 - 57 Hz, ± 0.075 mm
Climatic environmental conditions
Ambient operating temperature - min
0 °C
Ambient operating temperature - max
55 °C
Ambient storage temperature - min
-20 °C
Ambient storage temperature - max
70 °C
Electro magnetic compatibility
Emitted interference
Class A (according to DIN/EN 55011/22)
Terminals
Optionally, screw terminals or spring-loaded terminals for digital/analog modules
Rated operational voltage
24 (12) V DC
Supply voltage
20.4 – 28.8 (11.8 – 14.4) V DC, Admissible range, Power supply
Addressing
Address range: 2 - 31
Bus termination
Switchable for RS485, RS422
Character formats
8E1, 8O1, 8N1, 8N2, 7E2, 7O2, 7N2, 7E1
Connection type
9-pole SUB-D connector (male), RS232
6-pole spring-loaded terminal block, RS422/RS485
Data transfer rate
0.3 kBit/s, Interface, Transparent mode
2.4 kBit/s, Interface, Transparent mode
4.8 kBit/s, Interface, Transparent mode
9.6 kBit/s, Interface, Transparent mode
0.6 kBit/s, Interface, Transparent mode
250 Byte per slave, Transmit/receive data
187.5 kBit/s, 375 kBit/s (Suconet)
38.4 kBit/s, Interface, Transparent mode
0.3 - 57.6 kBit/s
1.2 kBit/s, Interface, Transparent mode
120 Byte per slave (Suconet-K slave), Transmit/receive data
19.2 kBit/s, Interface, Transparent mode
57.6 kBit/s, Interface, Transparent mode
187.5 or 375 kBit/s, Suconet-K slave
Interfaces
Number of active interfaces/modules: 1
RTS, CTS, DTR, DSR, DCD (Operating mode Transparent mode, Control and signal cables, Analog control inputs)
RS485
RS422
RS232(C), RS422, RS485 (built-in)
Number of bytes
250 bytes (per Com)
Number of modules
2 (XC100)
4 (XC200)
Number of slots
As required
Plug type
RS485, 422: plug terminal block
RS232: 9 pole SUB-D plug
Protocol
MODBUS
Other bus systems
RS485 (Interface)
SUCONET
Rapid counter inputs
250 bytes per Com
Explosion safety category for dust
None
Explosion safety category for gas
None
Potential isolation
Interfaces (RS485, RS422): yes
Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
6.6 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.