ANUNCIAR
PLSM-B20/4-MW 242587 Y7-242587 EATON ELECTRIC Over current switch, 20A, 4p, type B characteristic View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

PLSM-B20/4-MW 242587 Y7-242587 EATON ELECTRIC Over current switch, 20A, 4p, type B characteristic

PLSM-B20/4-MW

242587

Y7-242587

EATON-MOELLER

Over current switch, 20A, 4p, type B characteristic

PLSM-B20/4-MW

Eaton Moeller series xPole - PLS6/M MCB. PLSM, 4 pole, tripping characteristic: B, rated current In: 20 A, rated switching capacity IEC/EN 60898-1: 10 kA

Miniature circuit breaker (MCB), PLSM, 4 pole, tripping characteristic: B, rated current In: 20 A, rated switching capacity according to IEC/EN 60898-1: 10 kA, Switchgear for residential and commercial applications

More details


Circuit breakers and fuses > Miniature circuit breaker (MCB)

Modular Switchgear – Industrial

Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

Total: $205.84
Unit price: $205.84
This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



General specifications

Product Name
Eaton Moeller series xPole - PLS6/M MCB
Catalog Number
242587
Model Code
PLSM-B20/4-MW
EAN
4015082425876
Product Length/Depth
80 mm
Product Height
75 mm
Product Width
70 mm
Product Weight
0.418 kg
Compliances
RoHS conform

Product specifications

Type
Special features
Ambient temperature hint: a 1 °C increase results in a 0.5% linear reduction of current carrying capacity
Application
  • Switchgear for residential and commercial applications
  • xPole - Switchgear for residential and commercial applications
Amperage Rating
20 A
Features
Additional equipment possible
Concurrently switching N-neutral
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Pollution degree
2
Used with
Miniature circuit breaker
PLSM
Degree of protection
IP20
Equipment heat dissipation, current-dependent
12.8 W
Rated impulse withstand voltage (Uimp)
4 kV
Tripping characteristic
B
Ambient operating temperature - max
75 °C
Ambient operating temperature - min
-25 °C
Built-in depth
70.5 mm
Connectable conductor cross section (multi-wired) - max
25 mm²
Connectable conductor cross section (multi-wired) - min
1 mm²
Connectable conductor cross section (solid-core) - max
25 mm²
Connectable conductor cross section (solid-core) - min
1 mm²
Current limiting class
3
Frequency rating - max
60 Hz
Frequency rating - min
50 Hz
Heat dissipation capacity
0 W
Heat dissipation per pole, current-dependent
0 W
Width in number of modular spacings
4
Voltage type
AC
Overvoltage category
III
Number of poles
Four-pole
Release characteristic
B
Number of poles (protected)
4
Number of poles (total)
4
Rated insulation voltage (Ui)
440 V
Rated operational current for specified heat dissipation (In)
20 A
Rated operational voltage (Ue) - max
400 V
Rated short-circuit breaking capacity (EN 60898) at 230 V
10 kA
Rated short-circuit breaking capacity (EN 60898) at 400 V
10 kA
Rated short-circuit breaking capacity (IEC 60947-2) at 230 V
0 kA
Rated short-circuit breaking capacity (IEC 60947-2) at 400 V
0 kA
Rated switching capacity (IEC/EN 60898-1)
10 kA
Static heat dissipation, non-current-dependent
0 W
Power loss
10.5 W

ETIM for 242587 Circuit breakers and fuses (EC000042)
Feature Name Feature Value
Built-in depth (EF000218) 70.5 mm
Release characteristic (EF000889) B
Number of poles (total) (EF008618) 4
Number of protected poles (EF005548) 4
Rated current (EF000227) 20 A
Rated voltage (EF000228) 400 V
Rated insulation voltage Ui (EF001366) 440 V
Rated impulse withstand voltage Uimp (EF011980) 4 kV
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V (EF009556) 10 kA
Voltage type (EF000187) AC
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V (EF009555) 10 kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V (EF009557) 0 kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V (EF009558) 0 kA
Frequency (EF000416) 50 Hz
Power loss (EF005387) 10.5 W
Current limiting class (EF002568) 3
Flush-mounted installation (EF007517) No
Concurrently switching neutral conductor (EF005997) Yes
Over voltage category (EF002569) 3
Pollution degree (EF002570) 2
Additional equipment possible (EF008148) Yes
Width in number of modular spacings (EF002950) 4
Degree of protection (IP) (EF005474) IP20
Ambient temperature during operating (EF007515) -25 °C
Connectable conductor cross section multi-wired (EF007343) 1 mm²
Connectable conductor cross section solid-core (EF007337) 1 mm²
Explosion-proof (EF004663) No

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.