Standards
Specification for general requirements: IEC/EN 61800-2
EMC requirements: IEC/EN 61800-3
Safety requirements: IEC/EN 61800-5-1
Certifications
CE, UL, cUL, RCM, UkrSEPRO, EAC
Production quality
RoHS, ISO 9001
Climatic proofing [ρw]
< 95%, average relative humidity (RH), non-condensing, non-corrosive %
Ambient temperatureoperation (150 % overload) [ϑ]
-10 - +50 °C
Ambient temperature
-10 - +45 °C for UL compliance over a period of 24 hours.
Ambient temperatureStorage [ϑ]
-40 - +60 °C
Radio interference levelRadio interference class (EMC)
C2, C3, depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Radio interference levelEnvironment (EMC)
1st and 2nd environments as per EN 61800-3
Radio interference levelmaximum motor cable length [I]
C2 ≤ 5 m
C3 ≤ 25 m m
Mounting position
Vertical
Altitude
0 - 1000 m above sea level
Above 1000 m: 1% derating for every 100 m
max. 4000 m m
Degree of Protection
IP20/NEMA 0
Protection against direct contact
BGV A3 (VBG4, finger- and back-of-hand proof)
SupplyRated operational voltage [Ue]
230 V AC, 3-phase
240 V AC, 3-phase
SupplyMains voltage (50/60Hz) [ULN]
200 (-10%) - 240 (+10%) V
SupplyInput current (150% overload) [ILN]
12.1 A
SupplySystem configuration
AC supply systems with earthed center point
SupplySupply frequency [fLN]
50/60 Hz
SupplyFrequency range [fLN]
48 - 62 Hz
SupplyMains switch-on frequency
Maximum of one time every 30 seconds
Power sectionFunction
Variable frequency drive with internal DC link and IGBT inverter
Power sectionOverload current (150% overload) [IL]
15.75 A
Power sectionmax. starting current (High Overload) [IH]
175 %
Power sectionNote about max. starting current
for 2 seconds every 20 seconds
Power sectionOutput voltage with Ve[U2]
230 V AC, 3-phase
240 V AC, 3-phase
Power sectionOutput Frequency [f2]
0 - 50/60 (max. 500) Hz
Power sectionSwitching frequency [fPWM]
16
adjustable 4 - 32 (audible) kHz
Power sectionOperation Mode
U/f control
Speed control with slip compensation
Power sectionFrequency resolution (setpoint value) [Δf]
0.1 Hz
Power sectionRated operational currentAt 150% overload [Ie]
10.5 A
Power sectionNote
Rated operational current at an operating frequency of 16 kHz and an ambient air temperature of +50 °C
Power sectionPower lossHeat dissipation at rated operational current Ie=150 % [PV]
90.2 W
Power sectionEfficiency [η]
95.9 %
Power sectionMaximum leakage current to ground (PE) without motor [IPE]
< 1 mA
Power sectionFitted with
Radio interference suppression filter
Brake chopper
7-digital display assembly
Power sectionFrame size
FS2
Motor feederNote
for normal internally and externally ventilated 4 pole, three-phase asynchronous motors with 1500 rpm-1at 50 Hz or 1800 min-1at 60 Hz
Motor feederNote
Overload cycle for 60 s every 600 s
Motor feederNote
at 230 V, 50 Hz
Motor feeder150 % Overload [P]
2.2 kW
Motor feederNote
at 220 - 240 V, 60 Hz
Motor feeder150 % Overload [P]
3 HP
Motor feedermaximum permissible cable length [I]
screened: 100
screened, with motor choke: 200
unscreened: 150
unscreened, with motor choke: 300 m
Motor feederApparent powerApparent power at rated operation 230 V [S]
4.18 kVA
Motor feederApparent powerApparent power at rated operation 240 V [S]
4.36 kVA
Motor feederBraking functionStandard braking torque
max. 30 % MN
Motor feederBraking functionDC braking torque
max. 100% of rated operational current Ie,variable
Motor feederBraking functionBraking torque with external braking resistance
Max. 100% of rated operational current Iewith external braking resistor
Motor feederBraking functionminimum external braking resistance [Rmin]
50 Ω
Motor feederBraking functionSwitch-on threshold for the braking transistor [UDC]
390 V DC V
Reference voltage [Us]
10 V DC (max. 10 mA) V
Analog inputs
2, parameterizable, 0 - 10 V DC, 0/4 - 20 mA
Analog outputs
1, parameterizable, 0 - 10 V
Digital inputs
4, parameterizable, max. 30 V DC
Digital outputs
1, parameterizable, 24 V DC
Relay outputs
1, parameterizable, N/O, 6 A (250 V, AC-1) / 5 A (30 V, DC-1)
Interface/field bus (built-in)
OP-Bus (RS485)/Modbus RTU, CANopen®
Assigned switching and protective elements
Power WiringSafety device (fuse or miniature circuit-breaker)IEC (Type B, gG), 150 %
FAZ-B16/3
Power WiringSafety device (fuse or miniature circuit-breaker)UL (Class CC or J)
15 A
Power WiringMains contactor150 % overload (CT/IH, at 50 °C)
DILM7
DILM7-…
Power WiringMain choke150 % overload (CT/IH, at 50 °C)
DX-LN3-016
DC link connectionBraking resistance10 % duty factor (DF)
DX-BR050-0K4
DC link connectionBraking resistance20 % duty factor (DF)
DX-BR050-0K8
DC link connectionBraking resistance40 % duty factor (DF)
DX-BR047-3K1
Motor feedermotor choke150 % overload (CT/IH, at 50 °C)
DX-LM3-016
Motor feederSine filter150 % overload (CT/IH, at 50 °C)
DX-SIN3-016