Product name
Eaton xComfort BF small distribution board
Product Length/Depth
140 millimetre
Product height
630 millimetre
Product width
600 millimetre
Product weight
10.2 kilogram
Certifications
IEC/EN 62208
IEC/EN 61439-3
IEC/EN 61439-1
Product Tradename
xComfort BF
Product Type
Small distribution board
Type
Basic deviceBF flat DBOInstallation distribution boards
Application
Indoor (installation site)
Color
Traffic white (RAL 9016)
White
Technical Data - Electrical
Voltage rating at AC
415 V AC
Frequency rating of contacts
50 Hz / 60 Hz
Technical Data - Mechanical
Width in number of modular spacings
24
Mounting method
Flush mounted (plaster)
Hollow wall
Flush mounting
DIN-rail
Hollow-wall mounting and flush mounting
Material
Sheet steel, powder-coated
Degree of protection
IP30
IK07 (impact resistance)
Number of module space units per row
24
Terminal type
Screw terminals
PE and N terminal number and cross section
N: 2 x 25 mm² + 13 x 16 mm²
PE: 2 x 25 mm² + 13 x 16 mm²
Cover/door type
Door
Single
Module rack type
Rail frame
Protective shrouding material
Metal
Temperature-rise verification as per IEC 60890
Heat diss. ambient 35°C delta T:20°C flush mount individ. encl. top(IEC 60890)
41 W
Heat diss. ambient 35°C delta T:35°C flush mount individ. encl. top(IEC 60890)
82 W
Design verification as per IEC/EN 61439 - technical data
Ambient operating temperature details
-5 °C - 40 °C
Design verification as per IEC/EN 61439
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2.5 Lifting
Does not apply to enclosures without lifting aids.
10.2.6 Mechanical impact
IK07
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
IP30
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
< 0.1 Ω; meets the product standard's requirements.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Ui = 415 V AC
10.9.3 Impulse withstand voltage
Does not apply to basic enclosures as defined in EN 62208.
10.9.4 Testing of enclosures made of insulating material
Does not apply to metal enclosures.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.
Features
EMC-version
Earthing terminal block
Neutral terminal block
Fitted with:
Door with Profi-Line three-point turn-lock
Neutral-/protective conductor terminal
Front plates
Wall trough with door frame
DIN rail mounting frame
Protection class
I (earthed)
Special features
IP30Protection Class ISteel sheet enclosure white (RAL 9016)
Used with
Basic device
Installation distribution board
BF flat distribution board