Standards
EN60947-4-1, EN60947-5-1
Lifespan, mechanicalAC operated [Operations]
1 x 106
Lifespan, mechanicalDC operated [Operations]
1 x 106
Operating frequency, mechanicalAC operated [Operations/h]
1000
Operating frequency, mechanicalDC operated [Operations/h]
1000
Maximum operating frequencyelectrical (Contactors without overload relay) [Operations/h]
100
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperatureOpen
-40 - +70 °C
Ambient temperatureEnclosed
- 40 - + 40 °C
Ambient temperatureStorage
- 40 - + 80 °C
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 10 msMain contactsN/O contact
10 g
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 10 msAuxiliary contactsN/O contact
10 g
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 10 msAuxiliary contactsN/C contact
8 g
Degree of Protection
IP00
Protection against direct contact when actuated from front (EN 50274)
Covers on main terminals safeguarded against accidental contact with fingers or back of hand
Terminal capacity main cableFlexible with cable lug
50 - 240 mm2
Terminal capacity main cableStranded with cable lug
50 - 240 mm2
Terminal capacity main cableSolid or stranded
1/0 - 500 MCM AWG
Terminal capacity main cableBusbar [Width]
40 mm
Main cable connection screw/bolt
M10
Terminal capacity control circuit cablesSolid
1 x (0.75 - 2.5)
2 x (0.75 - 2.5) mm2
Terminal capacity control circuit cablesFlexible with ferrule
1 x (0.75 - 2.5)
2 x (0.75 - 2.5) mm2
Terminal capacity control circuit cablesSolid or stranded
2 x (18 - 12) AWG
Control circuit cable connection screw/bolt
M3.5
ToolMain cableWidth across flats
16 mm
ToolControl circuit cablesPozidriv screwdriver
2 Size
ToolControl circuit cablesStandard screwdriver
0.8 x 5.5
1 x 6 mm
Rated impulse withstand voltage [Uimp]
8000 V
Overvoltage category/pollution degree
III/3
Rated insulation voltage [Ui]
1000 V DC
Rated operational voltage [Ue]
1000 V DC
Safe isolation to EN 61140Between control inputs and main contacts
1000 V
Safe isolation to EN 61140Between auxiliary contacts and main contacts
1000 V
Safe isolation to EN 61140between the contacts
1000 V
Breaking capacity220 V 230 V
900 A
Breaking capacity380 V 400 V
900 A
Breaking capacity500 V
900 A
Breaking capacity660 V 690 V
900 A
Breaking capacity1000 V
900 A
Short-circuit ratingShort-circuit protection maximum fuseType “2” coordination400 V DC [gR 1000 VDC]
900 (max. short-circuit current 6 kA) A
Short-circuit ratingShort-circuit protection maximum fuseType “2” coordination690 V DC [gR 1000 VDC]
900 (max. short-circuit current 6 kA) A
Short-circuit ratingShort-circuit protection maximum fuseType “2” coordination1000 V DC [gR 1000 VDC]
900 (max. short-circuit current 6 kA) A
Short-circuit ratingShort-circuit protection maximum fuseType “1” coordination400 V DC [gR 1000 VDC]
900 (max. short-circuit current 30 kA) A
Short-circuit ratingShort-circuit protection maximum fuseType “1” coordination690 V DC [gR 1000 VDC]
900 (max. short-circuit current 30 kA) A
Short-circuit ratingShort-circuit protection maximum fuseType “1” coordination1000 V DC [gR 1000 VDC]
900 (max. short-circuit current 30 kA) A
Rated operational current, openDC-1Notes
Ieat 60 °C
Rated operational current, openDC-11000 V [Ie]
600 A
Voltage toleranceUS
110 - 250 V 40-60 Hz
110 - 350 V DC
Voltage toleranceAC operated [Pick-up]
0.7 x US min- 1.15 x US maxx US
Voltage toleranceDC operated [Pick-up]
0.7 x US min- 1.15 x US maxx US
Voltage toleranceAC operated [Drop-out]
0.2 x US max- 0.6 x US minx US
Voltage toleranceDC operated [Drop-out]
0.2 x US max- 0.6 x US minx US
Voltage toleranceActuation directly from PLCUC
24 V DC
Voltage toleranceActuation directly from PLCUCmin - max
15 - 31,2 V DC
Power consumption of the coil in a cold state and 1.0 x USNote on power consumption
Control transformer with uk≦ 6%
Power consumption of the coil in a cold state and 1.0 x USPull-in power [Pick-up]
600 VA
Power consumption of the coil in a cold state and 1.0 x USPull-in power [Pick-up]
550 W
Power consumption of the coil in a cold state and 1.0 x USSealing power [Sealing]
18 VA
Power consumption of the coil in a cold state and 1.0 x USSealing power [Sealing]
9.5 W
Changeover time at 100 % US(recommended value)Main contactsClosing delay
80 ms
Changeover time at 100 % US(recommended value)Main contactsOpening delay
40 ms
PLC signal level (A3 - A4) to IEC/EN 61131-2 (type 2)High
15 V
PLC signal level (A3 - A4) to IEC/EN 61131-2 (type 2)Low
5 V
Electromagnetic compatibility (EMC)
Electromagnetic compatibility
This product is designed for operation in industrial environments (environment A). Its use in residential environments (environment B) may cause radio-frequency interference, requiring additional noise suppression measures.
Rating data for approved types
Switching capacityMaximum motor ratingSingle-phaseGeneral use
600 A
Auxiliary contactsPilot DutyAC operated
A600
Auxiliary contactsPilot DutyDC operated
P300
Auxiliary contactsGeneral UseAC
600 V
Auxiliary contactsGeneral UseAC
15 A
Auxiliary contactsGeneral UseDC
250 V
Auxiliary contactsGeneral UseDC
1 A