Standards
EN 55011, EN 55022, IEC/EN 61000-4, IEC 60068-2-6, IEC 60068-2-27
Dimensions (W x H x D)
107.5 x 90 x 72 (6 PE) mm
Mounting
Top-hat rail IEC/EN 60715, 35 mm or screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Solid
0.2/4 (AWG 22 - 12) mm2
Flexible with ferrule
0.2/2.5 (AWG 22 - 12) mm2
Standard screwdriver
0.8 x 3.5 mm
Max. tightening torque
0.6 Nm
Climatic environmental conditions
Operating ambient temperature
In accordance with IEC 60068-2-1, -25 - +55 °C
Condensation
Take appropriate measures to prevent condensation
LCD display (clearly legible)
0 - 55 °C
Storage [ϑ]
In accordance with IEC 60068-2-1, -2, -14
-40 - +70 °C
relative humidity
in accordance with IEC 60068-2-30, IEC 60068-2-78
5 - 95 %
Air pressure (operation)
795 - 1080 hPa
Ambient conditions, mechanical
Protection type (IEC/EN 60529, EN50178, VBG 4)
IP20
Vibrations
In accordance with IEC 60068-2-6
constant amplitude 0.15 mm: 10 - 57
constant acceleration 2 g: 57 - 150 Hz
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms
18 Impacts
Drop to IEC/EN 60068-2-31 [Drop height]
50 mm
Free fall, packaged (IEC/EN 60068-2-32)
1 m
Mounting position
Vertical or horizontal
Electromagnetic compatibility (EMC)
Overvoltage category/pollution degree
III/2
Electrostatic discharge (ESD)applied standard
nach IEC/EN 61000-4-2
Electrostatic discharge (ESD)Air discharge
8 kV
Electrostatic discharge (ESD)Contact discharge
6 kV
Electromagnetic fields (RFI) to IEC EN 61000-4-3
0.8 - 1.0 GHz: 10
1.4 - 2 GHz: 3
2.0 - 2.7 GHz: 1 V/m
Radio interference suppression
EN 55011 Class B
Burst
according to IEC/EN 61000-4-4 kV
power pulses (Surge)
according to IEC/EN 61000-4-5
1 kV (supply cables, symmetrical)
Immunity to line-conducted interference to (IEC/EN 61000-4-6)
10 V
Clearance in air and creepage distances
EN 50178, UL 508, CSA C22.2, No. 142
Insulation resistance
EN 50178
Back-up of real-time clock
Back-up of real-time clock
① Backup time (hours) with fully charged double layer capacitor
② Service life (years)
Accuracy of real-time clock to inputs
typ. ± 2 (± 0.2 h⁄Year) s/day
depending on ambient air temperature fluctuations of up to ± 5 s/day (± 0.5 h⁄year) are possible
Repetition accuracy of timing relays
Accuracy of timing relays (of values)
± 0.02 %
ResolutionRange “H:M”
1 min
Write cycles of the retentive memory
1012(read⁄write cycles)
Rated operational voltage [Ue]
24 DC (-15/+20%) V
Permissible range [Ue]
20.4 - 28.8 V DC
Protection against polarity reversal
yes
Input current
140 mA at Ue
Voltage dips
≤ In accordance with IEC 61131-2
≤ 20 ms
Power loss [P]
Normally 3.4 W
Inputs can be used as analog inputs
4 (I7, I8, I11, I12)
Status Display
LCD-Display
Potential isolation
from power supply: no
between digital inputs: no
from the outputs: yes
to interface/memory card: no
to easyLink: no
to easyNet: yes
Rated operational voltage [Ue]
24 V DC
Input voltage
Signal 0: ≦ 5 (I1 - I6, I9, I10, ≦ 8 (I7, I8, I11, I12)
Signal 1: ≧ 15 (I1 - I6, I9, I10), ≧ 8 (I7, I8, I11, I12) V DC
Input current at signal 1
I1 - I6, I9, I10: 3.3 (at 24 V DC)
I7, I8, I11, I12: 2.2 (at 24 V DC) mA
Deceleration time
20 (0 -> 1/1 -> 0, Debounce ON)
normally 0.025 (0 -> 1/1 -> 0, Debounce OFF, I1 - I4)
normally 0.25 (0 -> 1/1 -> 0, Debounce OFF, I5, I6, I9, I10)
normally 0.15 (0 -> 1/1 -> 0, Debounce OFF, I7, I8, I11, I12) ms
Cable length
100 (unshielded) m
Frequency counterNumber
4 (I1, I2, I3, I4)
Frequency counterCounter frequency
≦ 5 kHz
Frequency counterPulse shape
Square
Frequency counterPulse pause ratio
1:1
Frequency counterCable length
≦ 20 (screened) m
Incremental counterNumber of counter inputs
2 (I1 + I2, I3 + I4)
Incremental counterCounter frequency
≦ 3 kHz
Incremental counterPulse shape
Square
Incremental counterSignal offset
90°
Incremental counterPulse pause ratio
1:1
Rapid counter inputsNumber
4 (I1, I2, I3, I4)
Rapid counter inputsCable length
≦ 20 (screened) m
Rapid counter inputsCounter frequency
≦ 5 kHz
Rapid counter inputsPulse shape
Square
Rapid counter inputsPulse pause ratio
1:1
Status Display
LCD-Display
Number
4 (I7, I8, I11, I12)
Potential isolation
from power supply: no
between digital inputs: no
from the outputs: yes
to interface/memory card: no
to easyLink: no
to easyNet: yes
Resolution
0.01 V analog
0.01 V digital
10 Bit (value 0 - 1023)
Accuracy of actual valuetwo devices from series
± 3 %
Accuracy of actual valueWithin a single device
± 2, (I7, I8, I11, I12) ± 0.12 V %
Conversion time, analog/digital
each CPU cycle ms
Cable length
≦ 30, screened m
Rated operational voltage [Ue]
24 V DC
Permissible range [Ue]
20.4 - 28.8 V DC
Supply current
Norm./max. 18/32 at signal 0
24/44 at signal 1 mA
Protection against polarity reversal
yes (Notice: A short-circuit will result if 0 V or earth is applied to the outputs in the event that the supply voltage is connected to the wrong poles.)
Potential isolation
from power supply: yes
From the inputs: yes
between digital inputs: no
to the interface: yes
to easyLink: yes
to easyNet: yes
Rated operational current at signal „1” DC per channel [Ie]
max. 0.5 A
Lamp load without Rvper channel
3 (Q1 - Q4)
5 (Q5 - Q8) W
Residual current on 0 signal per channel
< 0.1 mA
Max. output voltage
2.5 (signal 0 at external load < 10 MΩ)
U = Ue- 1 V (signal 1 at Ie= 0.5 A) V
Short-circuit protection
Yes, electronic (Q1 - Q4), thermal (Q5 - Q8)
Short-circuit tripping current for Ra≦ 10 mΩ
0.7 ≦ Ie≦ 2 per output
depending on number of active channels and their load A
Total short-circuit current
8 A
Peak short-circuit current
16 A
Max. operating frequency with constant resistive load
40000 Operations/h
Parallel connection of outputsWith resistive load, inductive load with external suppressor circuit, combination within a group
Group 1: Q1 to Q4
Group 2: Q5 - Q8
Parallel connection of outputsNumber of outputs [max.]
4
Parallel connection of outputsMax. total current
Group 1: Q1 - Q4 A
Output status indication
LCD-display
Inductive load to EN 60947-5-1Without external suppressor circuitT0.95 = 1 ms, R = 48 Ω, L = 16 mHUtilization factor
0.25 g
Inductive load to EN 60947-5-1Without external suppressor circuitT0.95 = 1 ms, R = 48 Ω, L = 16 mHDuty factor
100 % DF
Inductive load to EN 60947-5-1Without external suppressor circuitT0.95 = 1 ms, R = 48 Ω, L = 16 mHMax. switching frequency f = 0.5 Hz (max. DF = 50 %)
1500 Operations
Inductive load to EN 60947-5-1Without external suppressor circuitDC-13, T0.95 = 72 ms, R = 48 Ω, L = 1.15 HUtilization factor
0.25 g
Inductive load to EN 60947-5-1Without external suppressor circuitDC-13, T0.95 = 72 ms, R = 48 Ω, L = 1.15 HDuty factor
100 % DF
Inductive load to EN 60947-5-1Without external suppressor circuitDC-13, T0.95 = 72 ms, R = 48 Ω, L = 1.15 HMax. switching frequency f = 0.5 Hz (max. DF = 50 %)
1500 Operations
Inductive load to EN 60947-5-1Without external suppressor circuitT0.95 = 15 ms, R = 48 Ω, L = 0.24 HUtilization factor
0.25 g
Inductive load to EN 60947-5-1Without external suppressor circuitT0.95 = 15 ms, R = 48 Ω, L = 0.24 HDuty factor
100 % DF
Inductive load to EN 60947-5-1Without external suppressor circuitT0.95 = 15 ms, R = 48 Ω, L = 0.24 HMax. switching frequency f = 0.5 Hz (max. DF = 50 %)
1500 Operations
Inductive load to EN 60947-5-1With external suppressor circuitUtilization factor
1 g
Inductive load to EN 60947-5-1With external suppressor circuitDuty factor
100 % DF
Inductive load to EN 60947-5-1With external suppressor circuitMax. switching frequency, max. duty factor
Depending on the suppressor circuit Operations
Data transfer rate/distance
1000 KBit/s, 6 m
500 KBit/s, 25 m
250 Kbit/s, 40 m
125 Kbit/s, 300 m
50 KBit/s, 300 m
20 KBit/s, 700 m
10 KBit/s, 1000 m
Lengths from 40 m can be obtained only with cables with reinforced cross-section and terminal adapter.
Potential isolation
from power supply POW: yes
From the inputs: yes
from the outputs: yes
to easyLink: yes
to the interface: yes
Bus termination (first and last station)
yes
Terminal types
RJ45, 8-polig
Terminal capacity
up to 1000 m, < 16 mΩ/m: 1.5 (AWG: 16)
up to 600 m, < 26 mΩ/m: 0.75 - 0.8 (AWG: 18)
up to 600 m, < 26 mΩ/m: 0.5 - 0.6 (AWG: 20, 19)
up to 400 m, < 40 mΩ/m: 0.34 - 0.5 (AWG: 22, 21, 20)
up to 250 m, < 60 mΩ/m: 0.25 - 0.34 (AWG: 23, 22)
up to 175 m, < 70 mΩ/m: 0.13 (AWG: 26)
up to 40 m, < 140 mΩ/m: 1.5 (AWG: 16)