DUCT HUMIDITY- AND TEMPERATURE SENSORS KFTF-MBCalibratable duct humidity and temperature sensor KFTF-T3 (± 2.0%) withModbus RTU connection, in a resistant IP65 plastic housing with quick-locking screws and M16 cable gland for cable connection and a plasticsinter filter (exchangeable). Including mounting flange to detect therelative humidity (0…100% RH) and the temperature (–35...+80 °C) insidea tube, including various parameters in the humidity measurement. Theduct sensor is applied in a non-aggressive and dust-free environment andis suitable for installation in ceilings, ducts and devices.International SI units (default) can be switched to Imperial (viaModbus).Measuring range: 0...100 % RH (humidity) / – 35...0 % (20.....+70 °C / –22...

More details


OPTIONS AND ACCESSORIES FC302 FC202 FC102 - DANFOSS DRIVES

Brand new product in its original packaging covered by the warranties and certifications provided by DANFOSS DRIVES

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



DUCT HUMIDITY- AND TEMPERATURE SENSORS KFTF-MB
Calibratable duct humidity and temperature sensor KFTF-T3 (± 2.0%) with
Modbus RTU connection, in a resistant IP65 plastic housing with quick-
locking screws and M16 cable gland for cable connection and a plastic
sinter filter (exchangeable). Including mounting flange to detect the
relative humidity (0…100% RH) and the temperature (–35...+80 °C) inside
a tube, including various parameters in the humidity measurement. The
duct sensor is applied in a non-aggressive and dust-free environment and
is suitable for installation in ceilings, ducts and devices.
International SI units (default) can be switched to Imperial (via
Modbus).
Measuring range: 0...100 % RH (humidity) / – 35...+80 °C (temperature)
Medium: clean air and non-aggressive, non-combustible gases
Deviation, humidity: typical ± 2.0 % (20...80 % RH) at +25 °C, otherwise
± 3.0 %
Deviation, temperature: typical ± 0.2 K at +25 °C
Zero point offset: ± 10 % RH (humidity) / ± 5 °C (temperature)
Power: 24VAC (± 20%) / 15…36VDC - 24DC <1,2W
Operation temperature: –30...+70 °C / –22...+158 °F
T3-IP65 plastic housing with two M20 cable glands
Housing dimensions: 108 x 78.5 x 43.3 mm / 4.25 x 3.1 x 1.7 in

Product details

Gross weight0.385 Kilogram
Net weight0.23 Kilogram
Volume4.285 Liter
EAN5715253547046
Gross weight0.385 Kilogram
Net weight0.23 Kilogram
Volume4.285 Liter
EAN5715253547046

OptionsControl related options
OptionsControl related options

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.