EATON - MOELLER NZM2/3-XU60AC 259495 Y7-259495 - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

NZM2/3-XU60AC 259495 Y7-259495 EATON ELECTRIC Undervoltage release, 60VAC

Reference: NZM2/3-XU60AC

Code: 259495

Catalog Number: Y7-259495

Manufacturer: EATON - MOELLER

Description:

Undervoltage release, 60VAC
NZM2/3-XU60AC
Eaton Moeller series NZM - Molded Case Circuit Breaker. Undervoltage release, 60VAC, 2/3
Optional accessories for the circuit-breaker series NZM offers a comprehensive portfolio of application options for use world wide. The mounting is always flexible and easy thanks to the modular function groups. Notes: non-delayed disconnection of NZM circuit-breaker or N switch-disconnector when the control voltage sinks below 35-70% US. For use with Emergency-Stop devices in conjunction with emergency-stop button. when the undervoltage release is de-energized, accidental contact with the main contacts of the switch during attempts to switch on is safely prevented . Undervoltage releases cannot be installed simultaneously with NZM..-XHIV.. early-make auxiliary contact or NZM..-XA.. shunt release. Can be used for: NZM2(-4), N(N/O)2(-4), NZM3(-4), N(N/O)3(-4)

Categories:

  • Low-voltage industrial components > Under voltage coil
  • EATON - MOELLER > Circuit Breakers NZM

Brand new product in its original packaging covered by the warranties and certifications provided by EATON - MOELLER

  • More Info
  • ETIM
  • PDF
  • Reviews
Guarantee, repair and return.

Unit Price: 118,63 €

This price is per unit and is the net value (not including taxes if applicable).

Calculate price by quantity

QuantityPrice

Standard lead time: 3 weeks.

  • These delivery times are an estimate any may vary when the item order has been processed.

LAST VIEWED

MORE INFO

General specifications

Product Name
Eaton Moeller series NZM release
Catalog Number
259495
Model Code
NZM2/3-XU60AC
EAN
4015082594954
Product Length/Depth
42 mm
Product Height
90 mm
Product Width
30 mm
Product Weight
0.064 kg
Compliances
IEC
UL/CSA
RoHS conform
Certifications
CE marking
CSA certified
CSA (File No. 22086)
CSA (Class No. 1437-01)
IEC60947
CSA-C22.2 No. 5-09
UL (File No. E140305)
UL listed
UL489
UL (Category Control Number DIHS)

Product specifications

Type
AccessoryUndervoltage release
Special features
Non-delayed disconnection of NZM circuit-breaker or N switch-disconnector when the control voltage sinks below 35 – 70% US.For use with emergency-stop devices in connection with an emergency-stop button.When the under-voltage trip is switched off, accidental contact with the circuit breaker’s primary contacts is prevented when switched on.Undervoltage releases cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XA... shunt release.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Electric connection type
Screw connection
Frame
NZM2/3
Used with
NZM3(-4), N(S)3(-4)
NZM2(-4), N(S)2(-4)
Number of contacts (normally open contacts)
0
Rated control supply voltage
60 V 50/60 Hz
Rated control supply voltage (Us) at AC, 50 Hz - max
60 V
Rated control supply voltage (Us) at AC, 50 Hz - min
60 V
Rated control supply voltage (Us) at AC, 60 Hz - max
60 V
Rated control supply voltage (Us) at AC, 60 Hz - min
60 V
Suitable for
Off-load switch
Connection type
With bolt connection
Voltage type
AC
Rated control supply voltage (Us) at DC - max
0 V
Rated control supply voltage (Us) at DC - min
0 V
Number of contacts (normally closed contacts)
0
Number of contacts (change-over contacts)
0
Undelayed short-circuit release - min
0 A
Undelayed short-circuit release - max
0 A

ETIM for 259495 Low-voltage industrial controls and switchgear (EC001022)

Feature nameRated control supply voltage AC 50 Hz (EF003978)
Feature value60 V
Feature nameRated control supply voltage AC 60 Hz (EF003979)
Feature value60 V
Feature nameRated control supply voltage DC (EF003980)
Feature value0 V
Feature nameVoltage type for actuating (EF008242)
Feature valueAC
Feature nameType of electric connection (EF003961)
Feature valueScrew connection
Feature nameNumber of contacts as normally open contact (EF008256)
Feature value0
Feature nameNumber of contacts as normally closed contact (EF008255)
Feature value0
Feature nameNumber of contacts as change-over contact (EF008257)
Feature value0
Feature nameDelayed (EF001541)
Feature valuefalse
Feature nameSuitable for power circuit breaker (EF005863)
Feature valuefalse
Feature nameSuitable for off-load switch (EF001543)
Feature valuetrue
Feature nameSuitable for motor safety switch (EF005826)
Feature valuefalse
Feature nameSuitable for overload relay (EF001545)
Feature valuefalse

DATASHEET - PDF

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.