EATON - MOELLER NZM4-XA48AC/DC 266448 Y7-266448 - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

NZM4-XA48AC/DC 266448 Y7-266448 EATON ELECTRIC Shunt release, 48VAC/DC

Reference: NZM4-XA48AC/DC

Code: 266448

Catalog Number: Y7-266448

Manufacturer: EATON - MOELLER

Description:

Shunt release, 48VAC/DC
NZM4-XA48AC/DC
Eaton Moeller series NZM - Molded Case Circuit Breaker. Shunt release, 48VAC/DC, 4
Optional accessories for the circuit-breaker series NZM offers a comprehensive portfolio of application options for use world wide. The mounting is always flexible and easy thanks to the modular function groups. Notes: switches are tripped by a voltage pulse or by the application of uninterrupted voltage. If the shunt release is energized, accidental contact with the main contacts of the switch during attempts to switch on is safely prevented.undervoltage releases cannot be installed simultaneously with NZM..-XHIV.. early-make auxiliary contact or NZM..-XU.. shunt release. Can be used for: NZM4(-4), N(N/O)4(-4)

Categories:

  • Low-voltage industrial components > Shunt release (for power circuit breaker)
  • EATON - MOELLER > Circuit Breakers NZM

Brand new product in its original packaging covered by the warranties and certifications provided by EATON - MOELLER

  • More Info
  • ETIM
  • PDF
  • Reviews
Guarantee, repair and return.

Unit Price: 145,08 €

This price is per unit and is the net value (not including taxes if applicable).

Calculate price by quantity

QuantityPrice

Standard lead time: 3 weeks.

  • These delivery times are an estimate any may vary when the item order has been processed.

LAST VIEWED

MORE INFO

General specifications

Product Name
Eaton Moeller series NZM release
Catalog Number
266448
Model Code
NZM4-XA48AC/DC
EAN
4015082664480
Product Length/Depth
107 mm
Product Height
51 mm
Product Width
64 mm
Product Weight
0.218 kg
Compliances
UL/CSA
IEC
RoHS conform
Certifications
CE marking
IEC60947
CSA-C22.2 No. 5-09
CSA certified
CSA (File No. 22086)
CSA (Class No. 1437-01)
UL (File No. E140305)
UL489
UL (Category Control Number DIHS)
UL listed

Product specifications

Type
Special features
  • Switches are tripped by a voltage pulse or by the application of uninterrupted voltage.
  • If the shunt trip is live, contact with the circuit breaker’s primary contacts is prevented when switched on.
  • Shunt releases cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XU... undervoltage release.
Voltage rating
0.7 - 1.1 x Us
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Electric connection type
Screw connection
Frame
NZM4
Frequency rating
50 Hz / 60 Hz / 200 Hz / 400 Hz, DC (shunt release)
Used with
NZM4(-4), N(S)4(-4)
Minimum command time - max
15 ms
Minimum command time - min
10 ms
Number of contacts (normally open contacts)
0
Reaction time
22 ms
Pick-up power consumption (shunt release)
2.5 VA/W
Rated control supply voltage
48 V AC/DC
Rated control supply voltage (Us) at AC, 50 Hz - max
48 V
Rated control supply voltage (Us) at AC, 50 Hz - min
48 V
Rated control supply voltage (Us) at AC, 60 Hz - max
48 V
Rated control supply voltage (Us) at AC, 60 Hz - min
48 V
Suitable for
Off-load switch
Connection type
With bolt connection
Voltage type
AC/DC
Terminal capacity (solid/flexible conductor)
0.75 mm² - 2.5 mm² (1x) at shunt release with ferrule
18 - 14 AWG (1x) at shunt release
0.75 mm² - 2.5 mm² (1x) for undervoltage releases, off-delayed with ferrule
0.75 mm² - 2.5 mm² (2x) for undervoltage releases, off-delayed with ferrule
18 - 14 AWG (2x) at shunt release
0.75 mm² - 2.5 mm² (2x) at shunt release with ferrule
18 - 14 AWG (1x) for undervoltage releases, off-delayed
18 - 14 AWG (2x) for undervoltage releases, off-delayed
Rated control supply voltage (Us) at DC - max
48 V
Rated control supply voltage (Us) at DC - min
48 V
Voltage rating at AC (x Us) - max
1.1
Voltage rating at AC (x Us) - min
.7
Number of contacts (normally closed contacts)
0
Number of contacts (change-over contacts)
0
Undelayed short-circuit release - min
0 A
Undelayed short-circuit release - max
0 A
Time on duty - max
∞
Rated control voltage (relay contacts)
48 V DC
48 V AC

ETIM for 266448 Low-voltage industrial controls and switchgear (EC001023)

Feature nameRated control supply voltage AC 50 Hz (EF003978)
Feature value48 V
Feature nameRated control supply voltage AC 60 Hz (EF003979)
Feature value48 V
Feature nameRated control supply voltage DC (EF003980)
Feature value48 V
Feature nameVoltage type for actuating (EF008242)
Feature valueAC/DC
Feature nameInitial value of the undelayed short-circuit release - setting range (EF008187)
Feature value0 A
Feature nameEnd value adjustment range undelayed short-circuit release (EF008188)
Feature value0 A
Feature nameType of electric connection (EF003961)
Feature valueScrew connection
Feature nameNumber of contacts as normally open contact (EF008256)
Feature value0
Feature nameNumber of contacts as normally closed contact (EF008255)
Feature value0
Feature nameNumber of contacts as change-over contact (EF008257)
Feature value0
Feature nameSuitable for power circuit breaker (EF005863)
Feature valueNo
Feature nameSuitable for off-load switch (EF001543)
Feature valueYes
Feature nameSuitable for motor safety switch (EF005826)
Feature valueNo
Feature nameSuitable for overload relay (EF001545)
Feature valueNo

DATASHEET - PDF

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.