EATON - MOELLER NZMS1-A80-SVE 112786 Y7-112786 - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

NZMS1-A80-SVE 112786 Y7-112786 EATON ELECTRIC Circuit-breaker 3-pole 80 A, system/cable protection, withdraw..

Reference: NZMS1-A80-SVE

Code: 112786

Catalog Number: Y7-112786

Manufacturer: EATON - MOELLER

Description:

Circuit-breaker 3-pole 80 A, system/cable protection, withdrawable unit
NZMS1-A80-SVE
Circuit-breaker 3-pole 80A, system/cable protection, withdrawable unit
Series NZM..-A circuit-breakers cover all application cases with just four compact sizes and are suitable for the IEC market. Modular function groups always make mounting flexible. With thermomagnetic releases for systems and cable protection.

Categories:

  • Low-voltage industrial components > Power circuit-breaker for trafo/generator/installation protection
  • EATON - MOELLER > Circuit Breakers NZM

Brand new product in its original packaging covered by the warranties and certifications provided by EATON - MOELLER

  • More Info
  • ETIM
  • PDF
  • Reviews
Guarantee, repair and return.

Unit Price: 548,58 €

This price is per unit and is the net value (not including taxes if applicable).

Calculate price by quantity

QuantityPrice

Standard lead time: 3 weeks.

  • These delivery times are an estimate any may vary when the item order has been processed.

LAST VIEWED

MORE INFO

Circuit-breaker 3-pole 80A, system/cable protection, withdrawable unit
Series NZM..-A circuit-breakers cover all application cases with just four compact sizes and are suitable for the IEC market. Modular function groups always make mounting flexible. With thermomagnetic releases for systems and cable protection.

General specifications
Product name
Eaton Moeller series NZM molded case circuit breaker thermo-magnetic
Part no.
NZMS1-A80-SVE
EAN
4015081123261
Product Length/Depth
88 millimetre
Product height
145 millimetre
Product width
90 millimetre
Product weight
1.195 kilogram
Compliances
RoHS conform
Product Tradename
NZM
Product Type
Molded case circuit breaker
Product Sub Type
Thermo-magnetic
Delivery program
Number of poles
Three-pole
Amperage Rating
80 A
Features
Protection unit
Special features
Rated current = rated uninterrupted current: 80 A
Technical Data - Electrical
Voltage rating
690 V - 690 V
Instantaneous current setting (Ii) - min
480 A
Instantaneous current setting (Ii) - max
800 A
Overload current setting (Ir) - min
63 A
Overload current setting (Ir) - max
80 A
Short delay current setting (Isd) - min
0 A
Short delay current setting (Isd) - max
0 A
Short-circuit release non-delayed setting - min
6 A
Short-circuit release non-delayed setting - max
10 A
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz
70 kA
Electrical connection type of main circuit
Frame clamp
Handle type
Rocker lever
Technical Data - Mechanical
Mounting Method
Built-in device plug-in technique
Degree of protection
IP20
Number of auxiliary contacts (change-over contacts)
0
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
0
Position of connection for main current circuit
Back side
Special features
Rated current = rated uninterrupted current: 80 A
Design verification as per IEC/EN 61439 - technical data
Equipment heat dissipation, current-dependent
16.32 W
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
70 °C
Ambient storage temperature - min
40 °C
Ambient storage temperature - max
70 °C
Design verification as per IEC/EN 61439
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

ETIM for 112786 Low-voltage industrial controls and switchgear (EC000228)

Feature nameRated permanent current Iu (EF001389)
Feature value80 A
Feature nameRated voltage (EF003977)
Feature value690 V
Feature nameRated short-circuit breaking capacity Icu at 400 V, 50 Hz (EF007048)
Feature value70 kA
Feature nameOverload release current setting (EF002336)
Feature value63 A
Feature nameAdjustment range short-term delayed short-circuit release (EF007129)
Feature value0 A
Feature nameAdjustment range undelayed short-circuit release (EF007131)
Feature value480 A
Feature nameDevice construction (EF008240)
Feature valueBuilt-in device plug-in technique
Feature nameIntegrated earth fault protection (EF007296)
Feature valueNo
Feature nameType of electrical connection of main circuit (EF006819)
Feature valueFrame clamp
Feature nameSuitable for DIN rail (top hat rail) mounting (EF007250)
Feature valueNo
Feature nameDIN rail (top hat rail) mounting optional (EF008904)
Feature valueNo
Feature nameNumber of auxiliary contacts as normally closed contact (EF001377)
Feature value0
Feature nameNumber of auxiliary contacts as normally open contact (EF001376)
Feature value0
Feature nameNumber of auxiliary contacts as change-over contact (EF003531)
Feature value0
Feature nameWith switched-off indicator (EF007006)
Feature valueNo
Feature nameWith integrated under voltage release (EF001390)
Feature valueNo
Feature nameNumber of poles (EF001391)
Feature value3
Feature namePosition of connection for main current circuit (EF006671)
Feature valueBack
Feature nameType of control element (EF006976)
Feature valueRocker lever
Feature nameComplete device with protection unit (EF008906)
Feature valueYes
Feature nameMotor drive integrated (EF006697)
Feature valueNo
Feature nameMotor drive optional (EF007386)
Feature valueNo
Feature nameDegree of protection (IP) (EF005474)
Feature valueIP20

DATASHEET - PDF

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.