Selected parameters MODULE TYPE Input/Output module HOUSING DIN-rail POWER SUPPLY AC I/O TYPE Voltage input NUMBER OF I/O 4 Others MODULE TYPE Input/Output module HOUSING H4 (W72) I/O TYPE 6-265 VAC/VDC input / 5A SPST relay POWER SUPPLY 24 VAC MAIN CHARACTERISTICS Input/Output module with 2 voltage inputs and 2 relay outputs
Home > CARLO GAVAZZI
Brand new product in its original packaging covered by the warranties and certifications provided by CARLO GAVAZZI
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
Transceiver forDigital Signals
Type G 3440 4443
• 4-channel monostable transceiver
• 2 opto-isolated voltage inputs:
10 to 265 VAC/DC
• 2 SPST relay outputs
• Load 2 x 5 A/250 VAC
• H4-housing
• For mounting on DIN-rail (EN 50022)
• LED-indications for supply, Dupline® carrier, inputs and outputs
• AC or DC power supply
• Channel coding by GAP 1605
Product Description Ordering Key
G 3440 4443 024
Dupline®transceiverwith4 in-putsforAC/DCvoltages
and 2 SPST relay outputs.
Type: Dupline® H4-housing Transceiver
No. of channels Input/output type Power supply
Type Selection
SupplyOrdering no.
4 channels
2 x voltage input
2 x SPST relay outputs
24 VACG 3440 4443 024
115 VAC G 3440 4443 115
230 VAC G 3440 4443 230
15 to 30 VDCG 3440 4443 824
InputSpecifications
Inputs 2 voltage-type
Isolated in groups of 1 x 2
Input voltage VBB 10 to 265 VAC/DC Frequency range on AC45 to 400 Hz
Input voltage for signal “0”≤ 1 VAC/DC Input voltage for signal “1”≥ 10 VAC/DC
Input current for signal “1”Typ. 10 mA (VBB 10-18 VDC)
lower at other input voltages
Input current limiter Yes
Inrush current≤ 450 mA (@ VBB = 265 VDC) Operating time for signal “1” ≤ 1 pulse train + 3 ms
Operating time for signal “0” ≤ 1 pulse train + 50 ms
Cable length ≤ 25 m
Dielectric voltage
Inputs - Dupline® ≥ 4 kVAC (rms) Inputs - Outputs ≥ 4 kVAC (rms)
Output Specifications
Output2 SPST relays
Isolated in groups of 2 x 1
Contact ratings (AgCdO) µ (micro gap)
Resistive loads AC 1≤ 5 A/250 VAC (1250 VA) DC 1≤ 0.25 A/250 VDC (62 W) or≤ 5 A/25 VDC (125 W)
Inductive loads AC 152.5 A/230 VAC DC 135 A/24 VDC
Mechanical lifetime ≥ 30 x 106 operations
Electrical lifetime
(at max load)AC 1≥ 2 x 106 operations Operating frequency ≤ 7200 operations/h Dielectric voltage
Outputs - Dupline®≥ 4 kVAC (rms)
Response time1 pulse train
Specifications are subject to change without notice (23.10.2014) 1
| Title: | Size: | Type: |
|---|---|---|
| PDF CATALOG CARLO GAVAZZI EN.pdf | 3 Mbytes |
|
| Download general catalog |
|
No customer reviews for the moment.
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.