MURRELEKTRONIK 56440 56440 - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

56440 MURRELEKTRONIK MASI20 I/O MODULE K3

Reference: 56440

Manufacturer: MURRELEKTRONIK

Description:

MASI20 I/O MODULE K3
MASI20 I/O MODULE K34 digital inputs, 4 digital, passive safety outputs

Categories:

  • MURRELEKTRONIK > BUS systems

Brand new product in its original packaging covered by the warranties and certifications provided by MURRELEKTRONIK

  • More Info
  • PDF
  • Reviews
Guarantee, repair and return.

Unit Price: 245,58 €

This price is per unit and is the net value (not including taxes if applicable).

Calculate price by quantity

QuantityPrice

Standard lead time: 2-4 weeks.

  • These delivery times are an estimate any may vary when the item order has been processed.

MORE INFO

4 digital inputs, 4 digital, passive safety outputs
Art.No.: 56440
Weight: 0.174 kg
Ask question
Recommend Product
Digital inputs/outputs
Safe outputs (Safety)
Output groups up to PLd (EN ISO 13849-1) can be switched off via safety relays
DI4 - 0.2 A DO4 - 0.5 A (AB) (K3)
Current manuals can be downloaded at: www.murrelektronik.com
Input
Supply voltagealternatively (switchable) from AS-Interface or from 24 V DC (EN 61131-2) by additional supply
Sensor supply USmax.200 mA externally or from AS Interface, (short-circuit and overload protected)
Typefor 3-wire sensors or mechanical switches, PNP
Input currentmax. 10 mA
Technical Data
Bus voltage (AS-Interface)26.5...31.6 V DC
Total current (AS-Interface)max. 300 mA
Addressingvia built-in address port or master
Address range1...62 (1...31 A or B)
Profile (IO/ID/ID2 code)S-7.A.7
General data
ProtectionIP20
ConnectionSpring clamp plug-in terminal: 0.2...2.5 mm²
Mounting methodDIN-rail mountable (EN 60715)
Temperature range0...+60 °C (storage temperature -20...+70 °C)
Dimensions H × W × D114×37×32 mm
Output
Supply voltage24 V DC (18...30.2 V DC) EN 61131-2 by additional supply, safely separated from input supply
Switching current per outputmax. 0.5 A (short-circuit and overload protected)
Total currentmax. 2 A
Switch off time in case of short circuitapprox. 20 ms
Diagnostic
Communication statusvia LED
Diagnostic via LEDper module
Monitoring - no voltageyes
Commercial data
country of originDE
customs tariff number85176200
EAN4048879048781
eClass27242604
Packaging unit1

DATASHEET - PDF

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.