MURRELEKTRONIK 5000-00501-2300001 5000-00501-2300001 - Image 1

Images are for illustrative purposes only. Please refer to data sheet for details.

5000-00501-2300001 MURRELEKTRONIK IO-Link / analog converter

Reference: 5000-00501-2300001

Manufacturer: MURRELEKTRONIK

Description:

IO-Link / analog converter
IO-Link / analog converterAO Multi U / I, M12, straight

Categories:

  • MURRELEKTRONIK > BUS systems

Brand new product in its original packaging covered by the warranties and certifications provided by MURRELEKTRONIK

  • More Info
  • PDF
  • Reviews
Guarantee, repair and return.

Unit Price: 160,27 €

This price is per unit and is the net value (not including taxes if applicable).

Calculate price by quantity

QuantityPrice

Standard lead time: 2-4 weeks.

  • These delivery times are an estimate any may vary when the item order has been processed.

LAST VIEWED

MORE INFO

AO Multi U / I, M12, straight
Art.No.: 5000-00501-2300001
Weight: 0.045 kg
Ask question
Recommend Product
IOL AO-U/I-STR-MULT-PAR
IO-Link V1.1
Connection cables are in the online shop under "Connection Technology".
Connections
IO-LinkM12 (male) 5-pole, A-coded
Analog outputM12 (female) 5-pole, A-coded, shielded
Module supply
Operating voltage24 V DC (18...30 V DC)
Current consumptionmax. 19 mA
General data
ProtectionIP65/IP67
Material (housing)Plastic
LabelingLaser labelled
Temperature range-30...+70 °C (storage temperature -40...+85 °C)
Dimensions H × W × D32.3×77.2×15 mm
IO-Link
SpecificationIO-Link V1.1
Operating modesCOM2 (38.4 kBit/s)
Port ClassA
Cycle timemin. 2.3 ms
Data width16 Bit / 2 Byte
Data formatSiemens S7
Output
Actuator supply UA24 V DC (EN 61131-2), max. 200 mA
Input range (analog)0...20 mA, 4...20 mA, 0...10 V, -10...+10 V
Valency348 nA, 348 nA, 179.4 µV, 358.9 µV
Resolution (analog)15 Bit + sign
Type2-, 3-, 4-wire technology
Accuracy0.10% (25 °C)
Temperature drift45 ppm/°K
Conversion time (analog)max. 5 ms
Output filteryes, mean value formation, parameterizable N = 0...64
Over voltage protection30 V DC
Parameterization
Measured valueCurrent/voltage
Diagnosticslower limit, upper limit, over heated, supply over voltage, supply under voltage, defective device, sensor cable break, sensor supply over current, overrun
lower limit2 Byte
upper limit2 Byte
Mean value filter1 Byte
Protection
Reverse polarity protection moduleyes, permanently
Short-circuit protection sensoryes, permanently
feed back resistanceyes, permanently
Over voltage protection30 V DC
Diagnostic
Communication statusvia LED and IO-Link
Diagnostic via LEDyes
Diagnostic via IO-Linkyes
Monitoring - limityes
Monitoring - temperatureyes
Monitoring - over voltageyes
Monitoring - under voltageyes
Underride and overrunyes
Commercial data
country of originDE
customs tariff number85389099
EAN4048879588416
eClass27242601
Packaging unit1

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.