TF140DU-110 RELAY TERM. OVERCAR. 80-110A
TF140DU-110 Thermal Overload Relay 80 ... 110 A
Low-voltage industrial components > Thermal overload relay
Contactors and overload relays > Thermal Relays
Brand new product in its original packaging covered by the warranties and certifications provided by ABB
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
| Ordering | |
|---|---|
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| Popular Downloads | |
| Data Sheet, Technical Information | 2CDC106061D0201 |
| Instructions and Manuals | 2CDC106050M6802 |
| Instructions and Manuals (Part 2) | 1SAC200017M0002 |
| Time-Current Characteristic Curve | 1SAZ400503F0002 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Dimension Diagram | 1SAZ400404F0001 |
| Dimensions | |
| Product Net Width | 89 mm |
| Product Net Height | 140 mm |
| Product Net Depth / Length | 126 mm |
| Product Net Weight | 0.82 kg |
| Technical | |
| Setting Range | 80 ... 110 A |
| Rated Operational Voltage | Auxiliary Circuit 440 V DC |
| Auxiliary Circuit 500 V AC | |
| Main Circuit 690 V AC | |
| Main Circuit 440 V DC | |
| Rated Operational Current (Ie) | 110 A |
| Rated Frequency (f) | Auxiliary Circuit 50 Hz |
| Auxiliary Circuit 60 Hz | |
| Auxiliary Circuit DC | |
| Main Circuit 60 Hz | |
| Main Circuit 50 Hz | |
| Main Circuit DC | |
| Rated Impulse Withstand Voltage (Uimp) | Auxiliary Circuit 6 kV |
| Main Circuit 8 kV | |
| Rated Insulation Voltage (Ui) | 690 V |
| Number of Poles | 3P |
| Number of Auxiliary Contacts NC | 1 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Protected Poles | 3 |
| Conventional Free-air Thermal Current (Ith) | Auxiliary Circuit NC 10 A |
| Auxiliary Circuit NO 6 A | |
| Rated Operational Current AC-15 (Ie) | (120 V) NC 3 A |
| (120 V) NO 1.5 A | |
| (240 V) NC 3 A | |
| (240 V) NO 1.2 A | |
| (400 V) NC 0.75 A | |
| (400 V) NO 0.37 A | |
| (440 V) NC 0.75 A | |
| (440 V) NO 0.37 A | |
| (500 V) NC 0.3 A | |
| (500 V) NO 0.25 A | |
| Rated Operational Current DC-13 (Ie) | (125 V) NC 0.25 A |
| (125 V) NO 0.25 A | |
| (24 V) NC 1.25 A | |
| (24 V) NO 1.25 A | |
| (250 V) NC 0.12 A | |
| (250 V) NO 0.04 A | |
| (60 V) NC 0.25 A | |
| (60 V) NO 0.25 A | |
| Degree of Protection | IP20 |
| Housing IP20 | |
| Main Circuit Terminals IP10 | |
| Pollution Degree | 3 |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Flexible 1/2x 0.75 ... 2.5 mm² | |
| Rigid 1/2x 0.75 ... 4 mm² | |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 16 ... 70 mm² |
| Flexible with Insulated Ferrule 1/2x 16 ... 70 mm² | |
| Flexible 1/2x 16 ... 70 mm² | |
| Rigid 1/2x 16 ... 70 mm² | |
| Tightening Torque | Auxiliary Circuit 0.8 ... 1.2 N·m |
| Main Circuit 8 ... 10 N·m | |
| Wire Stripping Length | Auxiliary Circuit 9 mm |
| Main Circuit 25 mm | |
| Recommended Screw Driver | Auxiliary Circuit Pozidriv 2 |
| Main Circuit Hexagon 4 | |
| Mounting Position | any |
| Power Loss | at Rated Operating Conditions per Pole 2.1 W |
| Suitable For | AF116 |
| AF140 | |
| Standards | IEC/EN 60947-1 |
| IEC/EN 60947-4-1 | |
| IEC/EN 60947-5-1 | |
| UL 60947-1 | |
| UL 60947-4-1 | |
| Technical UL/CSA | |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
| Contact Rating UL/CSA | (NC:) B600 |
| (NO:) C300 | |
| Connecting Capacity Main Circuit UL/CSA | Flexible 1/2x 6-2/0 AWG |
| Stranded 1/2x 6-2/0 AWG | |
| Connecting Capacity Auxiliary Circuit UL/CSA | Flexible 1/2x 18-14 AWG |
| Stranded 1/2x 18-14 AWG | |
| Tightening Torque UL/CSA | Auxiliary Circuit 12 in·lb |
| Environmental | |
| Ambient Air Temperature | Operation -25 ... +55 °C |
| Operation Compensated -25 ... +55 °C | |
| Storage -40 ... +70 °C | |
| Ambient Air Temperature Compensation | Yes |
| Maximum Operating Altitude Permissible | 2000 m |
| Resistance to Shock acc. to IEC 60068-2-27 | 11 ms Pulse 12g |
| 25g 2 shocks 13 ms | |
| Resistance to Vibrations | 20 Cycles with Load 0.8 In: 5g 5 ... 150 ... 5 Hz |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Declaration | 2CMT2021-006277 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| ABB EcoSolutions | |
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | No non-hazardous waste is sent to a landfill |
| End Of Life Disassembling Instructions | 1SAC200334H0001 |
| Environmental Information | 1SAC200090H0009 |
| Environmental Product Declaration - EPD | 1SAC200274H0001 |
| Certificates and Declarations | |
| ABS Certificate | 1SAA941004-0101 |
| BV Certificate | 1SAA941003-0201 |
| CB Certificate | 1SAA941012-2001 |
| CCC Certificate | 2024010304659821 |
| CQC Certificate | CQC2016010309922935 |
| Declaration of Conformity - CCC | 2020980304001320 |
| Declaration of Conformity - CE | 1SAD101100-3507 |
| Declaration of Conformity - UKCA | 1SAD201100-3507 |
| DNV GL Certificate | 1SAA941004-0301 |
| EAC Certificate | 1SAA941002-2702 |
| LR Certificate | 1SAA941004-0501 |
| RINA Certificate | RINA_ELE098115XG |
| RMRS Certificate | 1SAA941002-0701 |
| UL Certificate | E48139-20120831 |
| Container Information | |
| Package Level 1 Units | carton 1 piece |
| Package Level 1 Width | 165 mm |
| Package Level 1 Height | 133 mm |
| Package Level 1 Depth / Length | 151 mm |
| Package Level 1 Gross Weight | 0.945 kg |
| Package Level 1 EAN | 4013614446825 |
| Package Level 2 Units | 4 piece |
| Package Level 2 Width | 280 mm |
| Package Level 2 Height | 210 mm |
| Package Level 2 Depth / Length | 395 mm |
| Package Level 2 Gross Weight | 8.786 kg |
| Package Level 2 EAN | 4013614494369 |
| External Classifications and Standards | |
| Object Classification Code | F |
| ETIM 9 | EC000106 - Thermal overload relay |
| ETIM 10 | EC000106 - Thermal overload relay |
| eClass | V11.0 : 27371501 |
| UNSPSC | 39122330 |
| IDEA Granular Category Code (IGCC) | 5366 >> Thermal overload relay |
| E-Number (Finland) | 3706577 |
| E-Number (Norway) | 4116772 |
| E-Number (Sweden) | 3210242 |
| Feature Name | Feature Value |
|---|---|
| Adjustable current range (EF008211) | 110 A |
| Max. rated operation voltage Ue (EF007357) | 690 V |
| Mounting method (EF000003) | Direct attachment |
| Type of electrical connection of main circuit (EF006819) | Screw connection |
| Number of auxiliary contacts as normally closed contact (EF001377) | 1 |
| Number of auxiliary contacts as normally open contact (EF001376) | 1 |
| Number of auxiliary contacts as change-over contact (EF003531) | 1 |
| Release class (EF006668) | CLASS 10 A |
| Reset function input (EF011940) | No |
| Reset function automatic (EF011941) | Yes |
| Reset function push-button (EF011942) | Yes |
| Title: | Size: | Type: |
|---|---|---|
| PDF CATALOGUE MOTOR PROTECTION EN.pdf | 240 Mbytes |
|
| TF140DU-110 Thermal Overload Relay - ABB - TF140DU-110 - 1SAZ431201R1002 | 98 Kbytes |
![]() |
| TF140DU-110 1SAZ431201R1002 ABB TF140DU-110 Thermal Overload Relay | 76 Kbytes |
![]() |
No customer reviews for the moment.
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.