1SAZ711201R1040 ABB T16-7.6 Thermal Overload Relay View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

1SAZ711201R1040 ABB T16-7.6 Thermal Overload Relay

1SAZ711201R1040

ABB

T16-7.6 Thermal Overload Relay

T16-7.6 RELe TeRM CLASS 10, 5.70-7.60 A

T16-7.6 Thermal Overload Relay 5.7 ... 7.6 A

More details


Low-voltage industrial components > Thermal overload relay

Contactors and overload relays > Thermal Relays

Brand new product in its original packaging covered by the warranties and certifications provided by ABB

Total: $49.93
Unit price: $49.93
This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Related products

Best sellers

More info



Ordering
Minimum Order Quantity1 piece
Customs Tariff Number85364900
Popular Downloads
Data Sheet, Technical Information2CDC106020D0201
Instructions and Manuals2CDC106019M6802
Instructions and Manuals (Part 2)1SAC200017M0002
Time-Current Characteristic Curve1SAZ700505F0015
CAD Dimensional Drawing2CDC001079B0201
Dimension Diagram1SAZ700404F0001
Dimensions
Product Net Width45 mm
Product Net Height76.7 mm
Product Net Depth / Length53.5 mm
Product Net Weight0.1 kg
Technical
Setting Range5.7 ... 7.6 A
Rated Operational VoltageAuxiliary Circuit 600 V AC/DC
Main Circuit 690 V AC
Rated Operational Current (Ie)7.6 A
Rated Frequency (f)Auxiliary Circuit 50 Hz
Auxiliary Circuit 60 Hz
Auxiliary Circuit DC
Main Circuit 50 Hz
Main Circuit 60 Hz
Rated Impulse Withstand Voltage (Uimp)Auxiliary Circuit 6 kV
Main Circuit 6 kV
Rated Insulation Voltage (Ui)690 V
Number of Poles3P
Number of Auxiliary Contacts NC1
Number of Auxiliary Contacts NO1
Number of Protected Poles3
Conventional Free-air Thermal Current (Ith)Auxiliary Circuit NC 6 A
Auxiliary Circuit NO 4 A
Rated Operational Current AC-15 (Ie)(120 V) NC 3 A
(120 V) NO 0.5 A
(240 V) NC 3 A
(240 V) NO 0.5 A
(400 V) NC 0.75 A
(400 V) NO 0.5 A
(500 V) NC 0.75 A
(500 V) NO 0.5 A
Rated Operational Current DC-13 (Ie)(125 V) NC 0.55 A
(125 V) NO 0.55 A
(24 V) NC 1.25 A
(24 V) NO 1.25 A
(250 V) NC 0.27 A
(250 V) NO 0.27 A
(500 V) NC 0.15 A
(500 V) NO 0.15 A
(60 V) NC 0.55 A
(60 V) NO 0.55 A
Degree of ProtectionIP20
Pollution Degree3
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Flexible 1/2x 0.75 ... 1 mm²
Flexible 1/2x 1 ... 2.5 mm²
Rigid 1/2x 0.75 ... 4 mm²
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 0.75 ... 4 mm²
Flexible with Insulated Ferrule 1/2x 0.75 ... 4 mm²
Flexible 1/2x 0.75 ... 4 mm²
Solid 1/2x 0.75 ... 1.5 mm²
Solid 1/2x 1.5 ... 4 mm²
Stranded 1/2x 1 ... 4 mm²
Tightening TorqueAuxiliary Circuit 1 ... 1.2 N·m
Main Circuit 1.1 ... 1.5 N·m
Wire Stripping LengthAuxiliary Circuit 9 mm
Main Circuit 12 mm
Recommended Screw DriverMain Circuit Pozidriv 2
Power Lossat Rated Operating Conditions per Pole 1.1 ... 2.0 W
Suitable ForB6
BC6
B7
BC7
VB6
VBC6
VB7
VBC7
MC1
MC2
AS09
AS12
AS16
StandardsIEC/EN 60947-1
IEC/EN 60947-4-1
IEC/EN 60947-5-1
UL 60947-1
UL 60947-4-1
IEC 60335-2-40 A2L
Technical UL/CSA
Maximum Operating Voltage UL/CSAMain Circuit 600 V AC
Contact Rating UL/CSA(NC:) B600
(NC:) Q600
(NO:) Q600
(NO:) D300
Connecting Capacity Main Circuit UL/CSAFlexible 1/2x 18-12 AWG
Stranded 1/2x 18-10 AWG
Connecting Capacity Auxiliary Circuit UL/CSAFlexible 1/2x 18-12 AWG
Stranded 1/2x 18-12 AWG
Tightening Torque UL/CSAAuxiliary Circuit 9 ... 11 in·lb
Main Circuit 9 ... 13 in·lb
Environmental
Ambient Air TemperatureOperation -25 ... +60 °C
Operation Compensated -25 ... +60 °C
Storage -50 ... +80 °C
Ambient Air Temperature CompensationYes
Maximum Operating Altitude Permissible2000 m
Resistance to Shock acc. to IEC 60068-2-2711 ms Pulse 22g
Resistance to Vibrations3g 3 ... 150 Hz
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA2CMT2023-006525
Material Compliance
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration2CMT2021-006202
RoHS Declaration2CMT2021-006277
WEEE B2C / B2BBusiness To Business
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
Environmental Information1SAC200055H0009
Certificates and Declarations
A2L Certificate – IEC1SAA941000-4601
ABS Certificate1SAA941001-0102
BV Certificate1SAA941001-0203
CB Certificate1SAA941008-2001
CCC Certificate2024010304658957
CQC CertificateCQC2011010309459316
Declaration of Conformity - CCC2020980304001787
Declaration of Conformity - CE1SAD101100-3502
Declaration of Conformity - UKCA1SAD201100-3502
DNV GL Certificate1SAA941001-0302
EAC Certificate1SAA941002-2702
GL Certificate1SAA941007-0401
LR Certificate1SAA941001-0502
RINA Certificate1SAA941000-0802
RMRS Certificate1SAA941000-0704
UL CertificateE48139-20090126
Container Information
Package Level 1 Unitscarton 1 piece
Package Level 1 Width48 mm
Package Level 1 Height63 mm
Package Level 1 Depth / Length82 mm
Package Level 1 Gross Weight0.112 kg
Package Level 1 EAN4013614397943
Package Level 2 Units40 piece
Package Level 2 Width280 mm
Package Level 2 Height210 mm
Package Level 2 Depth / Length395 mm
Package Level 2 Gross Weight8.45 kg
Package Level 2 EAN4013614440656
External Classifications and Standards
Object Classification CodeF
ETIM 9EC000106 - Thermal overload relay
ETIM 10EC000106 - Thermal overload relay
eClassV11.0 : 27371501
UNSPSC39122330
IDEA Granular Category Code (IGCC)5366 >> Thermal overload relay
E-Number (Finland)3706147
E-Number (Norway)4117164
E-Number (Sweden)3212068

ETIM for 1SAZ711201R1040 Low-voltage industrial controls and switchgear (EC000106)
Feature Name Feature Value
Adjustable current range (EF008211) 5.7 A
Max. rated operation voltage Ue (EF007357) 690 V
Mounting method (EF000003) Direct attachment
Type of electrical connection of main circuit (EF006819) Screw connection
Number of auxiliary contacts as normally closed contact (EF001377) 1
Number of auxiliary contacts as normally open contact (EF001376) 1
Number of auxiliary contacts as change-over contact (EF003531) 1
Release class (EF006668) CLASS 10
Reset function input (EF011940) No
Reset function automatic (EF011941) Yes
Reset function push-button (EF011942) Yes

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.