Product successfully added to your shopping cart
1SFL527062R1222
ABB
1
AF205B-30-22RT-12 Contactor
Contactors and overload relays
Brand new product in its original packaging covered by the warranties and certifications provided by ABB
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
| Ordering | |
|---|---|
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| Popular Downloads | |
| Data Sheet, Technical Information | 1SBC100214C0202 |
| Data Sheet, Technical Information (Part 2) | 1SAC200017M0002 |
| Instructions and Manuals | 1SFC100008M0201 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Dimensions | |
| Product Net Width | 105 mm |
| Product Net Depth / Length | 152 mm |
| Product Net Height | 196 mm |
| Product Net Weight | 2.4 kg |
| Technical | |
| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 2 |
| Number of Auxiliary Contacts NC | 2 |
| Number of Poles | 3P |
| Standards | IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, IEC 60077-1 (applicable parts), IEC 60077-2 (applicable parts), EN 50155 (applicable parts), TR CU 001/2011, IEC 61373, For compliance confirmation on applicable parts based on your application and combination, please consult your ABB sales representatives. |
| Rated Operational Voltage | Main Circuit 1000 V |
| Rated Frequency (f) | Main Circuit 50 / 60 Hz |
| Rated Operational Current AC-1 (Ie) | (1000 V) 40 °C 275 A |
| (1000 V) 60 °C 250 A | |
| (1000 V) 70 °C 200 A | |
| (690 V) 40 °C 350 A | |
| (690 V) 60 °C 300 A | |
| (690 V) 70 °C 240 A | |
| Rated Operational Current AC-3 (Ie) | (415 V) 55 °C 205 A |
| (440 V) 55 °C 205 A | |
| (500 V) 55 °C 165 A | |
| (690 V) 55 °C 165 A | |
| (1000 V) 55 °C 100 A | |
| (380 / 400 V) 55 °C 205 A | |
| (220 / 230 / 240 V) 55 °C 205 A | |
| Rated Operational Current DC-1 (Ie) | (100 V) 1 Pole, 40 °C 350 A |
| (100 V) 1 Pole, 60 °C 300 A | |
| (100 V) 1 Pole, 70 °C 240 A | |
| (110 V) 2 Poles in Series, 40 °C 350 A | |
| (110 V) 2 Poles in Series, 60 °C 300 A | |
| (110 V) 2 Poles in Series, 70 °C 240 A | |
| (110 V) 3 Poles in Series, 40 °C 350 A | |
| (110 V) 3 Poles in Series, 60 °C 300 A | |
| (110 V) 3 Poles in Series, 70 °C 240 A | |
| (175 V) 2 Poles in Series, 40 °C 350 A | |
| (175 V) 2 Poles in Series, 60 °C 300 A | |
| (175 V) 2 Poles in Series, 70 °C 240 A | |
| (200 V) 2 Poles in Series, 40 °C 350 A | |
| (200 V) 2 Poles in Series, 60 °C 300 A | |
| (200 V) 2 Poles in Series, 70 °C 240 A | |
| (220 V) 3 Poles in Series, 40 °C 350 A | |
| (220 V) 3 Poles in Series, 60 °C 300 A | |
| (220 V) 3 Poles in Series, 70 °C 240 A | |
| (260 V) 3 Poles in Series, 40 °C 350 A | |
| (260 V) 3 Poles in Series, 60 °C 300 A | |
| (260 V) 3 Poles in Series, 70 °C 240 A | |
| (300 V) 3 Poles in Series, 40 °C 350 A | |
| (300 V) 3 Poles in Series, 60 °C 300 A | |
| (300 V) 3 Poles in Series, 70 °C 240 A | |
| (72 V) 1-Pole, 40 °C 350 A | |
| (72 V) 1-Pole, 60 °C 300 A | |
| (72 V) 1-Pole, 70 °C 240 A | |
| (72 V) 2 Poles in Series, 40 °C 350 A | |
| (72 V) 2 Poles in Series, 60 °C 300 A | |
| (72 V) 2 Poles in Series, 70 °C 240 A | |
| (72 V) 3 Poles in Series, 40 °C 350 A | |
| (72 V) 3 Poles in Series, 60 °C 300 A | |
| (72 V) 3 Poles in Series, 70 °C 240 A | |
| (90 V) 1 Pole, 40 °C 350 A | |
| (90 V) 1 Pole, 60 °C 300 A | |
| (90 V) 1 Pole, 70 °C 240 A | |
| Rated Operational Current DC-3 (Ie) | (110 V) 2 Poles in Series, 40 °C 275 A |
| (110 V) 2 Poles in Series, 60 °C 275 A | |
| (110 V) 2 Poles in Series, 70 °C 240 A | |
| (110 V) 3 Poles in Series, 40 °C 275 A | |
| (110 V) 3 Poles in Series, 60 °C 275 A | |
| (110 V) 3 Poles in Series, 70 °C 240 A | |
| (220 V) 3 Poles in Series, 40 °C 275 A | |
| (220 V) 3 Poles in Series, 60 °C 275 A | |
| (220 V) 3 Poles in Series, 70 °C 240 A | |
| (72 V) 2 Poles in Series, 40 °C 275 A | |
| (72 V) 2 Poles in Series, 60 °C 275 A | |
| (72 V) 2 Poles in Series, 70 °C 240 A | |
| (72 V) 3 Poles in Series, 40 °C 275 A | |
| (72 V) 3 Poles in Series, 60 °C 275 A | |
| (72 V) 3 Poles in Series, 70 °C 240 A | |
| Rated Operational Current DC-5 (Ie) | (110 V) 2 Poles in Series, 40 °C 275 A |
| (110 V) 2 Poles in Series, 60 °C 275 A | |
| (110 V) 2 Poles in Series, 70 °C 240 A | |
| (110 V) 3 Poles in Series, 40 °C 275 A | |
| (110 V) 3 Poles in Series, 60 °C 275 A | |
| (110 V) 3 Poles in Series, 70 °C 240 A | |
| (220 V) 3 Poles in Series, 40 °C 275 A | |
| (220 V) 3 Poles in Series, 60 °C 275 A | |
| (220 V) 3 Poles in Series, 70 °C 240 A | |
| (72 V) 2 Poles in Series, 40 °C 275 A | |
| (72 V) 2 Poles in Series, 60 °C 275 A | |
| (72 V) 2 Poles in Series, 70 °C 240 A | |
| (72 V) 3 Poles in Series, 40 °C 275 A | |
| (72 V) 3 Poles in Series, 60 °C 275 A | |
| (72 V) 3 Poles in Series, 70 °C 240 A | |
| Rated Operational Power AC-3 (Pe) | (415 V) 110 kW |
| (440 V) 132 kW | |
| (500 V) 110 kW | |
| (690 V) 160 kW | |
| (1000 V) 132 kW | |
| (380 / 400 V) 110 kW | |
| (220 / 230 / 240 V) 55 kW | |
| Rated Breaking Capacity AC-3e | 8.5 x Ie AC-3e |
| Rated Making Capacity AC-3 | 10 x Ie AC-3 |
| Rated Making Capacity AC-3e | 12 x Ie AC-3e |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 350 A |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 947 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 2050 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1640 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 670 A | |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V |
| acc. to UL/CSA 600 V | |
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour |
| (AC-3) 300 cycles per hour | |
| Mechanical Durability | 5 million |
| Maximum Mechanical Switching Frequency | 300 cycles per hour |
| Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) |
| Rated Control Circuit Voltage (Uc) | 50 Hz / 60 Hz 48 ... 130 V |
| DC Operation 48 ... 130 V | |
| Coil Consumption | Holding at Max. Rated Control Circuit Voltage 50 Hz 14.5 V·A |
| Holding at Max. Rated Control Circuit Voltage 60 Hz 14.5 V·A | |
| Holding at Max. Rated Control Circuit Voltage DC 2.5 V·A | |
| Holding at Max. Rated Control Circuit Voltage DC 2.5 W | |
| Pull-in at Max. Rated Control Circuit Voltage 50 Hz 340 V·A | |
| Pull-in at Max. Rated Control Circuit Voltage 60 Hz 340 V·A | |
| Pull-in at Max. Rated Control Circuit Voltage DC 465 V·A | |
| Pull-in at Max. Rated Control Circuit Voltage DC 465 W | |
| Power Loss | 8 W |
| at Rated Operating Conditions per Pole 8 W | |
| Connecting Capacity Main Circuit | Flexible 2 x 50 ... 95 mm² |
| Rigid Cu-Cable 2 x 50 ... 120 mm² | |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 2x 0.75 ... 2.5 mm² |
| Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² | |
| Flexible 2x0.75 ... 2.5 mm² | |
| Solid 2 x 1 ... 4 mm² | |
| Stranded 2 x 1 .... 4 mm² | |
| Connecting Capacity | Flexible 2 x 50 ... 95 mm² |
| Rigid Cu-Cable 2 x 50 ... 120 mm² | |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP40 |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00 | |
| Tightening Torque | Cable Lug 9 N·m |
| Main Circuit 14 ... 31 N·m | |
| Terminal Type | Main Circuit: Bars |
| Product Name | Block Contactor |
| Technical UL/CSA | |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
| General Use Rating UL/CSA | (1000 V AC) 275 A |
| Horsepower Rating UL/CSA | (200 ... 208 V AC) Three Phase 60 hp |
| (220 ... 240 V AC) Three Phase 75 hp | |
| (440 ... 480 V AC) Three Phase 150 hp | |
| (550 ... 600 V AC) Three Phase 200 hp | |
| Full Load Amps Motor Use | (200 ... 208 V AC) Three Phase 177 A |
| (220 ... 240 V AC) Three Phase 192 A | |
| (440 ... 480 V AC) Three Phase 180 A | |
| (550 ... 600 V AC) Three Phase 192 A | |
| Environmental | |
| Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 55 °C |
| Close to Contactor for Storage -40 ... 70 °C | |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Declaration | 2CMT2021-006277 |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| ABB EcoSolutions | |
| End Of Life Disassembling Instructions | 1SFC100112M0001 |
| Environmental Product Declaration - EPD | 1SFC100095D0201 |
| Certificates and Declarations | |
| A2L Certificate – UL | 9AKK108468A6695 |
| CB Certificate | SE-82315 |
| CQC Certificate | CQC2014010304676685 |
| Declaration of Conformity - CCC | 2020980304001306 |
| Declaration of Conformity - CE | 2CMT2015-005440 |
| Declaration of Conformity - UKCA | 2CMT2020-006124 |
| EAC Certificate | 9AKK107046A8618 |
| UR Certificate | 20150602-E36588_1 |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 160 mm |
| Package Level 1 Depth / Length | 258 mm |
| Package Level 1 Height | 235 mm |
| Package Level 1 Gross Weight | 3 kg |
| Package Level 1 EAN | 7320500510230 |
| External Classifications and Standards | |
| Object Classification Code | Q |
| ETIM 7 | EC000066 - Power contactor, AC switching |
| ETIM 8 | EC000066 - Power contactor, AC switching |
| ETIM 9 | EC000066 - Power contactor, AC switching |
| eClass | V11.0 : 27371003 |
| UNSPSC | 39121529 |
| IDEA Granular Category Code (IGCC) | 4755 >> Contactors |
| Title: | Size: | Type: |
|---|---|---|
| PDF CATALOGUE MOTOR PROTECTION EN.pdf | 240 Mbytes |
|
| 1SFL527062R1222 1SFL527062R1222 EN_1SFL527062R1222.pdf | 97 Kbytes |
![]() |
No customer reviews for the moment.
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.