ANUNCIAR
1SFL487082R1312 ABB AFS190-30-12-13 100-250V View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

1SFL487082R1312 ABB AFS190-30-12-13 100-250V

1SFL487082R1312

ABB

AFS190-30-12-13 100-250V

AFS190-30-12-13

More details


Low-voltage industrial components > Power contactor, AC switching

Contactors and overload relays

Brand new product in its original packaging covered by the warranties and certifications provided by ABB

Total: $1,023.44
Unit price: $1,023.44
This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Related products

Best sellers

More info



Ordering
Minimum Order Quantity1 piece
Customs Tariff Number85364900
Popular Downloads
EPLAN Data9AAC412759_EPLAN
Data Sheet, Technical Information1SBC100214C0202
Data Sheet, Technical Information (Part 2)1SAC200017M0002
Instructions and Manuals1SFC100008M0201
CAD Dimensional Drawing2CDC001079B0201
Dimensions
Product Net Width105 mm
Product Net Depth / Length152 mm
Product Net Height196 mm
Product Net Weight2.4 kg
Technical
Number of Main Contacts NO3
Number of Main Contacts NC0
Number of Auxiliary Contacts NO1
Number of Auxiliary Contacts NC2
Number of Poles3P
Rated Operational VoltageMain Circuit 1000 V
Rated Frequency (f)Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 275 A
Rated Operational Current AC-1 (Ie)(1000 V) 40 °C 250 A
(1000 V) 60 °C 225 A
(1000 V) 70 °C 185 A
(690 V) 40 °C 275 A
(690 V) 60 °C 250 A
(690 V) 70 °C 200 A
Rated Operational Current AC-3 (Ie)(415 V) 60 °C 190 A
(440 V) 60 °C 190 A
(500 V) 60 °C 135 A
(690 V) 60 °C 135 A
(1000 V) 60 °C 85 A
(380 / 400 V) 60 °C 190 A
(220 / 230 / 240 V) 60 °C 190 A
Rated Operational Current AC-3e (Ie)(415 V) 60 °C 190 A
(440 V) 60 °C 190 A
(500 V) 60 °C 135 A
(690 V) 60 °C 135 A
(1000 V) 60 °C 85 A
(380 / 400 V) 60 °C 190 A
(220 / 230 / 240 V) 60 °C 190 A
Rated Operational Current DC-1 (Ie)(110 V) 2 Poles in Series, 40 °C 250 A
(220 V) 3 Poles in Series, 40 °C 250 A
Rated Operational Current DC-3 (Ie)(110 V) 2 Poles in Series, 40 °C 250 A
(220 V) 3 Poles in Series, 40 °C 250 A
Rated Operational Current DC-5 (Ie)(110 V) 2 Poles in Series, 40 °C 250 A
(220 V) 3 Poles in Series, 40 °C 250 A
Rated Operational Power AC-3 (Pe)(415 V) 90 kW
(440 V) 110 kW
(500 V) 90 kW
(690 V) 132 kW
(1000 V) 110 kW
(380 / 400 V) 90 kW
(220 / 230 / 240 V) 55 kW
Rated Operational Power AC-3e (Pe)(415 V) 90 kW
(440 V) 110 kW
(500 V) 90 kW
(690 V) 132 kW
(1000 V) 110 kW
(380 / 400 V) 90 kW
(220 / 230 / 240 V) 55 kW
Rated Breaking Capacity AC-38 x Ie AC-3
Rated Breaking Capacity AC-3e8.5 x Ie AC-3e
Rated Making Capacity AC-310 x Ie AC-3
Rated Making Capacity AC-3e12 x Ie AC-3e
Short-Circuit Protective DevicesgG Type Fuses 355 A
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1640 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 275 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 621 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1900 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 878 A
Maximum Breaking Capacitycos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3300 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 2200 A
Rated Insulation Voltage (Ui)acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V
acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)Main Circuit 8 kV
Maximum Electrical Switching Frequency(AC-1) 300 cycles per hour
(AC-2 / AC-4) 150 cycles per hour
(AC-3) 300 cycles per hour
Mechanical Durability5 million
Maximum Mechanical Switching Frequency300 cycles per hour
Coil Operating Limits(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc)50 Hz 100 ... 250 V
60 Hz 100 ... 250 V
DC Operation 100 ... 250 V
Coil ConsumptionHolding at Max. Rated Control Circuit Voltage 50 Hz 7 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 7 V·A
Holding at Max. Rated Control Circuit Voltage DC 2.5 W
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 220 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 220 V·A
Pull-in at Max. Rated Control Circuit Voltage DC 190 W
Power Lossat Rated Operating Conditions per Pole 7 W
Operate TimeBetween Coil De-energization and NO Contact Opening 37 ... 47 ms
Between Coil Energization and NO Contact Closing 25 ... 55 ms
Connecting Capacity Main CircuitFlexible 2 x 50 ... 95 mm²
Rigid Al-Cable 1 x 95 ... 185 mm²
Rigid Cu-Cable 1 x 6 ... 150 mm²
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²
Flexible 2x0.75 ... 2.5 mm²
Solid 2 x 1 ... 4 mm²
Stranded 2 x 1 .... 4 mm²
Connecting CapacityFlexible 2 x 50 ... 95 mm²
Rigid Al-Cable 1 x 95 ... 185 mm²
Rigid Cu-Cable 1 x 6 ... 150 mm²
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Recommended Screw DriverMain Circuit M8
Control Circuit M3.5
Control Circuit 5.5
Control Circuit Pozidriv 2
Tightening TorqueCable Lug 18 N·m
Main Circuit 14 ... 31 N·m
Terminal TypeMain Circuit: Bars
Product NameBlock Contactor
Technical UL/CSA
Maximum Operating Voltage UL/CSAMain Circuit 600 V
General Use Rating UL/CSA(600 V AC) 250 A
Horsepower Rating UL/CSA(200 ... 208 V AC) Three Phase 50 hp
(220 ... 240 V AC) Three Phase 60 hp
(440 ... 480 V AC) Three Phase 125 hp
(550 ... 600 V AC) Three Phase 150 hp
Full Load Amps Motor Use(200 ... 208 V AC) Three Phase 150 A
(220 ... 240 V AC) Three Phase 154 A
(440 ... 480 V AC) Three Phase 156 A
(550 ... 600 V AC) Three Phase 144 A
Environmental
Ambient Air TemperatureClose to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C
Close to Contactor for Storage -40 ... 70 °C
Maximum Operating Altitude PermissibleWithout Derating 3000 m
Material Compliance
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration2CMT2021-006202
RoHS Declaration2CMT2021-006277
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA2CMT2023-006525
WEEE B2C / B2BBusiness To Business
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
ABB EcoSolutionsYes
ABB Site Meeting Group Waste To Landfill TargetNon-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility
End Of Life Disassembling Instructions1SFC100112M0001
Environmental Product Declaration - EPD1SFC100095D0201
Improved Energy Efficiency for CustomersProduct Efficiency - Product requires less energy to operate compared to similar product on market or older products from the same line
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 79.2 %
Sustainable Material Content in Product (wt. %)Recycled Metal - 35 %
Certificates and Declarations
CB CertificateSE-82315
CQC CertificateCQC2014010304676685
Declaration of Conformity - CCC2020980304001306
Declaration of Conformity - CE2CMT2018-005695
Declaration of Conformity - UKCA2CMT2020-006125
EAC Certificate1SFC101360D1101
SUVA Certificate2CMT2019-005857
UL Certificate20121023-E36588
Container Information
Package Level 1 Unitsbox 1 piece
Package Level 1 Width160 mm
Package Level 1 Depth / Length258 mm
Package Level 1 Height235 mm
Package Level 1 Gross Weight3 kg
Package Level 1 EAN7320500540480
External Classifications and Standards
Object Classification CodeQ
ETIM 7EC000066 - Power contactor, AC switching
ETIM 8EC000066 - Power contactor, AC switching
ETIM 9EC000066 - Power contactor, AC switching
eClassV11.0 : 27371003
UNSPSC39121529
IDEA Granular Category Code (IGCC)4755 >> Contactors
E-Number (Finland)3709004

ETIM for 1SFL487082R1312 Low-voltage industrial controls and switchgear (EC000066)
Feature Name Feature Value
Rated control supply voltage AC 50 Hz (EF003978) 100 V
Rated control supply voltage AC 60 Hz (EF003979) 100 V
Rated control supply voltage DC (EF003980) 100 V
Voltage type for actuating (EF008242) AC/DC
Rated operation current Ie at AC-1, 400 V (EF001393) 275 A
Rated operation current Ie at AC-3, 400 V (EF001392) 190 A
Rated operation power at AC-3, 400 V (EF001364) 90 kW
Rated operation power NEMA (EF011960) 44.7420 kW
Modular version (EF001126) No
Number of auxiliary contacts as normally open contact (EF001376) 1
Number of auxiliary contacts as normally closed contact (EF001377) 2
Type of electrical connection of main circuit (EF006819) Screw connection
Number of normally closed contacts as main contact (EF001375) 0
Number of normally open contacts as main contact (EF001374) 3

Datasheet - PDF

Title: Size: Type:
PDF CATALOGUE MOTOR PROTECTION EN.pdf 240 Mbytes

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.