1SBL911074R8301 ABB AX12-30-01-83 48V50/60Hz View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

1SBL911074R8301 ABB AX12-30-01-83 48V50/60Hz

1SBL911074R8301

ABB

AX12-30-01-83 48V50/60Hz

AX12-30-01-83 48V 50/60Hz Contactor

More details


Low-voltage industrial components > Power contactor, AC switching

Contactors and overload relays

Brand new product in its original packaging covered by the warranties and certifications provided by ABB

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



Ordering
Minimum Order Quantity1 piece
Customs Tariff Number85364900
Popular Downloads
EPLAN Data9AAC177925_EPLAN
Data Sheet, Technical Information1SBC100187L0203
Instructions and Manuals9AKK107492A7057
CAD Dimensional Drawing2CDC001079B0201
Dimensions
Product Net Width44 mm
Product Net Depth / Length74 mm
Product Net Height74 mm
Product Net Weight0.326 kg
Technical
Number of Main Contacts NO3
Number of Main Contacts NC0
Number of Auxiliary Contacts NO0
Number of Auxiliary Contacts NC1
Rated Operational VoltageAuxiliary Circuit 690 V
Main Circuit 690 V
Rated Frequency (f)Auxiliary Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (Ith)acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 26 A
acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-1 (Ie)(220 / 240 V) 55 °C 22 A
(690 V) 40 °C 25 A
(690 V) 70 °C 18 A
Rated Operational Current AC-3 (Ie)(415 V) 55 °C 12 A
(440 V) 55 °C 9 A
(500 V) 55 °C 9 A
(690 V) 55 °C 7 A
(380 / 400 V) 55 °C 12 A
(220 / 230 / 240 V) 55 °C 12 A
Rated Operational Current AC-15 (Ie)(500 V) NC 2
(500 V) 2 A
(690 V) 2 A
(24 / 127 V) 6 A
(220 / 240 V) 4 A
(380 / 400 V) 3 A
(400 / 440 V) 2 A
Rated Operational Current DC-13 (Ie)(24 V) 6 A / 144 W
(110 V) 1.1 A / 121 W
(125 V) 1.1 A / 138 W
(220 V) 0.55 A / 121 W
(250 V) 0.55 A / 138 W
(400 V) 2.8 A / 134 W
(500 V) 2 A / 144 W
Rated Operational Power AC-3 (Pe)(415 V) 5.5 kW
(440 V) 4 kW
(500 V) 5.5 kW
(690 V) 5.5 kW
(380 / 400 V) 5.5 kW
(220 / 230 / 240 V) 3 kW
Rated Short-time Withstand Current Low Voltage (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 120 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 26 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 55 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 280 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 70 A
for 0.1 s 140 A
for 1 s 100 A
Maximum Breaking Capacitycos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 90 A
Rated Insulation Voltage (Ui)acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
Rated Impulse Withstand Voltage (Uimp)Auxiliary Circuit 6 kV
Maximum Electrical Switching Frequency(AC-1) 600 cycles per hour
(AC-15) 1200 cycles per hour
(AC-3) 1200 cycles per hour
(DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency3600 cycles per hour
Rated Control Circuit Voltage (Uc)50 Hz 48 V
60 Hz 48 V
Power Lossat Rated Operating Conditions AC-1 per Pole 0.8 W
at Rated Operating Conditions AC-3 per Pole 0.1 W
Operate TimeBetween Coil De-energization and NC Contact Closing 9 ... 16 ms
Between Coil De-energization and NO Contact Opening 4 ... 11 ms
Between Coil Energization and NC Contact Opening 7 ... 21 ms
Between Coil Energization and NO Contact Closing 10 ... 26 ms
Degree of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
Tightening TorqueAuxiliary Circuit 1 N·m
Control Circuit 1 N·m
Main Circuit 1 N·m
Terminal TypeScrew Terminals
Product NameBlock Contactor
Technical UL/CSA
General Use Rating UL/CSA(600 V AC) 25 A
Horsepower Rating UL/CSA(120 V AC) Single Phase 3/4 hp
(200 ... 208 V AC) Three Phase 3 hp
(220 ... 240 V AC) Three Phase 3 hp
(240 V AC) Single Phase 2 hp
(440 ... 480 V AC) Three Phase 7.5 hp
(550 ... 600 V AC) Three Phase 10 hp
Tightening Torque UL/CSAAuxiliary Circuit 9 in·lb
Control Circuit 9 in·lb
Main Circuit 9 in·lb
Full Load Amps Motor Use(120 V AC) Single Phase 13.8 A
(200 ... 208 V AC) Three Phase 11 A
(220 ... 240 V AC) Three Phase 9.6 A
(240 V AC) Single Phase 12 A
(440 ... 480 V AC) Three Phase 11 A
(550 ... 600 V AC) Three Phase 11 A
Environmental
Ambient Air TemperatureClose to Contactor Fitted with Thermal O/L Relay -25 ... 55 °C
Close to Contactor without Thermal O/L Relay -40 ... 70 °C
Close to Contactor for Storage -60 ... +80 °C
Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic Withstandaccording to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 Specification II
Maximum Operating Altitude PermissibleWithout Derating 3000 m
Material Compliance
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration2CMT2021-006202
RoHS Declaration2CMT2021-006277
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Simplified SCIP005919a1-d24d-4aee-86ab-0b4d27d3f547 Finland
02501028-8fca-4fa9-a07c-1020efc17d73 Belgium
21a3a7c2-9029-4f2f-abeb-56cad0161ca9 Netherlands
45d82c7f-d451-4d13-bff1-da306b33177c Hungary
5a43926c-134f-48fe-a132-27d99a8b4c32 Spain
683cfd44-157c-4568-97c0-e6db16a52363 Portugal
6d32c396-25b1-4733-bf53-9d0d6644e4d7 Estonia
79498efb-7da9-4371-a126-bad0cc11bb39 France
7c68a93a-dbba-43d1-8a20-bb5c5ce0c399 Germany
8b03f4fe-e3de-4126-a788-31e6d3d2acf8 Poland
8ca4f596-2a77-4966-9942-5c4470a84439 Croatia
8d1d8283-0937-4610-a216-132d2c8494b3 Norway
8e312383-310a-4095-80d9-b5ca79caa3f9 Czech Republic
a444583b-bdac-4149-af0b-bea74793e702 Greece
cd619957-f39a-4179-b1aa-962e36d526a7 Denmark
d1cc4c1e-49b1-4a00-8d8f-85ec82be4e1e Sweden
fd6ea5be-0935-4f9d-a223-3fa6533cfe45 Italy
Toxic Substances Control Act - TSCA2CMT2023-006525
WEEE B2C / B2BBusiness To Business
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
Certificates and Declarations
CB Certificate9AKK107492A7072
CCC Certificate9AKK107492A7089
CCS CertificateGZ23PTB00147
CQC CertificateCQC2013010304646608
Declaration of Conformity - CCC2020980304001066
Declaration of Conformity - CE1SBD250011U1000
UL CertificateUL_20140702-E312527-10-5
Container Information
Package Level 1 Unitsbox 1 piece
Package Level 1 Width48 mm
Package Level 1 Depth / Length78 mm
Package Level 1 Height79 mm
Package Level 1 Gross Weight0.34 kg
Package Level 1 EAN3471522394835
External Classifications and Standards
Object Classification CodeQ
ETIM 7EC000066 - Power contactor, AC switching
ETIM 8EC000066 - Power contactor, AC switching
ETIM 9EC000066 - Power contactor, AC switching
eClassV11.0 : 27371003
UNSPSC39121529
IDEA Granular Category Code (IGCC)4755 >> Contactors

ETIM for 1SBL911074R8301 Low-voltage industrial controls and switchgear (EC000066)
Feature Name Feature Value
Rated control supply voltage AC 50 Hz (EF003978) 48 V
Rated control supply voltage AC 60 Hz (EF003979) 48 V
Voltage type for actuating (EF008242) AC
Rated operation current Ie at AC-1, 400 V (EF001393) 25 A
Rated operation current Ie at AC-3, 400 V (EF001392) 12 A
Rated operation power at AC-3, 400 V (EF001364) 5.5 kW
Modular version (EF001126) No
Number of auxiliary contacts as normally open contact (EF001376) 0
Number of auxiliary contacts as normally closed contact (EF001377) 1
Type of electrical connection of main circuit (EF006819) Screw connection
Number of normally closed contacts as main contact (EF001375) 0
Number of normally open contacts as main contact (EF001374) 3

Datasheet - PDF

Title: Size: Type:
PDF CATALOGUE MOTOR PROTECTION EN.pdf 240 Mbytes

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.