1SBL271005R8400
ABB
1
Low-voltage industrial components > Power contactor, AC switching
Contactors and overload relays
Brand new product in its original packaging covered by the warranties and certifications provided by ABB
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
| Ordering | |
|---|---|
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| Popular Downloads | |
| Data Sheet, Technical Information | 1SBC100219C0201 |
| Instructions and Manuals | 1SBC101061M6801 |
| Instructions and Manuals (Part 2) | 1SAC200017M0002 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Dimensions | |
| Product Net Width | 45 mm |
| Product Net Depth / Length | 86 mm |
| Product Net Height | 92.3 mm |
| Product Net Weight | 0.356 kg |
| Technical | |
| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 3P |
| Standards | IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1 |
| Rated Operational Voltage | Main Circuit 690 V |
| Rated Frequency (f) | Control Circuit 50 / 60 Hz |
| Main Circuit 50 / 60 Hz | |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 50 A |
| acc. to IEC 60947-5-1, Θ = 40 °C 16 A | |
| Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 50 A |
| (690 V) 60 °C 42 A | |
| (690 V) 70 °C 37 A | |
| Rated Operational Current AC-3 (Ie) | (415 V) 60 °C 32 A |
| (440 V) 60 °C 32 A | |
| (500 V) 60 °C 28 A | |
| (690 V) 60 °C 21 A | |
| (380 / 400 V) 60 °C 32 A | |
| (220 / 230 / 240 V) 60 °C 33 A | |
| Rated Operational Current AC-3e (Ie) | (415 V) 60 °C 32 A |
| (440 V) 60 °C 32 A | |
| (500 V) 60 °C 28 A | |
| (690 V) 60 °C 21 A | |
| (380 / 400 V) 60 °C 32 A | |
| (220 / 230 / 240 V) 60 °C 33 A | |
| Rated Operational Current DC-1 (Ie) | (110 V) 2 Poles in Series, 40 °C 50 A |
| (110 V) 2 Poles in Series, 60 °C 42 A | |
| (110 V) 2 Poles in Series, 70 °C 37 A | |
| (110 V) 3 Poles in Series, 40 °C 50 A | |
| (110 V) 3 Poles in Series, 60 °C 42 A | |
| (110 V) 3 Poles in Series, 70 °C 37 A | |
| (220 V) 3 Poles in Series, 40 °C 50 A | |
| (220 V) 3 Poles in Series, 60 °C 42 A | |
| (220 V) 3 Poles in Series, 70 °C 37 A | |
| (72 V) 1-Pole, 40 °C 50 A | |
| (72 V) 1-Pole, 60 °C 42 A | |
| (72 V) 1-Pole, 70 °C 37 A | |
| (72 V) 2 Poles in Series, 40 °C 50 A | |
| (72 V) 2 Poles in Series, 60 °C 42 A | |
| (72 V) 2 Poles in Series, 70 °C 37 A | |
| (72 V) 3 Poles in Series, 40 °C 50 A | |
| (72 V) 3 Poles in Series, 60 °C 42 A | |
| (72 V) 3 Poles in Series, 70 °C 37 A | |
| Rated Operational Current DC-3 (Ie) | (110 V) 2 Poles in Series, 40 °C 50 A |
| (110 V) 2 Poles in Series, 60 °C 42 A | |
| (110 V) 2 Poles in Series, 70 °C 37 A | |
| (110 V) 3 Poles in Series, 40 °C 50 A | |
| (110 V) 3 Poles in Series, 60 °C 42 A | |
| (110 V) 3 Poles in Series, 70 °C 37 A | |
| (220 V) 3 Poles in Series, 40 °C 50 A | |
| (220 V) 3 Poles in Series, 60 °C 42 A | |
| (220 V) 3 Poles in Series, 70 °C 37 A | |
| (72 V) 1-Pole, 40 °C 50 A | |
| (72 V) 1-Pole, 60 °C 42 A | |
| (72 V) 1-Pole, 70 °C 37 A | |
| (72 V) 2 Poles in Series, 40 °C 50 A | |
| (72 V) 2 Poles in Series, 60 °C 42 A | |
| (72 V) 2 Poles in Series, 70 °C 37 A | |
| (72 V) 3 Poles in Series, 40 °C 50 A | |
| (72 V) 3 Poles in Series, 60 °C 42 A | |
| (72 V) 3 Poles in Series, 70 °C 37 A | |
| Rated Operational Current DC-5 (Ie) | (110 V) 2 Poles in Series, 40 °C 50 A |
| (110 V) 2 Poles in Series, 60 °C 42 A | |
| (110 V) 2 Poles in Series, 70 °C 37 A | |
| (110 V) 3 Poles in Series, 40 °C 50 A | |
| (110 V) 3 Poles in Series, 60 °C 42 A | |
| (110 V) 3 Poles in Series, 70 °C 37 A | |
| (220 V) 3 Poles in Series, 40 °C 25 A | |
| (220 V) 3 Poles in Series, 60 °C 25 A | |
| (220 V) 3 Poles in Series, 70 °C 25 A | |
| (72 V) 1-Pole, 40 °C 25 A | |
| (72 V) 1-Pole, 60 °C 25 A | |
| (72 V) 1-Pole, 70 °C 25 A | |
| (72 V) 2 Poles in Series, 40 °C 50 A | |
| (72 V) 2 Poles in Series, 60 °C 42 A | |
| (72 V) 2 Poles in Series, 70 °C 37 A | |
| (72 V) 3 Poles in Series, 40 °C 50 A | |
| (72 V) 3 Poles in Series, 60 °C 42 A | |
| (72 V) 3 Poles in Series, 70 °C 37 A | |
| Rated Operational Power AC-3 (Pe) | (415 V) 15 kW |
| (440 V) 18.5 kW | |
| (500 V) 18.5 kW | |
| (690 V) 18.5 kW | |
| (380 / 400 V) 15 kW | |
| (220 / 230 / 240 V) 9 kW | |
| Rated Operational Power AC-3e (Pe) | (415 V) 15 kW |
| (440 V) 18.5 kW | |
| (500 V) 18.5 kW | |
| (690 V) 18.5 kW | |
| (380 / 400 V) 15 kW | |
| (220 / 230 / 240 V) 9 kW | |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 350 A |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 50 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 150 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 700 A | |
| at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 225 A | |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 500 A |
| cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 200 A | |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 690 V |
| acc. to UL/CSA 600 V | |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour |
| (AC-15) 0 cycles per hour | |
| (AC-2 / AC-4) 150 cycles per hour | |
| (AC-3) 1200 cycles per hour | |
| (DC-13) 0 cycles per hour | |
| Maximum Mechanical Switching Frequency | 3600 cycles per hour |
| Rated Control Circuit Voltage (Uc) | 50 Hz 110 V |
| 60 Hz 110 ... 120 V | |
| Coil Consumption | Average Holding Value 50 / 60 Hz 8 V·A |
| Average Pull-in Value 50 Hz 70 V·A | |
| Average Pull-in Value 60 Hz 66 V·A | |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 2.44 W |
| at Rated Operating Conditions AC-3 per Pole 1 W | |
| Operate Time | Between Coil De-energization and NC Contact Closing 9 ... 20 ms |
| Between Coil De-energization and NO Contact Opening 4 ... 18 ms | |
| Between Coil Energization and NC Contact Opening 7 ... 21 ms | |
| Between Coil Energization and NO Contact Closing 10 ... 26 ms | |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | |
| Mounting by Screws (not supplied) | 2 x M4 Screws Placed Diagonally |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 1 ... 6 mm² |
| Flexible with Insulated Ferrule 1/2x 1 ... 6 mm² | |
| Flexible 1/2x 1 ... 6 mm² | |
| Rigid Solid 1/2x 1 ... 2.5 mm² | |
| Rigid Stranded 1/2x 4 ... 10 mm² | |
| Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 0.5 ... 2.5 mm² |
| Flexible with Insulated Ferrule 1/2x 0.5 ... 1.5 mm² | |
| Flexible 1/2x 0.5 ... 2.5 mm² | |
| Rigid 1/2x 1 ... 2.5 mm² | |
| Rigid Solid 1/2x 1 ... 2.5 mm² | |
| Wire Stripping Length | Control Circuit 10 mm |
| Main Circuit 14 mm | |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20 | |
| Recommended Screw Driver | Pozidriv PZ |
| Terminal Type | Push-in Spring Terminals |
| Product Name | Block Contactor |
| Technical UL/CSA | |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
| General Use Rating UL/CSA | (600 V AC) 45 A |
| Horsepower Rating UL/CSA | (120 V AC) Single Phase 2 hp |
| (200 ... 208 V AC) Three Phase 10 hp | |
| (220 ... 240 V AC) Three Phase 10 hp | |
| (240 V AC) Single Phase 5 hp | |
| (440 ... 480 V AC) Three Phase 20 hp | |
| (550 ... 600 V AC) Three Phase 25 hp | |
| Connecting Capacity Main Circuit UL/CSA | Rigid Solid 1/2x 18-14 AWG |
| Rigid Stranded 1/2x 18-8 AWG | |
| Connecting Capacity Control Circuit UL/CSA | Rigid Solid 1/2x 18-14 AWG |
| Full Load Amps Motor Use | (120 V AC) Single Phase 24 A |
| (200 ... 208 V AC) Three Phase 32.2 A | |
| (220 ... 240 V AC) Three Phase 28 A | |
| (240 V AC) Single Phase 28 A | |
| (440 ... 480 V AC) Three Phase 27 A | |
| (550 ... 600 V AC) Three Phase 27 A | |
| Environmental | |
| Ambient Air Temperature | Close to Contactor without Thermal O/L Relay -40 ... 70 °C |
| Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 60 °C | |
| Close to Contactor without Thermal O/L Relay (Uc) -40 ... 70 °C | |
| Close to Contactor for Storage -60 ... +80 °C | |
| Climatic Withstand | according to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 Specification II |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Resistance to Vibrations | 4g Closed Position & 2g Open position 5 ... 300 Hz |
| Pollution Degree | 3 |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Declaration | 2CMT2021-006277 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| Certificates and Declarations | |
| BV Certificate | BV_2634H24898C1 |
| CB Certificate | CB_SE-113158 |
| CCS Certificate | GZ23PTB00147 |
| CQC Certificate | CQC2010010304445623 |
| Declaration of Conformity - CCC | 2020980304001254 |
| Declaration of Conformity - CE | 1SBD250024U1000 |
| Declaration of Conformity - UKCA | 1SBD250045U1000 |
| DNV Certificate | 9AKK108470A6934 |
| KC Certificate | 9AKK108471A9569 |
| RINA Certificate | 9AKK108470A5006 |
| UL Certificate | E312527-20231026 |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 93 mm |
| Package Level 1 Depth / Length | 86 mm |
| Package Level 1 Height | 45 mm |
| Package Level 1 Gross Weight | 0.383 kg |
| Package Level 1 EAN | 3471523015012 |
| External Classifications and Standards | |
| Object Classification Code | Q |
| ETIM 7 | EC000066 - Power contactor, AC switching |
| ETIM 8 | EC000066 - Power contactor, AC switching |
| ETIM 9 | EC000066 - Power contactor, AC switching |
| eClass | V11.0 : 27371003 |
| UNSPSC | 39121529 |
| IDEA Granular Category Code (IGCC) | 4755 >> Contactors |
| Feature Name | Feature Value |
|---|---|
| Rated control supply voltage AC 50 Hz (EF003978) | 110 V |
| Rated control supply voltage AC 60 Hz (EF003979) | 110 V |
| Voltage type for actuating (EF008242) | AC |
| Rated operation current Ie at AC-1, 400 V (EF001393) | 50 A |
| Rated operation current Ie at AC-3, 400 V (EF001392) | 32 A |
| Rated operation power at AC-3, 400 V (EF001364) | 15 kW |
| Modular version (EF001126) | No |
| Number of auxiliary contacts as normally open contact (EF001376) | 0 |
| Number of auxiliary contacts as normally closed contact (EF001377) | 0 |
| Type of electrical connection of main circuit (EF006819) | Spring clamp connection |
| Number of normally closed contacts as main contact (EF001375) | 0 |
| Number of normally open contacts as main contact (EF001374) | 3 |
| Title: | Size: | Type: |
|---|---|---|
| PDF CATALOGUE MOTOR PROTECTION EN.pdf | 240 Mbytes |
|
No customer reviews for the moment.
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.