Product successfully added to your shopping cart
MINI MCR-2-UNI-UI-UIRO-PT
2902028
PHOENIX_CONTACT
1
Signal conditioner
INTERFACE Components (IF)
* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
Orderkey | 2902028 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 70 (C-5-2017) |
GTIN | 4046356649698 |
Weight per Piece (excluding packing) | 62.900 g |
Custom tariff number | 85437090 |
Country of origin | DE (Germany) |
Ambient temperature (operation) | -40 °C ... 70 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
Number of inputs | 1 |
---|---|
Configurable/programmable | Yes |
Voltage input signal | 0 V ... 10 V (via DIP switch) |
2 V ... 10 V (via DIP switch) | |
0 V ... 5 V (via DIP switch) | |
1 V ... 5 V (via DIP switch) | |
10 V ... 0 V (via DIP switch) | |
10 V ... 2 V (via DIP switch) | |
5 V ... 0 V (via DIP switch) | |
5 V ... 1 V (via DIP switch) | |
0 V ... 12 V (can be set via software) | |
Current input signal | 0 mA ... 20 mA (via DIP switch) |
4 mA ... 20 mA (via DIP switch) | |
0 mA ... 10 mA (via DIP switch) | |
2 mA ... 10 mA (via DIP switch) | |
20 mA ... 0 mA (via DIP switch) | |
20 mA ... 4 mA (via DIP switch) | |
10 mA ... 0 mA (via DIP switch) | |
10 mA ... 2 mA (via DIP switch) | |
0 mA ... 24 mA (can be set via software) | |
max. input voltage | 12 V |
Max. input current | 24 mA |
Input resistance of voltage input | > 120 kΩ |
Input resistance current input | approx. 50 Ω (+ 0.7 V for test diode) |
Number of outputs | 1 |
---|---|
Configurable/programmable | Yes |
Voltage output signal | 0 V ... 10 V (via DIP switch) |
2 V ... 10 V (via DIP switch) | |
0 V ... 5 V (via DIP switch) | |
1 V ... 5 V (via DIP switch) | |
0 V ... 10.5 V (can be set via software) | |
Current output signal | 0 mA ... 20 mA (via DIP switch) |
4 mA ... 20 mA (via DIP switch) | |
0 mA ... 10 mA (via DIP switch) | |
2 mA ... 10 mA (via DIP switch) | |
0 mA ... 21 mA (can be set via software) | |
Max. output voltage | approx. 12.3 V |
Max. output current | 24.6 mA |
Load/output load voltage output | ≥ 10 kΩ |
Load/output load current output | ≤ 600 Ω (at 20 mA) |
Ripple | < 20 mVPP(at 600 Ω) |
< 20 mVPP(at 600 Ω) |
Output name | Switching output |
---|---|
Number of outputs | 1 |
Contact type | 1 N/O contact |
Minimum switching voltage | 1 V |
Maximum switching voltage | 30 V DC |
Min. switching current | 100 µA |
Max. switching current | 100 mA (at 30 V) |
Nominal supply voltage | 24 V DC |
---|---|
Supply voltage range | 9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715)) |
Typical current consumption | 32 mA (24 V DC) |
63 mA (12 V DC) | |
Power consumption | ≤ 1 W (at IOUT= 20 mA, 9.6 V DC, 600 Ω load) |
Connection method | Push-in connection |
---|---|
Single conductor/terminal point, solid, with ferrule, min. | 0.14 mm² |
Single conductor/terminal point, solid, with ferrule, max. | 2.5 mm² |
Single conductor/terminal point, solid, without ferrule, min. | 0.14 mm² |
Single conductor/terminal point, solid, without ferrule, max. | 2.5 mm² |
Conductor cross section flexible min. | 0.14 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Min. AWG conductor cross section, flexible | 24 |
Max. AWG conductor cross section, flexible | 12 |
Stripping length | 10 mm |
No. of channels | 1 |
---|---|
Maximum transmission error | 0.1 % (of final value) |
Maximum temperature coefficient | 0.01 %/K |
Temperature coefficient, typical | 0.01 %/K |
Step response (10-90%) | approx. 140 ms (15 Hz sample rate) |
approx. 45 ms (60 Hz sample rate) | |
approx. 25 ms (240 Hz sample rate) | |
Status display | Yellow LED (switching output) |
Electrical isolation | Reinforced insulation in accordance with IEC 61010-1 |
Overvoltage category | II |
Degree of pollution | 2 |
Rated insulation voltage | 300 V (effective) |
Test voltage, input/output/supply | 3 kV (50 Hz, 1 min.) |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
Color | gray |
Housing material | PBT |
Mounting position | any |
Assembly instructions | The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715. |
Conformance | CE-compliant |
ATEX | II 3 G Ex nA IIC T4 Gc X |
UL, USA/Canada | UL 508 Listed |
Class I, Div. 2, Groups A, B, C, D T6 | |
Class I, Zone 2, Group IIC T6 | |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Designation | Electromagnetic RF field |
---|---|
Standards/regulations | EN 61000-4-3 |
Typical deviation from the measuring range final value | 0.2 % |
Designation | Fast transients (burst) |
Standards/regulations | EN 61000-4-4 |
Typical deviation from the measuring range final value | 0.1 % |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Typical deviation from the measuring range final value | 2.8 % |
Electromagnetic compatibility | Conformance with EMC directive |
---|---|
Noise emission | EN 61000-6-4 |
Standards/regulations | EN 61000-4-2 |
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
EN 61000-4-4 | |
EN 61000-4-5 | |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Electrical isolation | Reinforced insulation in accordance with IEC 61010-1 |
Conformance | CE-compliant |
ATEX | II 3 G Ex nA IIC T4 Gc X |
UL, USA/Canada | UL 508 Listed |
Class I, Div. 2, Groups A, B, C, D T6 | |
Class I, Zone 2, Group IIC T6 | |
DNV GL-Temperature | B |
DNV GL-Humidity | B |
DNV GL-Vibration | A |
DNV GL-EMC | A |
DNV GL-Enclosure | Required protection according to the Rules shall be provided upon installation on board |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
REACh SVHC | Lead 7439-92-1 |
---|---|
China RoHS | Environmentally Friendly Use Period = 50 |
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
Title: | Size: | Type: |
---|---|---|
PDF CATALOG PHOENIX INTERFACE TECHNOLOGY AND SWITCHING DEVICES EN.pdf | 27 Mbytes | |
PHOENIX CONTACT-2902028-MINI MCR-2-UNI-UI-UIRO-PT | 136 Kbytes |
No customer reviews for the moment.
Rating: | |
Name: | |
Email: | |
Subject: | |
Text: | |
Do you recommend this product to buy? | |
Add review |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.