Product successfully added to your shopping cart
MINI MCR-SL-PT100-UI-SP-NC
2864286
PHOENIX_CONTACT
1
Resistance thermometer measuring transducer
INTERFACE Components (IF)
* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
Orderkey | 2864286 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 105 (C-7-2015) |
GTIN | 4017918974824 |
Weight per Piece (excluding packing) | 67.500 g |
Custom tariff number | 85437090 |
Country of origin | DE (Germany) |
Ambient temperature (operation) | -20 °C ... 65 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Configurable/programmable | Yes |
---|---|
Sensor types (RTD) that can be used | Pt 100 (IEC 60751/EN 60751) |
Sensor input current | 1 mA (constant) |
Connection technology | 2, 3, 4-wire |
Number of outputs | 1 |
---|---|
Configurable/programmable | Yes, unconfigured |
Voltage output signal | 0 V ... 10 V |
10 V ... 0 V | |
0 V ... 5 V | |
1 V ... 5 V | |
Current output signal | 0 mA ... 20 mA |
20 mA ... 0 mA | |
20 mA ... 4 mA | |
4 mA ... 20 mA | |
Max. output voltage | approx. 12.5 V |
Max. output current | 23 mA |
Short-circuit current | approx. 10 mA |
Load/output load voltage output | ≥ 10 kΩ |
Load/output load current output | < 500 Ω (at 20 mA) |
Ripple | < 20 mVPP(at 500 Ω) |
< 20 mVPP(at 500 Ω) |
Nominal supply voltage | 24 V DC |
---|---|
Supply voltage range | 19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715)) |
Max. current consumption | < 21 mA (at 24 V DC) |
Power consumption | < 500 mW |
Connection method | Spring-cage connection |
---|---|
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Stripping length | 8 mm |
No. of channels | 1 |
---|---|
Transmission error in the set measuring range | ((100 K / set measurement range [K]) + 0.1)% |
Transmission error in the full measuring range | ≤ 0,2 % |
Maximum temperature coefficient | < 0.02 %/K |
Protective circuit | Transient protection |
Electrical isolation | Basic insulation according to EN 61010 |
Overvoltage category | II |
Degree of pollution | 2 |
Rated insulation voltage | 50 V AC/DC |
Test voltage, input/output/supply | 1.5 kV (50 Hz, 1 min.) |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
Color | green |
Housing material | PBT |
Mounting position | any |
Assembly instructions | The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715. |
Conformance | CE-compliant |
ATEX | II 3 G Ex nA IIC T4 Gc X |
UL, USA/Canada | UL 508 Recognized |
Class I, Div. 2, Groups A, B, C, D T5 | |
GL | GL EMC 2 D |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Designation | Electromagnetic RF field |
---|---|
Standards/regulations | EN 61000-4-3 |
Typical deviation from the measuring range final value | 10 % |
Designation | Fast transients (burst) |
Standards/regulations | EN 61000-4-4 |
Typical deviation from the measuring range final value | 10 % |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Typical deviation from the measuring range final value | 10 % |
Electromagnetic compatibility | Conformance with EMC directive |
---|---|
Noise emission | EN 61000-6-4 |
Connection in acc. with standard | CUL |
Standards/regulations | EN 61000-4-2 |
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
EN 61000-4-4 | |
EN 61000-4-5 | |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Electrical isolation | Basic insulation according to EN 61010 |
Conformance | CE-compliant |
ATEX | II 3 G Ex nA IIC T4 Gc X |
UL, USA/Canada | UL 508 Recognized |
Class I, Div. 2, Groups A, B, C, D T5 | |
GL | GL EMC 2 D |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
China RoHS | Environmentally Friendly Use Period = 50 |
---|---|
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
Title: | Size: | Type: |
---|---|---|
PDF CATALOG PHOENIX INTERFACE TECHNOLOGY AND SWITCHING DEVICES EN.pdf | 27 Mbytes | |
PHOENIX CONTACT-2864286-MINI MCR-SL-PT100-UI-SP-NC | 139 Kbytes |
No customer reviews for the moment.
Rating: | |
Name: | |
Email: | |
Subject: | |
Text: | |
Do you recommend this product to buy? | |
Add review |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.