MACX MCR-EX-SL-IDSI-I 2865405 PHOENIX CONTACT Output signal conditioner View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

MACX MCR-EX-SL-IDSI-I 2865405 PHOENIX CONTACT Output signal conditioner

MACX MCR-EX-SL-IDSI-I

2865405

PHOENIX_CONTACT

Output signal conditioner

More details


INTERFACE Components (IF)

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

Go to successor article: MACX MCR-EX-IDS-I-I 2908060

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Key Commercial Data

Orderkey2865405
Packing unit1 pc
Catalog pagePage 144 (C-5-2017)
GTIN4046356160421
Weight per Piece (excluding packing)139.300 g
Custom tariff number85437090
Country of originDE (Germany)

Note

Utilization restriction1

Dimensions

Width12.5 mm
Height99 mm
Depth114.5 mm

Ambient conditions

Ambient temperature (operation)-20 °C ... 60 °C (Any mounting position)
Ambient temperature (storage/transport)-40 °C ... 80 °C
Maximum altitude≤ 2000 m
Permissible humidity (operation)10 % ... 95 % (non-condensing)
Noise immunityEN 61000-6-2 When being exposed to interference, there may be minimal deviations.

Input data

Current input signal0 mA ... 20 mA
4 mA ... 20 mA
Input voltage limitation5.4 V (at 20 mA)
Input impedance> 100 kΩ (If there is a line fault)

Output data

Signal outputCurrent output
Current output signal0 mA ... 20 mA (intrinsically safe)
4 mA ... 20 mA (intrinsically safe)
Transmission Behavior1:1 to input signal
Load/output load current output< 800 Ω (20 mA)
< 730 Ω (22.5 mA)
Output ripple< 20 mVrms

Power supply

Supply voltage range19.2 V DC ... 30 V DC (24 V DC -20%...+25%)
Max. current consumption< 46 mA (at 24 V DC / 20 mA)
Power dissipation< 1.1 W (at 24 V DC / 20 mA)

Connection data

Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.14
Stripping length7 mm
Screw threadM3
Connection methodScrew connection
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm

General

No. of channels1
Maximum transmission error< 0.1 % (of final value)
Maximum temperature coefficient< 0.01 %/K
Step response (10-90%)< 140 µs (for 4 mA ... 20 mA step)
Status displayGreen LED (supply voltage)
Flammability rating according to UL 94V0
Degree of pollution2
Overvoltage categoryII
Electromagnetic compatibilityConformance with EMC directive
Interference emissionEN 61000-6-4
Housing materialPA 6.6-FR
Colorgray
DesignationInput/output/power supply
Electrical isolation1.5 kV (50 Hz, 1 min., test voltage)
DesignationOutput/input
Electrical isolation375 V (Peak value in accordance with EN 60079-11)
DesignationOutput/supply
Electrical isolation375 V (Peak value in accordance with EN 60079-11)
ConformanceCE-compliant, additionally EN 61326
ATEX II (1) G [Ex ia Ga] IIC/IIB
 II (1) D [Ex ia Da] IIIC
 II 3(1) G Ex nA [ia Ga] IIC/IIB T4 Gc
IECEx[Ex ia Ga] IIC/IIB
[Ex ia Da] IIIC
Ex nA [ia Ga] IIC/IIB T4 Gc
UL, USA/CanadaClass I Div 2; IS for Class I, II, III Div 1
SIL2

Data communication (bypass)

HART functionYes
Protocols supportedHART

Safety characteristic data

Integrity requirementIEC 61508 - Low demand
Equipment typeType A
Safety Integrity Level (SIL)2
Safe Failure Fraction (SFF)94.68 %
λSU4.965 x 10-7(496.5 FIT)
λSD0
λDU2.79 x 10-8(27.9 FIT)
λDD0
Probability of a hazardous failure on demand (PFDAVG)1.22 x 10-4(1 year)
6.1 x 10-4(5 years)
12.2 x 10-4(10 years)
Diagnostic coverage (DC)DCS=0 %, DCD=0 %
Integrity requirementIEC 61508 - High demand
Equipment typeType A
Safety Integrity Level (SIL)2
Safe Failure Fraction (SFF)94.68 %
λSU4.965 x 10-7(496.5 FIT)
λSD0
λDU2.79 x 10-8(27.9 FIT)
λDD0
Probability of a hazardous failure per hour (PFHD)2,79 x 10-8
Diagnostic coverage (DC)DCS=0 %, DCD=0 %

Safety data

Max. output voltage Uo27.7 V
Max. output current Io92 mA
Max. output power Po633 mW
GroupIIC
Max. external inductivity Lo2 mH
Max. external capacity Co85 nF
GroupIIB
Max. external inductivity Lo4 mH
Max. external capacity Co663 nF
Safety-related maximum voltage Um253 V AC (125 V DC)

EMC data

DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3

Standards and Regulations

Electromagnetic compatibilityConformance with EMC directive
Noise emissionEN 61000-6-4
DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3
Flammability rating according to UL 94V0
ConformanceCE-compliant, additionally EN 61326
ATEX II (1) G [Ex ia Ga] IIC/IIB
 II (1) D [Ex ia Da] IIIC
 II 3(1) G Ex nA [ia Ga] IIC/IIB T4 Gc
IECEx[Ex ia Ga] IIC/IIB
[Ex ia Da] IIIC
Ex nA [ia Ga] IIC/IIB T4 Gc
UL, USA/CanadaClass I Div 2; IS for Class I, II, III Div 1
DNV GL-TemperatureB
DNV GL-HumidityB
DNV GL-VibrationA
DNV GL-EMCB
DNV GL-EnclosureRequired protection according to the Rules shall be provided upon installation on board
GroupIIC
IIB

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.