MCR analog frequency transducers for converting analog standard signals into frequency signals or PWM signals, with spring-cage connection

More details


Converters

INTERFACE Signal converters, switching devices, and power supply units - PHOENIX CONTACT

Modular Converter MCR technique. Analog - PHOENIX CONTACT

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

QuantityPrice
1+$141.20
2+$137.35
3+$135.44
4+$134.22
6+$132.75
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Dimensions

Width6.2 mm
Height93.1 mm
Depth102.5 mm

Ambient conditions

Ambient temperature (operation)-20 °C ... 65 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Degree of protectionIP20

Input data

Configurable/programmableYes
Current input signal0 mA ... 20 mA
4 mA ... 20 mA
0 mA ... 10 mA
2 mA ... 10 mA
Input resistance current inputapprox. 50 Ω
Voltage input signal0 V ... 5 V
1 V ... 5 V
0 V ... 10 V
2 V ... 10 V
Input resistance of voltage inputapprox. 110 kΩ

Output data

Number of outputs1

Output data

Frequency output0 Hz ... 10 kHz
0 Hz ... 5 kHz
0 Hz ... 2.5 kHz
0 Hz ... 1 kHz
0 Hz ... 500 Hz
0 Hz ... 250 Hz
0 Hz ... 100 Hz
0 Hz ... 50 Hz
Load min.4 mA ≤ (UL / RL) ≤ 20 mA
Output signal PWM7.8 kHz (10 bit)
3.9 kHz (10 bit)
1.9 kHz (12 bit)
977 Hz (12 bit)
488 Hz (14 bit)
244 Hz (14 bit)
122 Hz (16 bit)
61 Hz (16 bit)
Load min.12 mA ≤ (UL / RL) ≤ 20 mA
Maximum switching voltage30 V
Load current maximum20 mA
Overrange/underrangeCan be set (via DIP switch)
Type of protectionShort-circuit protection, polarity reversal protection
Step response (0–99%)< 15 ms (+ (1/f) smallest filter)
< 1 s (+ (1/f) largest filter)

Power supply

Nominal supply voltage24 V DC
Supply voltage range19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Max. current consumption< 10 mA (at 24 V DC)
Power consumption< 200 mW

Connection data

Connection methodSpring-cage connection
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Stripping length8 mm

General

No. of channels1
Maximum transmission error≤ 0.1 % (> 7 kHz ≤ 0.2 %)
Maximum temperature coefficient< 0.02 %/K
Electrical isolationBasic insulation according to EN 61010
Overvoltage categoryII
Pollution degree2
Rated insulation voltage50 V AC/DC
Test voltage, input/output/supply1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibilityConformance with EMC Directive 2004/108/EC
Noise emissionEN 61000-6-4
Noise immunityEN 61000-6-2 When being exposed to interference, there may be minimal deviations.
Colorgreen
Housing materialPBT
Mounting positionany
ConformanceCE-compliant
ATEXEx II 3 G Ex nA IIC T4 Gc X
UL, USA / CanadaUL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T5 applied for
GLGL EMC 2 D

EMC data

DesignationElectromagnetic RF field
Standards/regulationsEN 61000-4-3
Typical deviation from the measuring range final value2 %
DesignationFast transients (burst)
Standards/regulationsEN 61000-4-4
Typical deviation from the measuring range final value2 %
DesignationConducted interferences
Standards/regulationsEN 61000-4-6
Typical deviation from the measuring range final value2 %

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2810243-MINI MCR-SL-UI-F-SPEnglish138 KbytesPHOENIX CONTACT-2810243-MINI MCR-SL-UI-F-SP

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or