UM-2KS50/16DI/RS/MKDS 2900173 PHOENIX CONTACT Input module View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

UM-2KS50/16DI/RS/MKDS 2900173 PHOENIX CONTACT Input module

UM-2KS50/16DI/RS/MKDS

2900173

PHOENIX_CONTACT

Input module

More details


INTERFACE Components (IF)

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total price: $315.91
Unit price: $315.91

Quantity Price
1+$315.91
2+$304.66
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Key Commercial Data

Orderkey2900173
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 522 (C-5-2017)
GTIN4046356484053
Weight per Piece (excluding packing)474.000 g
Custom tariff number85369010
Country of originDE (Germany)

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width162 mm
Height112 mm
Depth80 mm

Ambient conditions

Ambient temperature (operation)-20 °C ... 70 °C

General

NoteVoltage monitoring on the module does not work in combination with upstream HESILED fuse terminal blocks with integrated LED display.
Max. perm. operating voltage24 V DC ±5 %
Max. perm. current (per branch)100 mA
Max. permissible current (separate power supply)2 A (F150, F151) plug-in fuse (5x20, 2 A), DIN 41662
Number of positions50
Status displayGreen LED (supply), yellow LED (channel)
Mounting positionany
Degree of protectionIP00

Connection data for connection 1

Connection nameField level
Connection methodScrew connection
Conductor cross section solid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 1.5 mm²
Conductor cross section AWG24 ... 14

Connection data for connection 2

Connection nameController level
Connection methodYokogawa KS-compatible
Torque0.5 Nm
Number of connections2
Number of positions50

Connection data for connection 3

Connection nameSupply
Connection methodpluggable
Number of connections1
Number of positions6

Supported controller

ControllerYokogawa ProSafe-RS
- suitable I/O cardSDV144

Standards and Regulations

DesignationAir clearances and creepage distances
Standards/regulationsDIN EN 50178: 1998-04
Rated insulation voltage50 V
Rated surge voltage0.5 kV (1.2/50 μs)
InsulationFunctional insulation
Degree of pollution2
Overvoltage categoryII

Environmental Product Compliance

REACh SVHCLead 7439-92-1
China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.