PKE12/XTU-1,2 121731 EATON MOELLER Motor-protective circuit-breaker, 3p, Ir 0.3-1.2A, standard View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

PKE12/XTU-1,2 121731 EATON MOELLER Motor-protective circuit-breaker, 3p, Ir 0.3-1.2A, standard

PKE12/XTU-1,2

121731

EATON - MOELLER

Available

Ship on today

Motor-protective circuit-breaker, 3p, Ir=0.3-1.2A, standard

More details


Motor Circuit Protectors Protection Breaker

Motor Protective Circuit Breakers PKZ - EATON - MOELLER

Motor-protective circuit-breakers PKE - EATON - MOELLER

* Brand new produt in its original packing covered by the warranties and certifications provided by EATON - MOELLER

QuantityPrice
1+$102.52
3+$97.79
5+$96.08
7+$95.08
10+$94.27
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Delivery programme

Motor rating

Rated motor current

AC-3

220 V

230 V

240 V

380 V

400 V

410 V

440 V

500 V

660 V

690 V

P

I

I

I

I

I

kW

A

A

A

A

A

Product range
  PKE motor protective circuit-breakers with electronic wide-range overload protection up to 32 A
Basic function
  Motor protection
Motor protection for heavy starting duty
Single unit/Complete unit
  Complete device with standard knob
 
  
0.06 0.37 - - - -
0.09 0.54 0.31 - - -
0.12 0.72 0.41 0.37 0.33 -
0.18 1.04 0.6 0.54 0.48 0.35
0.25 - 0.8 0.76 0.7 0.5
0.37 - 1.1 1.02 0.9 0.7
0.55 - - - - 0.9
0.75 - - - - 1.1
Technical data
General
Standards
  IEC/EN 60947, VDE 0660
Climatic proofing
  Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
   
Storage
ϑ°C-40 - +80
Open
 °C-25 - +55
Enclosed
 °C-25 - +40
Mounting position
  
Technical data for design verification
   
Rated operational current for specified heat dissipation
InA1.2
Heat dissipation per pole, current-dependent
PvidW0.1
Equipment heat dissipation, current-dependent
PvidW0.3
Static heat dissipation, non-current-dependent
PvsW0
Heat dissipation capacity
PdissW0
Operating ambient temperature min.
 °C-25
Operating ambient temperature max.
 °C55
IEC/EN 61439 design verification
   
10.2 Strength of materials and parts
   
10.2.2 Corrosion resistance
  Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
  Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
  Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
  Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
  Meets the product standard's requirements.
10.2.5 Lifting
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
  Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
  Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
  Meets the product standard's requirements.
10.5 Protection against electric shock
  Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
  Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
  Is the panel builder's responsibility.
10.8 Connections for external conductors
  Is the panel builder's responsibility.
10.9 Insulation properties
   
10.9.2 Power-frequency electric strength
  Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
  Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
  Is the panel builder's responsibility.
10.10 Temperature rise
  The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
  The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 6.0(Show features)(Hide features)
Low-voltage industrial components (EG000017) / Motor protection circuit-breaker (EC000074)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Motor protection circuit-breaker ([email protected] [AGZ529013])
Overload release current setting
 A0.3 - 1.2
Adjustment range undelayed short-circuit release
 A18.6 - 18.6
Thermal protection
  No
Phase failure sensitive
  Yes
Switch off technique
  Electronic
Rated operating voltage
 V690 - 690
Rated permanent current Iu
 A1.2
Rated operation power at AC-3, 230 V
 kW0.12
Rated operation power at AC-3, 400 V
 kW0.25
Type of electrical connection of main circuit
  Screw connection
Type of control element
  Turn button
Device construction
  Built-in device fixed built-in technique
With integrated auxiliary switch
  No
With integrated under voltage release
  No
Number of poles
  3
Rated short-circuit breaking capacity lcu at 400 V, AC
 kA100
Degree of protection (IP)
  IP20
Height
 mm102.5
Width
 mm45
Depth
 mm102.5
Approvals
Product Standards  UL508; CSA-C22.2 No.14-10;IEC60947-4-1; CE marking
UL File No.  E36332
UL Category Control No.  NLRV
CSA File No.  165628
CSA Class No.  3211-05
North America Certification  UL listed, CSA certified
Specially designed for North America  No
Characteristics
IL03402019Z (AWA1210-2490) PKE motor-protective circuit-breaker with wide-range overload protection
 
>
>>

Datasheet - PDF

Title:Language:Size:Type:
Datasheet 1: 121731 - PKE12/XTU-1,2English928 KbytesDatasheet 1: 121731 - PKE12/XTU-1,2
Datasheet 2: 121731 - PKE12/XTU-1,2English112 KbytesDatasheet 1: 121731 - PKE12/XTU-1,2
Datasheet 3: 121731 - PKE12/XTU-1,2English885 KbytesDatasheet 1: 121731 - PKE12/XTU-1,2
Complete catalogue 1: 121731 - PKE12/XTU-1,2English25 MbytesDatasheet 1: 121731 - PKE12/XTU-1,2

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or