Product name
Eaton Moeller® series ETR4 Timing relay
Product Length/Depth
103 millimetre
Product height
83 millimetre
Product width
23 millimetre
Product weight
0.141 kilogram
Certifications
UL File No.: E29184
CSA-22.2 No. 14
UL 508
CE
UL Category Control No.: NKCR
VDE 0435
IEC/EN 60947-5-1
IEC/EN 61000-4-3
CSA File No.: 012528
CSA
Standard IEC/EN 61812
CSA Class No.: 3211-03
IEC/EN 61812-1
UL
IEC/EN 61000-4-2
Catalog Notes
Changeover contact can be converted to 2 timed contacts or 1 non-delayed contact and 1 timed contact
Making and breaking conditions to DC13, time constant as stated
When supplied directly from mains or transformer > 1000 VA
Electric connection type
Screw connection
Fitted with:
Connection for potentiometer (4,7 kΩ)
Functions
Remote operation possible
Fleeting contact on energization
Delay on de-energization
Delay-on energization
Flashing, starting with pause, fixed time
Pulse shaping
Flashing, pulse initiating
Flashing, starting with pulse, fixed time
Fleeting contact on de-energization
Clock function, starting with pulse, variable
On- and Off-delayed
Pulse generating
Multi-functional
Adjustable timing function
Clock function, starting with pause, variable
On-delayed
Outputs, reversible delayed/undelayed
Off-delayed
Pulse forming
Degree of protection
Terminals: IP20
IP20
Lifespan, mechanical
30,000,000 Operations (DC operated)
30,000,000 Operations (AC operated)
Mounting position
As required
Number of contacts (change-over contacts)
2
Product category
ETR4 timing relays
Rated impulse withstand voltage (Uimp)
4000 V AC
6000 V AC
Shock resistance
4 g, Make contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 20 ms
Suitable for
DIN rail (top hat rail) mounting
Terminal capacity
1 x (20 - 14) AWG, solid or stranded
1 x (0.5 - 2.5) mm², flexible with ferrule
1 x (0.5 - 2.5) mm², solid
2 x (0.5 - 1.5) mm², solid
2 x (0.5 - 1.5) mm², flexible with ferrule
Climatic environmental conditions
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
60 °C
Ambient operating temperature (enclosed) - min
25 °C
Ambient operating temperature (enclosed) - max
45 °C
Ambient storage temperature - min
45 °C
Ambient storage temperature - max
85 °C
Climatic proofing
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78
Electro magnetic compatibility
Burst impulse
According to IEC/EN 61000-4-4
2 kV, Supply cable
1 kV, Signal cable
Electromagnetic fields
3 V/m at 1.4 - 2 GHz (according to IEC EN 61000-4-3)
10 V/m at 80 - 1000 MHz (according to IEC EN 61000-4-3)
1 V/m at 2.0 - 2.7 GHz (according to IEC EN 61000-4-3)
Immunity to line-conducted interference
10 V (according to IEC/EN 61000-4-6)
Radio interference class
Class B (EN 55011, radiated)
Class B (EN 55011, conducted)
Surge rating
2 kV, symmetrical, power pulses (Surge), EMC
According to IEC/EN 61000-4-5, power pulses (Surge), EMC
4 kV, asymmetrical, power pulses (Surge), EMC
Conventional thermal current ith of auxiliary contacts (1-pole, open)
6 A
Mains voltage tolerance
24 - 240 V AC (at 50/60 Hz)
24 – 240 V DC
Rated breaking capacity
3 A at AC-15 (cos ϕ = 0.3 220 V)
3 A at AC-14 (cos ϕ = 0.3 440 V)
1.1 x Iₑ (DC-11 L/R - 40 ms)
Rated making capacity
48 A (AC-14 cos ϕ = 0.3 400 V)
50 A (AC-15 cos ϕ = 0.3 220 V)
1.1 x Iₑ (DC-11 L/R - 40 ms)
Rated operational current (Ie)
3 A at AC-14, 380 V 400 V 415 V
3 A at AC-15, 220 V 230 V 240 V
1.2 A at DC-11, L/R max. 50 ms
3 A at AC-15, 380 V 400 V 415 V
1.5 A at DC-11, 24 V
3 A at AC-14, 440 V
3 A at AC-14, 300 V (NC)
3 A at AC-15, 300 V
Rated operational voltage (Ue) at AC - max
440 V
Safe isolation
250 V AC, Between auxiliary contacts, According to EN 61140
250 V AC, Between coil and auxiliary contacts, According to EN 61140
Short-circuit protection rating
Max. 6 A gG/gL, Fuse, Short-circuit rating without welding, Contacts
Max. 6 A gG/gL, fuse, Without welding, Contacts
Command time
50 ms, AC
30 ms, DC
Contact changeover time
4 ms
Operating frequency
4000 Operations/h
Pick-up voltage
0.85 - 1.1 V AC x Uc
0.7 - 1.1 V DC x Uc
Power consumption
2 VA at AC (Pick-up power)
2 VA at AC (Sealing power)
1.8 W at DC (Sealing power)
1.8 W at DC (Pick-up power)
Rated control supply voltage (Us) at AC, 50 Hz - min
24 V
Rated control supply voltage (Us) at AC, 50 Hz - max
240 V
Rated control supply voltage (Us) at AC, 60 Hz - min
24 V
Rated control supply voltage (Us) at AC, 60 Hz - max
240 V
Rated control supply voltage (Us) at DC - min
24 V
Rated control supply voltage (Us) at DC - max
240 V
Recovery time
70 ms (after 100 % time delay)
Repetition accuracy
≤ 0.5 % (deviation)
Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
1.4 W
Rated operational current for specified heat dissipation (In)
6 A
Static heat dissipation, non-current-dependent Pvs
1.8 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.