Standards
EN 61000-6-1/-2/-3/-4, IEC 60068-2-6, IEC 60068-2-27
Dimensions (W x H x D)
107.5 x 90 x 30 mm
Mounting
Fitted on the fixing shaft of the display or on top-hat rail according to IEC/EN 60715, 35 mm deep (without display)
Solid
0.2⁄4 (AWG 24 - 12) mm2
Flexible with ferrule
0.2⁄2.5 (AWG 24 - 12) mm2
Standard screwdriver
3.5 x 0.6 mm
Climatic environmental conditions
Operating ambient temperature
-25 to 55, cold as per IEC 60068-2-1, heat as per IEC 60068-2-2 °C
Condensation
Take appropriate measures to prevent condensation
Relative humidity, non-condensing (IEC/EN 60068-2-30)
5 - 95 %
Air pressure (operation)
795 - 1080 hPa
Ambient conditions, mechanical
Protection type (IEC/EN 60529, EN50178, VBG 4)
IP20
Vibrations (IEC/EN 60068-2-6)Constant amplitude 0.15 mm
10 - 57 Hz
Vibrations (IEC/EN 60068-2-6)Constant acceleration 2 g
57 - 150 Hz
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms
18 Impacts
Drop to IEC/EN 60068-2-31 [Drop height]
50 mm
Free fall, packaged (IEC/EN 60068-2-32)
1 m
Mounting position
Vertical or horizontal
Electromagnetic compatibility (EMC)
Electrostatic discharge (IEC/EN 61000-4-2, Level 3, ESD)Air discharge
8 kV
Electrostatic discharge (IEC/EN 61000-4-2, Level 3, ESD)Contact discharge
6 kV
Electromagnetic fields (RFI) to IEC EN 61000-4-3
10 V/m
Radio interference suppression
EN 55011 Class B, EN 55022 Class B
Burst Impulse (IEC/EN 61000-4-4, Level 3)Supply cable
2 kV
Burst Impulse (IEC/EN 61000-4-4, Level 3)Signal lines
2 kV
Power pulses (surge) (IEC/EN 61000-4-5)
2 (supply cables, symmetrical) kV
power pulses (surge) (IEC/EN 61000-4-5, level 2)
2 (supply cables symmetrical, MFD-AC-CP8..) kV
Immunity to line-conducted interference to (IEC/EN 61000-4-6)
10 V
Clearance in air and creepage distances
EN 50178, UL 508, CSA C22.2, No. 142
Insulation resistance
EN 50178
Back-up of real-time clock
Back-up of real-time clock
① Backup time (hours) with fully charged double layer capacitor
② Service life (years)
Accuracy of the real-time clock
Normally ±5 s/day (±0.5 h⁄year) s/day
Repetition accuracy of timing relays
Accuracy of timing relays (of values)
± 0.02 %
ResolutionRange “M:S”
1 s
ResolutionRange “H:M”
1 min
Write cycles of the retentive memory
1010(read/write cycles)
Rated operational voltage [Ue]
24 DC (-15⁄+20 %) V
Admissible range
20.4 - 28.8 V DC
Input currentat 24 V DC
Normally 200 mA
Power lossHeat dissipation at 24 V DC
3.4 W
Note on heat dissipation
Current consumption at 24 V DC
Data transfer rate/distance
1000 kBit/s, 6 m
500 Kbit/s, 25 m
250 Kbit/s, 40 m
125 kBit/s, 125 m
50 Kbit/s, 300 m
20 Kbit/s, 700 m
10 Kbit/s, 1000 m
Potential isolationFrom power supply
yes
Potential isolationFrom the inputs
yes
Potential isolationFrom the outputs
yes
Potential isolationto PC interface, memory card, easyNet, easyLink
yes
Bus termination (first and last station)
yes
Connection technique
RJ45, 8-pole