Standards
IEC/EN 60947, VDE 0660, UL, CSA
Lifespan, mechanicalAC operated [Operations]
10 x 106
Lifespan, mechanicalDC operated [Operations]
10 x 106
Operating frequency, mechanicalAC operated [Operations/h]
5000
Operating frequency, mechanicalDC operated [Operations/h]
5000
Climatic proofing
Damp heat, constant, to IEC 60068-2-3
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperatureOpen
-25 - +60 °C
Ambient temperatureEnclosed
- 25 - 40 °C
Ambient temperatureStorage
- 40 - 80 °C
Mounting positionMounting position
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 10 msMain contactsN/O contact
10 g
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 10 msAuxiliary contactsN/O contact
7 g
Mechanical shock resistance (IEC/EN 60068-2-27)Half-sinusoidal shock, 10 msAuxiliary contactsN/C contact
5 g
Degree of Protection
IP00
Protection against direct contact when actuated from front (EN 50274)
Finger and back-of-hand proof
Terminal capacity main cableSolid
1 x (2.5 - 16)
2 x (2.5 - 16) mm2
Terminal capacity main cableFlexible with ferrule
1 x (2.5 - 35)
2 x (2.5 - 25) mm2
Terminal capacity main cableStranded
1 x (16 - 50)
2 x (16 - 35) mm2
Terminal capacity main cableSolid or stranded
12 - 2 AWG
Terminal capacity main cableFlat conductor [Lamellenzahl x Breite x Dicke ]
2 x (6 x 9 x 0.8) mm
Terminal capacity main cableTerminal screw
M6
Terminal capacity main cableTightening torque
3.3 Nm
Terminal capacity main cableStripping length
10 mm
Terminal capacity control circuit cablesSolid
1 x (0.75 - 4)
2 x (0.75 - 4) mm2
Terminal capacity control circuit cablesFlexible with ferrule
1 x (0.75 - 2.5)
2 x (0.75 - 2.5) mm2
Terminal capacity control circuit cablesSolid or stranded
18 - 14 AWG
Terminal capacity control circuit cablesStripping length
10 mm
Terminal capacity control circuit cablesTerminal screw
M3.5
Terminal capacity control circuit cablesTightening torque
1.2 Nm
ToolMain cablePozidriv screwdriver
2 Size
ToolMain cableStandard screwdriver
0.8 x 5.5
1 x 6 mm
ToolControl circuit cablesPozidriv screwdriver
2 Size
ToolControl circuit cablesStandard screwdriver
0.8 x 5.5
1 x 6 mm
Rated impulse withstand voltage [Uimp]
8000 V AC
Overvoltage category/pollution degree
III/3
Rated insulation voltage [Ui]
690 V AC
Rated operational voltage [Ue]
690 V AC
Safe isolation to EN 61140between coil and contacts
440 V AC
Safe isolation to EN 61140between the contacts
440 V AC
Making capacity (cos ϕ) [Up to 690 V]
560
According to IEC/EN 60947 A
Breaking capacity220 V 230 V
400 A
Breaking capacity380 V 400 V
400 A
Breaking capacity500 V
400 A
Breaking capacity660 V 690 V
250 A
Short-circuit ratingShort-circuit protection maximum fuseType “2” coordination400 V [gG/gL 500 V]
63 A
Short-circuit ratingShort-circuit protection maximum fuseType “2” coordination690 V [gG/gL 690 V]
50 A
Short-circuit ratingShort-circuit protection maximum fuseType “1” coordination400 V [gG/gL 500 V]
125 A
Short-circuit ratingShort-circuit protection maximum fuseType “1” coordination690 V [gG/gL 690 V]
80 A
AC-1Rated operational currentConventional free air thermal current, 3 pole, 50 - 60 HzOpenat 40 °C [Ith=Ie]
63 A
AC-1Rated operational currentConventional free air thermal current, 3 pole, 50 - 60 HzOpenat 50 °C [Ith=Ie]
60 A
AC-1Rated operational currentConventional free air thermal current, 3 pole, 50 - 60 HzOpenat 55 °C [Ith=Ie]
58 A
AC-1Rated operational currentConventional free air thermal current, 3 pole, 50 - 60 HzOpenat 60 °C [Ith=Ie]
54 A
AC-1Rated operational currentConventional free air thermal current, 3 pole, 50 - 60 Hzenclosed [Ith]
50 A
AC-1Rated operational currentConventional free air thermal current, 1 poleopen [Ith]
162 A
AC-1Rated operational currentConventional free air thermal current, 1 poleenclosed [Ith]
146 A
AC-1Motor rating [P]220/230 V [P]
23 kW
AC-1Motor rating [P]240 V [P]
25 kW
AC-1Motor rating [P]380/400 V [P]
39 kW
AC-1Motor rating [P]415 V [P]
43 kW
AC-1Motor rating [P]440 V [P]
46 kW
AC-1Motor rating [P]500 V [P]
52 kW
AC-1Motor rating [P]690 V [P]
68 kW
AC-3Rated operational currentOpen, 3-pole: 50 – 60 HzNotes
At maximum permissible ambient temperature (open.)
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz220 V 230 V [Ie]
40 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz240 V [Ie]
40 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz380 V 400 V [Ie]
40 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz415 V [Ie]
40 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz440V [Ie]
40 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz500 V [Ie]
40 A
AC-3Rated operational currentOpen, 3-pole: 50 – 60 Hz660 V 690 V [Ie]
25 A
AC-3Motor rating [P]220 V 230 V [P]
12.5 kW
AC-3Motor rating [P]240V [P]
13.5 kW
AC-3Motor rating [P]380 V 400 V [P]
18.5 kW
AC-3Motor rating [P]415 V [P]
24 kW
AC-3Motor rating [P]440 V [P]
25 kW
AC-3Motor rating [P]500 V [P]
28 kW
AC-3Motor rating [P]660 V 690 V [P]
23 kW
Rated operational current, openDC-160 V [Ie]
63 A
Rated operational current, openDC-1110 V [Ie]
63 A
Rated operational current, openDC-1220 V [Ie]
63 A
3 pole, at Ith(60°)
16.5 W
Impedance per pole
1.9 mΩ
Voltage toleranceAC operated 50 Hz [Pick-up]
0.8 - 1.1 x Uc
Voltage toleranceAC operated 50/60 Hz
0.85 - 1.1 x Uc
Voltage toleranceDrop-out voltage AC operated [Drop-out]
0.4 - 0.6 x Uc
Power consumption of the coil in a cold state and 1.0 x USAC operated 50/60 Hz [Pick-up]
150 VA
Power consumption of the coil in a cold state and 1.0 x USAC operated 50/60 Hz [Pick-up]
95 W
Power consumption of the coil in a cold state and 1.0 x USAC operated 50/60 Hz [Sealing]
16 VA
Power consumption of the coil in a cold state and 1.0 x USAC operated 50/60 Hz [Sealing]
4.1 W
Changeover time at 100 % US(recommended value)Main contactsAC operatedClosing delay
12 - 18 ms
Changeover time at 100 % US(recommended value)Main contactsAC operatedOpening delay
8 - 13 ms
Changeover time at 100 % US(recommended value)Permissible residual current with actuation of A1 - A2 by the electronics (with 0 signal).
≦ 1 mA
Rating data for approved types
Switching capacityMaximum motor ratingThree-phase200 V
208 V
10 HP
Switching capacityMaximum motor ratingThree-phase230 V
240 V
15 HP
Switching capacityMaximum motor ratingThree-phase460 V
480 V
30 HP
Switching capacityMaximum motor ratingThree-phase575 V
600 V
40 HP
Switching capacityMaximum motor ratingSingle-phase115 V
120 V
3 HP
Switching capacityMaximum motor ratingSingle-phase230 V
240 V
7.5 HP
Switching capacityGeneral use
63 A
Short Circuit Current RatingBasic RatingSCCR
10 kA
Short Circuit Current RatingBasic Ratingmax. Fuse
250 A
Short Circuit Current RatingBasic Ratingmax. CB
250 A
Short Circuit Current Rating480 V High FaultSCCR (fuse)
30/100 kA
Short Circuit Current Rating480 V High Faultmax. Fuse
250/150 Class J A
Short Circuit Current Rating480 V High FaultSCCR (CB)
65 kA
Short Circuit Current Rating480 V High Faultmax. CB
100 A
Short Circuit Current Rating600 V High FaultSCCR (fuse)
30/100 kA
Short Circuit Current Rating600 V High Faultmax. Fuse
250/150 Class J A
Short Circuit Current Rating600 V High FaultSCCR (CB)
30 kA
Short Circuit Current Rating600 V High Faultmax. CB
250 A
Special Purpose RatingsElectrical Discharge Lamps (Ballast)480V 60Hz 3phase, 277V 60Hz 1phase
79 A
Special Purpose RatingsElectrical Discharge Lamps (Ballast)600V 60Hz 3phase, 347V 60Hz 1phase
79 A
Special Purpose RatingsIncandescent Lamps (Tungsten)480V 60Hz 3phase, 277V 60Hz 1phase
74 A
Special Purpose RatingsIncandescent Lamps (Tungsten)600V 60Hz 3phase, 347V 60Hz 1phase
74 A
Special Purpose RatingsResistance Air Heating480V 60Hz 3phase, 277V 60Hz 1phase
79 A
Special Purpose RatingsResistance Air Heating600V 60Hz 3phase, 347V 60Hz 1phase
79 A
Special Purpose RatingsElevator Control200V 60Hz 3phase
7.5 HP
Special Purpose RatingsElevator Control200V 60Hz 3phase
25.3 A
Special Purpose RatingsElevator Control240V 60Hz 3phase
10 HP
Special Purpose RatingsElevator Control240V 60Hz 3phase
28 A
Special Purpose RatingsElevator Control480V 60Hz 3phase
25 HP
Special Purpose RatingsElevator Control480V 60Hz 3phase
34 A
Special Purpose RatingsElevator Control600V 60Hz 3phase
30 HP
Special Purpose RatingsElevator Control600V 60Hz 3phase
32 A