Selected parameters SYSTEM System HOUSING 2-DIN SENSING FUNCTION Filling and Emptying CONNECTION Terminals OUTPUT Relay DPDT MATERIAL Plastic Others HOUSING 35,5 x 81 x 60 mm SENSING FUNCTION 250 oHm to 500 koHm MATERIAL NORYL ADDITIONAL Alarm HiHi and LoLo

More details


Level Sensors Detectors Measurement

Sensors

Conductive Level Sensors

* Brand new produt in its original packing covered by the warranties and certifications provided by CARLO GAVAZZI

QuantityPrice
1+$90.41
3+$86.30
5+$84.81
7+$83.94
9+$83.37
*This price is per unit and is the net value (not including taxes if applicable).

How it Works

How does this work?

1 Add the products of your choice to the shopping cart
2 Enter your contact details and submit your request
3 You will be notified by email with a quotation
4 From the quotation simply finish your order and you will receive the products

There are several options for payment
- Credit card
- Wire Transfer
- PayPal


Related products

More info



Conductive Sensors
2 to 4-point level controller
Type CL with potentiometer
• Conductive level controller
• Adjustment of sensitivity – operating resistance from
250Ω to 500KΩ
• Multiple combinations of filling and emptying applications
• Low-voltage AC electrodes
• Easy installation on DIN rails or with 11 pin circular plug
• Rated operational voltage:
24 VAC/DC, 115 VAC or 230 VAC
• Output 2x8A/250 VAC SPDT relay
• LED indication for: Output ON and Power ON
Product Description
Ordering Key
CLD4MA2DM24
µ-Processor based level controller for liquids with a wide sensitivity range (like sewage water, chemicals, salt water etc.). The controller has a separate output for alarm indication in case of a tank
Type Selection
running dry or if an overflow condition occurs.
8A SPDT/SPST relay output, NO/NC.
Sensitivity control by potenti- ometer level in 3 ranges.
Type
DIN rail mounting
Inputs Function Adjustment Outputs
Relay versions
Power supply
Mounting Relay Ordering no. Ordering no. Ordering no.
Supply: 24 VAC/DC Supply: 115 VAC Supply: 230 VAC
DIN-rail SPDT + SPST CLD4MA2DM24 CLD4MA2D115 CLD4MA2D230
11-p circular plug 2 SPST CLP4MA2AM24 CLP4MA2A115 CLP4MA2A230
Specifications
Rated operational voltage (UB)
Pin 2 & 10 230 195 to 265 VAC, 45 to 65 Hz
115 98 to 132 VAC, 45 to 65 Hz
Supply class 2 24 19.2 to 28.8 VAC/DC Rated insulation voltage <2.0 kVAC (rms) Rated impulse withstand
voltage 4 kV (1.2/50 µs) (line/neutral)
Rated operational power
AC supply 5 VA AC/DC supply 5 VA / 5 W
Delay on operate (tV) < 300 mS
Outputs Make or break on rotary-switch
Rated insulation voltage 250 VAC (rms) (cont./elec.)
Relay Rating (AgCdO) µ (micro gap)
Resistive loads AC1 8 A / 250 VAC (2500 VA) DC1 1 A / 250 VDC (250 W)
or 10 A / 25 VDC (250 W) Small induc. Loads AC15 0,4 A / 250 VAC
DC13 0,4 A / 30 VDC Mechanical life (typical) ≥ 30 x 106 operations
@ 18’000 imp/h
Electrical life (typical) AC1 > 250’000 operations
Level probe supply Max. 5 VAC Level probe current Max. 2 mA Sensitivity 250Ω to 500KΩ
Factory settings standard
range “S” 100KΩ
Ranges L (Low sensitivity) 250 Ω to 5 KΩ, CF* = 4.7 nF Ranges S (Standard sensitivity) 5 KΩ to 100 KΩ, CF* = 2.2 nF
Ranges H (High sensitivity) 50 KΩ to 500 KΩ, CF* = 1.0 nF
Dielectric voltage >2.0 KVAC (rms) (contacts / electronics)
Rated impulse withstand volt. 4 kV (1.2/50 µS) (contacts /
electronics) (IEC 664)
Operating frequency (f)
Relay output 0.5 HZ
Response time
OFF-ON (ton) 1 s
ON-OFF (toff) 1 s
Environment
Overvoltage category III (IEC 60664)
Degree of protection IP 20 (IEC 60529, 60947-1) Pollution degree 2 (IEC 60664/60664A,
60947-1)
Temperature
Operating -20º to +50ºC (-4º to + 122ºF) Storage -50º to +85ºC (-58º to +185ºF)
Housing material CLP NORYL PPO, light grey
CLD ABS VO, light grey
Weight
AC supply 200 g
AC/DC supply 125 g
UL Approvals cURus UL508, UL325, CSA-C22.2
No.247
CE marking Yes
*CF = maximum Cable Capacitance
Specifications are subject to change without notice (13.04.2015) 1

Datasheet - PDF

Title:Language:Size:Type:
pdf1-mostradoSelected parameters SYSTEM System HOUSING 2-DIN SENSING FUNCTION Filling and Emptying - CARLO GAEnglish484 Kbytespdf1-mostradoSelected parameters SYSTEM System HOUSING 2-DIN SENSING FUNCTION Filling and Emptying - CARLO GA
pdf1-Selected parameters SYSTEM System HOUSING 2-DIN SENSING FUNCTION Filling and Emptying - CARLO English12 Mbytespdf1-mostradoSelected parameters SYSTEM System HOUSING 2-DIN SENSING FUNCTION Filling and Emptying - CARLO GA
pdf2-mostradoSelected parameters SYSTEM System HOUSING 2-DIN SENSING FUNCTION Filling and Emptying - CARLO GAEnglish200 Kbytespdf1-mostradoSelected parameters SYSTEM System HOUSING 2-DIN SENSING FUNCTION Filling and Emptying - CARLO GA

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review
Have you got any questions?

If you have any questions, you can visit the following links or contact us via email

Please wait





* Required fields

or