Product name
Eaton XV-152 Touch panel
Part no.
XV-152-E6-57TVRC-10
Product Length/Depth
212 millimetre
Product height
52.5 millimetre
Product width
156 millimetre
Product weight
1.3 kilogram
Certifications
CSA Class No.: none
UL508
ATEX 94/9/EG: Zone 22, Category 3D (II 3D Ex tc IIIC T70°C IP6x)
Certified by UL for use in Canada
UL 508
IEC/EN 61241-1 (ATEX 94/9/EG: Zone 22, Category 3D (II 3D Ex tc IIIC T70°C IP6x)
CSA File No.: UL report applies to both US and Canada
Security:
CUL508
IEC/EN 60950
CULus
EN 50178
IEC/EN 61241-0 (ATEX 94/9/EG: Zone 22, Category 3D (II 3D Ex tc IIIC T70°C IP6x)
IEC/EN 60079-0 (ATEX 94/9/EG: Zone 22, Category 3D (II 3D Ex tc IIIC T70°C IP6x)
IEC/EN 61000-6-3
IEC/EN 61000-6-2
UL
EN 60950
UL File No.: E205091
DNV GL
IEC/EN 61000-6-4
IEC/EN 61131-2
UL 60950
UL Category Control No.: NRAQ
IEC/EN 61131-2, CE
Catalog Notes
4-wire Technology
7 W for basic device + 2.5 W for USB module
Heat dissipation with power consumption for 24 V
License certificates for onboard interfaces not required
Optionally with SD card -> article no. 139807
PLC license inclusive
Enclosure material
Metal, anodized
Features
Slot for SD card
Target and web visualization
Fanless CPU and system cooling, natural convection-based passive cooling
Ethernet interface
UL508, cUL approvals
Portrait format
USB Host
USB device
Overload proof
Fitted with:
Message system (incl. buffer and confirmation)
1 x USB device (built-in interface)
1 x Ethernet 10/100 Mbps (built-in interfaces)
Color display
Numeric keyboard
Alpha numeric keyboard
Printer output
1 x CANopen®/easyNet (built-in interfaces)
1 x USB host 2.0 (built-in interface)
1 x RS485 (built-in interface)
Message indication
1 x SmartWire-DT (built-in interface)
SW interfaces
Recipes
Functions
Process value representation (output) possible
SmartWire-DT coordination
Process default value (input) possible
Additional software components, loadable
Battery runtime
Back-up of real-time clock: CR 2032 (190 mA/h), zero maintenance (soldered)
Current consumption
0.4 A, continuous current, Power Supply, 24 V DC
Degree of protection
NEMA 4X
IP20, rear
IP20
Degree of protection (front side)
IP65
NEMA 4X
Fuse type
Built-in fuse (not accessible)
Lifespan
40,000 h (Service life of back-lighting)
Model
Metal enclosure and front plate
Mounting method
Flush mounting - Clearance: Width x Height x Depth ≥ 30 mm (1.18")
Flush mounting - Inclination from vertical: ±45° (if using natural convection)
Flush mounting
Product category
SmartWire-DT coordinators
Residual ripple
≤ 5 % (input voltage)
Short-circuit protection
No, external fuse FAZ Z3, Supply voltage UAux
Yes, Short-circuit rating, SmartWire-DT supply voltage
Software
EPAM, Visualisation software, Engineering
GALILEO, Visualisation software, Engineering
XSOFT-CODESYS-3, Visualisation software, Engineering
XSOFT-CODESYS-3, PLC-Programming software, Engineering
XSOFT-CODESYS-2, Visualisation software, Engineering
XSOFT-CODESYS-2, PLC-Programming software, Engineering
Terminal capacity
0.2 - 1.5 mm², solid
24 - 16 AWG, solid or stranded
0.25 - 1.5 mm², 24 - 16 AWG
Type
Coordinator for the SmartWire-DT communications system
Ambient conditions, mechanical
Shock resistance
Mechanical, According to IEC/EN 60068-2-27
Vibration resistance
According to IEC/EN 60068-2-6
Climatic environmental conditions
Air pressure
795 - 1080 hPa (operation)
Ambient operating temperature - min
0 °C
Ambient operating temperature - max
50 °C
Ambient storage temperature - min
-20 °C
Ambient storage temperature - max
60 °C
Operating temperature - min
0 °C
Operating temperature - max
50 °C
Relative humidity
10 - 95 % (non-condensing)
IEC/EN 50178
Electro magnetic compatibility
Voltage dips
≤ 10 ms, Bridging voltage dips
5 ms from undervoltage (19.2 V DC)
≤ 10 ms from rated voltage (24 V DC)
Inrush current
12.5 A (for 6 ms)
Permissible voltage
19.2 - 30 V DC, effective (rated operating voltage -20 %/+25 %)
18.0 - 31.2 V DC, absolute with ripple
18 - 31.2 V DC, battery powered (rated operating voltage -25 %/+30 %)
35 V DC (for a duration of < 100 ms)
Power consumption
Max. 7 W
2.5 W (USB Slave to USB Host)
9.5 W total
Rated control supply voltage
24 V DC (UPOW, -20 %/+25 %)
24 V DC (UAUX, -20 %/+25 %)
Rated operational current (Ie)
0.7 A
Rated operational voltage
14.5 V (± 3 % - SmartWire-DT)
24 V DC (power-supply - safety extra low voltage)
Typically UAUX -0.2 V (for 24 V DC slaves)
Supply current
3 A, Imax, Supply voltage UAux
If contactors with a total power consumption > 3 A are connected, a power feeder module EU5C-SWD-PF1/2 has to be used, Supply voltage UAux
If SmartWire-DT modules with a total power consumption > 0.7 A are connected, a power feeder module EU5C-SWD-PF2 has to be used; SmartWire-DT supply
0.7 A, Imax, SmartWire-DT supply
Supply voltage at AC, 50 Hz - min
0
Supply voltage at AC, 50 Hz - max
0
Supply voltage at DC - min
20.4
Supply voltage at DC - max
28.8
Addressing
Address set automatically
Communication interface
SmartWire-DT master
Connection
SmartWire-DT blade terminal SWD4-8MF2
Connection to SmartWire-DT
Yes
Connection type
SWD: Plug, 8-pole
Push in terminals, Supply voltage
Data transfer rate
125 kBit/s, SmartWire-DT
250 kBit/s, SmartWire-DT
Interfaces
CAN
easyNet
Ethernet (100Base-TX/10Base-T)
USB 2.0 device (not galvanically isolated)
RS485
LED indicator
Status indication of SmartWire-DT master: Green and red LEDs
Status indication of SmartWire-DT network: Configurable green or red LED
Status indication of Supply voltage: LED
Number of slots
1 (for SD-Card)
Number of SmartWire-DT slaves
99
Protocol
EtherNet/IP
Other bus systems
CAN
TCP/IP
MODBUS
Station
SmartWire-DT master, SmartWire-DT network
Display contrast ratio
300:1
Display lighting
Dimmable via software
LED
Display type
Color display, TFT
TFT
Standard front with standard membrane (fully enclosed)
Luminance intensity
250 cd/m²
Number of colors of the display
65536
Screen size (diagonal)
5.7 in
Touch technology
Glass with film touch sensor
Touch sensor (glass with foil), Resistive touch protective screen
Resistive touch
Resolution
640 x 480 px
VGA
Explosion safety category for dust
ATEX dust-ex-protection, in relation to CE
ATEX dust-ex-protection, II 3D Ex II T70°C IP5x: Zone 22, Category 3D
Potential isolation
Between UPow and 15 V SmartWire-DT supply voltage: no
Power supply: no
UAUX: no
Protection against polarity reversal
Yes
Yes, for supply voltage (Siemens MPI optional)
Backup time
10 years, typ. (time at zero voltage)
Memory
NOR-Flash: 2 MByte
NAND-Flash (can be used for data backup): approx. 64 MByte available
NVRAM (Retain data): 125 kByte
64 MByte internal DRAM (OS, Program and data memory)
SD Memory Card Slot: SDA Specification 1.00 (External)
Memory capacity
64,000 kByte
Operating system
Windows CE 5.0 (license included)
Processor
RISC CPU, 32 Bit, 400 MHz
Equipment heat dissipation, current-dependent Pvid
9.5 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
9.5 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Please enquire
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.