EATON - MOELLER P1-32/E-RT/HI11 004773 Y7-4773 - Image 1

Les images sont à titre illustratif. Svp, révisez la fiche technique.

P1-32/E-RT/HI11 004773 Y7-4773 EATON ELECTRIC Interrupteurs Marche-Arrêt, tripolaire + 1 Contact F + 1 Conta..

Référence: P1-32/E-RT/HI11

Code: 004773

Numéro de catalogue: Y7-4773

Fabricant: EATON - MOELLER

Description:

Interrupteurs Marche-Arrêt, tripolaire + 1 Contact F + 1 Contact O, 32 A, Fonctions d'ARRÊT D'URGENCE, Montage encastré
Sectionneur ON-OFF 3 pôles + 1 NO + 1 poignée NC 32 A
Eaton Moeller® series P1 On-Off switch, P1, 32 A, flush mounting, 3 pole, 1 N/O, 1 N/C, Emergency switching off function, with red thumb grip and yellow front plate
Interrupteur marche-arrêt, P1, Courant nominal ininterrompu (Iu) : 32 A, Fonctions : Fonction d’arrêt d’urgence, Interverrouillable, Équipé de : Poignée pour le pouce rouge et plaque frontale jaune, Mode de montage : Montage encastré, Nombre de pôles : Tripolaire, Degré de protection : NEMA 12

Catégories:

  • Appareillage industriel basse tension > Interrupteur-sectionneur
  • EATON - MOELLER > Sectionneurs et commutateurs à cames

Produit neuf dans son emballage d'origine avec toutes les garanties et les certifications émises par EATON - MOELLER

  • En savoir plus
  • ETIM
  • PDF
  • Commentaires
Garantie, réparation et dévolution.

Prix unitaire: 59,44 €

Ce prix est par unité et montre la valeur nette (excluant les taxes indirectes le cas échéant).

Calculer le prix par quantité

QuantitéPrix

Délai standard: 3 semaines.

  • Ces délais sont estimatifs et peuvent varier une fois la commande de l'article traitée.

DERNIÈRE CONSULTÉS

EN SAVOIR PLUS

Spécifications générales

Product Name
Eaton Moeller® series P1 On-off switch
Catalog Number
004773
Model Code
P1-32/E-RT/HI11
EAN
4015080047735
Product Length/Depth
95 mm
Product Height
70 mm
Product Width
65 mm
Product Weight
0.18 kg
Certifications
CE
CSA
IEC/EN 60204
CSA File No.: 012528
UL 60947-4-1
VDE 0660
IEC/EN 60947-3
UL Category Control No.: NLRV
CSA-C22.2 No. 60947-4-1-14
CSA-C22.2 No. 94
IEC/EN 60947
CSA Class No.: 3211-05
UL
UL File No.: E36332
Catalog Notes
Rated Short-time Withstand Current (Icw) for a time of 1 second

Features & Functions

Features
Version as main switch
Version as emergency stop installation
Fitted with:
Red thumb grip and yellow front plate
Functions
Emergency switching off function
Interlockable
Number of poles
Three-pole

General

Accessories
Auxiliary contact or neutral conductor fitted by user.
Degree of protection
NEMA 12
Degree of protection (front side)
IP65
Lifespan, mechanical
300,000 Operations
Mounting method
Flush mounting
Mounting position
As required
Operating frequency
1200 Operations/h
Overvoltage category
III
Pollution degree
3
Product Category
On-Off switch
Rated impulse withstand voltage (Uimp)
6000 V AC
Safe isolation
440 V AC, Between the contacts, According to EN 61140
Safety parameter (EN ISO 13849-1)
B10d values as per EN ISO 13849-1, table C.1
Shock resistance
15 g, Mechanical, According to IEC/EN 60068-2-27, Half-sinusoidal shock 20 ms
Suitable for
Front mounting 4-hole
Branch circuits, suitable as motor disconnect, (UL/CSA)

Climatic environmental conditions

Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
50 °C
Ambient operating temperature (enclosed) - min
-25 °C
Ambient operating temperature (enclosed) - max
40 °C
Climatic proofing
Damp heat, cyclic, to IEC 60068-2-30
Damp heat, constant, to IEC 60068-2-78

Terminal capacities

Terminal capacity
1 x (1 - 4) mm², flexible with ferrules to DIN 46228
1 x (1.5 - 6) mm², solid or stranded
14 - 8 AWG, solid or flexible with ferrule
2 x (1 - 4) mm², flexible with ferrules to DIN 46228
2 x (1.5 - 6) mm², solid or stranded
Screw size
M4, Terminal screw
Tightening torque
1.6 Nm, Screw terminals
14.1 lb-in, Screw terminals

Electrical rating

Rated breaking capacity at 220/230 V (cos phi to IEC 60947-3)
260 A
Rated breaking capacity at 400/415 V (cos phi to IEC 60947-3)
300 A
Rated breaking capacity at 500 V (cos phi to IEC 60947-3)
290 A
Rated breaking capacity at 660/690 V (cos phi to IEC 60947-3)
250 A
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V
26.4 A
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V
26.4 A
Rated operational current (Ie) at AC-3, 500 V
23.4 A
Rated operational current (Ie) at AC-3, 660 V, 690 V
14.7 A
Rated operational current (Ie) at AC-21, 440 V
32 A
Rated operational current (Ie) at AC-23A, 230 V
32 A
Rated operational current (Ie) at AC-23A, 400 V, 415 V
32 A
Rated operational current (Ie) at AC-23A, 500 V
30 A
Rated operational current (Ie) at AC-23A, 690 V
19.8 A
Rated operational current (Ie) at DC-1, load-break switches l/r = 1 ms
32 A
Rated operational current (Ie) at DC-23A, 24 V
25 A
Rated operational current (Ie) at DC-23A, 48 V
25 A
Rated operational current (Ie) at DC-23A, 60 V
25 A
Rated operational current (Ie) at DC-23A, 120 V
12 A
Rated operational power at AC-3, 380/400 V, 50 Hz
13 kW
Rated operational power at AC-3, 415 V, 50 Hz
13 kW
Rated operational power at AC-3, 690 V, 50 Hz
15 kW
Rated operational power at AC-23A, 220/230 V, 50 Hz
7.5 kW
Rated operational power at AC-23A, 400 V, 50 Hz
15 kW
Rated operational power at AC-23A, 500 V, 50 Hz
18.5 kW
Rated operational power at AC-23A, 690 V, 50 Hz
15 kW
Rated operational voltage (Ue) at AC - max
690 V
Rated uninterrupted current (Iu)
32 A
Uninterrupted current
Rated uninterrupted current Iu is specified for max. cross-section.

Short-circuit rating

Rated conditional short-circuit current (Iq)
80 kA
Rated short-time withstand current (Icw)
0.64 kA
640 A, Contacts, 1 second
Short-circuit current rating (basic rating)
110A, max. Fuse, SCCR (UL/CSA)
5 kA, SCCR (UL/CSA)
Short-circuit current rating (high fault)
10 kA, SCCR (UL/CSA)
50 A, Class J, max. Fuse, SCCR (UL/CSA)
Short-circuit protection rating
50 A gG/gL, Fuse, Contacts

Switching capacity

Load rating
1.3 x Iₑ (with intermittent operation class 12, 60 % duty factor)
2 x Iₑ (with intermittent operation class 12, 25 % duty factor)
1.6 x Iₑ (with intermittent operation class 12, 40 % duty factor)
Number of contacts in series at DC-23A, 24 V
1
Number of contacts in series at DC-23A, 48 V
2
Number of contacts in series at DC-23A, 60 V
2
Number of contacts in series at DC-23A, 120 V
3
Switching capacity (main contacts, general use)
30 A, Rated uninterrupted current max. (UL/CSA)
Switching capacity (auxiliary contacts, general use)
10A, IU, (UL/CSA)
Switching capacity (auxiliary contacts, pilot duty)
A600 (UL/CSA)
P600 (UL/CSA)
Rated making capacity up to 690 V (cos phi to IEC/EN 60947-3)
320 A
Voltage per contact pair in series
60 V

Motor rating

Assigned motor power at 115/120 V, 60 Hz, 1-phase
1 HP
Assigned motor power at 200/208 V, 60 Hz, 1-phase
2 HP
Assigned motor power at 200/208 V, 60 Hz, 3-phase
3 HP
Assigned motor power at 230/240 V, 60 Hz, 1-phase
3 HP
Assigned motor power at 230/240 V, 60 Hz, 3-phase
7.5 HP
Assigned motor power at 460/480 V, 60 Hz, 3-phase
10 HP
Assigned motor power at 575/600 V, 60 Hz, 3-phase
15 HP

Contacts

Control circuit reliability
1 failure per 100,000 switching operations statistically determined, at 24 V DC, 10 mA)
Number of auxiliary contacts (change-over contacts)
0
Number of auxiliary contacts (normally closed contacts)
1
Number of auxiliary contacts (normally open contacts)
1

Actuator

Actuator color
Red
Actuator type
Short thumb-grip

Design verification

Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
1.8 W
Rated operational current for specified heat dissipation (In)
32 A
Static heat dissipation, non-current-dependent Pvs
0 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
UV resistance only in connection with protective shield.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

ETIM for 004773 Appareillage industriel basse tension (EC000216)

Nom de la caractéristiqueFinition interrupteur général (EF006981)
Valeur de la caractéristiqueOui
Nom de la caractéristiqueFinition interrupteur de maintenance/réparation (EF006986)
Valeur de la caractéristiqueNon
Nom de la caractéristiqueFinition interrupteur de sécurité (EF006985)
Valeur de la caractéristiqueNon
Nom de la caractéristiqueFinition interrupteur de dispositif d'arrêt d'urgence (EF006959)
Valeur de la caractéristiqueOui
Nom de la caractéristiqueFinition de l'inverseur (EF009408)
Valeur de la caractéristiqueNon
Nom de la caractéristiqueNombre de commutateurs (EF005586)
Valeur de la caractéristique1
Nom de la caractéristiqueTension de fonctionnement nominale max. Ue en CA (EF007355)
Valeur de la caractéristique690 V
Nom de la caractéristiqueTension de fonctionnement normale (EF001435)
Valeur de la caractéristique690 V
Nom de la caractéristiqueCourant permanent nominal Iu (EF001389)
Valeur de la caractéristique32 A
Nom de la caractéristiqueCourant permanent nominal, CA-21, 400 V (EF011777)
Valeur de la caractéristique32 A
Nom de la caractéristiqueCourant permanent nominal , CA-21, 400 V (EF009165)
Valeur de la caractéristique32 A
Nom de la caractéristiquePuissance de fonctionnement nominale, CA-3, 400 V (EF001364)
Valeur de la caractéristique13 kW
Nom de la caractéristiqueCourant nominal de courte durée admissible Icw (EF007050)
Valeur de la caractéristique0.64 kA
Nom de la caractéristiquePuissance de fonctionnement nominale, CA-23, 400 V (EF007027)
Valeur de la caractéristique15 kW
Nom de la caractéristiquePuissance de commutation à 400 V (EF009166)
Valeur de la caractéristique15 kW
Nom de la caractéristiqueIntensité de court-circuit nominale conditionnelle Iq (EF001444)
Valeur de la caractéristique80 kA
Nom de la caractéristiqueNombre de pôles (EF001391)
Valeur de la caractéristique3
Nom de la caractéristiqueNombre de contacts auxiliaires à ouverture (EF001377)
Valeur de la caractéristique1
Nom de la caractéristiqueNombre de contacts auxiliaires à fermeture (EF001376)
Valeur de la caractéristique1
Nom de la caractéristiqueNombre de contacts auxiliaires à deux directions (EF003531)
Valeur de la caractéristique0
Nom de la caractéristiqueCommande motorisée en option (EF007386)
Valeur de la caractéristiqueNon
Nom de la caractéristiqueCommande motorisée intégrée (EF006697)
Valeur de la caractéristiqueNon
Nom de la caractéristiqueDéclencheur voltmétrique en option (EF007491)
Valeur de la caractéristiqueNon
Nom de la caractéristiqueType de construction de l'appareil (EF008240)
Valeur de la caractéristiqueTechnique d'encastrement fixe pour appareil encastré
Nom de la caractéristiqueAdapté à une fixation frontale à 4 trous (EF007247)
Valeur de la caractéristiqueOui
Nom de la caractéristiqueAdapté à une fixation frontale centrale (EF007248)
Valeur de la caractéristiqueNon
Nom de la caractéristiqueAdapté à un montage en distributeur (EF007262)
Valeur de la caractéristiqueNon
Nom de la caractéristiqueAdapté à un montage intermédiaire (EF007264)
Valeur de la caractéristiqueNon
Nom de la caractéristiqueCouleur de l'élément d'actionnement (EF007167)
Valeur de la caractéristiqueRouge
Nom de la caractéristiqueFinition de l'élément d'actionnement (EF006976)
Valeur de la caractéristiquePoignée tournante courte
Nom de la caractéristiqueVerrouillable (EF006281)
Valeur de la caractéristiqueOui
Nom de la caractéristiqueType de raccordement du circuit principal (EF006819)
Valeur de la caractéristiqueBorne à vis
Nom de la caractéristiqueAvec un câblage préparé (EF016444)
Valeur de la caractéristiqueNon
Nom de la caractéristiqueClasse de protection (IP), face avant (EF003118)
Valeur de la caractéristiqueIP65
Nom de la caractéristiqueClasse de protection (NEMA) (EF011959)
Valeur de la caractéristique12
Nom de la caractéristiqueLargeur (EF000008)
Valeur de la caractéristique65 mm
Nom de la caractéristiqueHauteur (EF000040)
Valeur de la caractéristique70 mm
Nom de la caractéristiqueProfondeur (EF000049)
Valeur de la caractéristique95 mm

FICHE TECHNIQUE - PDF

Derniers commentaires de nos clients

Toutes les évaluations que nous recevons des articles que nous proposons sont réels et vérifiés. Un petit geste, mais très précieux. Je vous remercie pour cette minute que vous passez à nous laisser votre avis et note sur les produits, car il nous aide à continuer à améliorer et à offrir encore plus la qualité de service.