Technical data for design verification | |||
Heat dissipation, at an ambient temperature of 35°C, delta T: 20 degrees, calculated as per IEC 60890 | |||
Individual enclosure for wall mounting | PV | CO | 148 |
Starting enclosure for wall mounting | PV | CO | 147 |
Middle enclosure for wall mounting | PV | CO | 147 |
Heat dissipation, at an ambient temperature of 35°C, delta T: 35 degrees, calculated as per IEC 60890 | |||
Individual enclosure for wall mounting | PV | CO | 297 |
Starting enclosure for wall mounting | PV | CO | 295 |
Middle enclosure for wall mounting | PV | CO | 295 |
IEC/EN 61439 design verification | |||
10.2 Strength of materials and parts | |||
10.2.2 Corrosion resistance | Meets the product standard's requirements. | ||
10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. | ||
10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. | ||
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects | 750 °C; meets the product standard's requirements. | ||
10.2.4 Resistance to ultra-violet (UV) radiation | Not relevant to indoor installations. | ||
10.2.5 Lifting | Does not apply to enclosures without lifting aids. | ||
10.2.6 Mechanical impact | IK09 | ||
10.2.7 Inscriptions | Meets the product standard's requirements. | ||
10.3 Degree of protection of ASSEMBLIES | IP54 | ||
10.4 Clearances and creepage distances | Is the panel builder's responsibility. | ||
10.5 Protection against electric shock | Protection class 2, therefore not applicable. | ||
10.6 Incorporation of switching devices and components | Is the panel builder's responsibility. | ||
10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. | ||
10.8 Connections for external conductors | Is the panel builder's responsibility. | ||
10.9 Insulation properties | |||
10.9.2 Power-frequency electric strength | Ui = 400 V AC | ||
10.9.3 Impulse withstand voltage | 3 kV | ||
10.9.4 Testing of enclosures made of insulating material | Does not apply to metal enclosures. | ||
10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. | ||
10.11 Short-circuit rating | Is the panel builder's responsibility. | ||
10.12 Electromagnetic compatibility | Is the panel builder's responsibility. | ||
10.13 Mechanical function | Meets the product standard's requirements. |