VAL-MB-T1/T2 600DC-PV/2+V 2906293 PHOENIX CONTACT Lightning/surge arrester type 1/2 View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

VAL-MB-T1/T2 600DC-PV/2+V 2906293 PHOENIX CONTACT Lightning/surge arrester type 1/2

VAL-MB-T1/T2 600DC-PV/2+V

2906293

PHOENIX_CONTACT

Lightning/surge arrester type 1/2

More details


Trabtech (TT)

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total price: $257.05
Unit price: $257.05

Quantity Price
1+$257.05
2+$236.80
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Key Commercial Data

Orderkey2906293
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 41 (C-4-2017)
GTIN4055626063010
Weight per Piece (excluding packing)417.800 g
Custom tariff number85363030
Country of originDE (Germany)

Dimensions

Height120 mm
Width71.2 mm
Depth65.5 mm
Horizontal pitch4 Div.

Ambient conditions

Degree of protectionIP20 (only when all terminal points are used)
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 6000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)50g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (5 - 500 Hz/2.5 h/X, Y, Z)

General

IEC test classificationPV I / II
PV T1 / T2
EN typeT1 / T2
IEC power supply systemDC
SPD failure behaviorOCM (Open-circuit mode)
Connection configurationY configuration
Installation locationInside
AccessibilityAccessible
Installation location of the disconnect deviceInternal
Mode of protection(L+) - (L-)
(L+) - PE
(L-) - PE
Mounting typeDIN rail: 35 mm
Colortraffic grey A RAL 7042
Housing materialPA 6.6
Degree of pollution2
Flammability rating according to UL 94V-0
TypeDIN rail module, one-piece
Surge protection fault messageoptical

Protective circuit DC voltage side (DC)

Maximum continuous operating voltage UCPV800 V DC
Short-circuit current rating ISCPV2000 A
Continuous operating current ICPV< 45 µA
Rated load current IL50 A
Residual current IPE≤ 45 µA DC
≤ 420 µA AC
Standby power consumption PC≤ 36 mVA
Nominal discharge current (8/20) µs20 kA
Maximum discharge current Imax(8/20) µs40 kA
Impulse discharge current (10/350) µs, charge3.125 As
Impulse discharge current (10/350) µs, specific energy9.77 kJ/Ω
Impulse discharge current (10/350) µs, peak value limp6.25 kA
Total discharge current Itotal(8/20) µs40 kA
Total discharge current Itotal(10/350) µs12.5 kA
Voltage protection level Up≤ 2.9 kV
Residual voltage Ures≤ 2.9 kV (at In)
≤ 2.1 kV (at 3 kA)
≤ 2.4 kV (at 6.25 kA)
≤ 2.5 kV (at 10 kA)
≤ 2.8 kV (at 15 kA)
≤ 3.6 kV (at 40 kA)
Response time tA≤ 25 ns
Insulation resistance Riso> 5 GΩ (at 500 V DC)

Connection data

Connection methodScrew connection
Screw threadM5
Tightening torque3 Nm
Stripping length16 mm
Conductor cross section flexible2.5 mm² ... 35 mm²
2 conductors with same cross section, stranded, ferrules without plastic sleeve, min.2.5 mm²
2 conductors with same cross section, stranded, ferrules without plastic sleeve, max.10 mm²
Conductor cross section AWG14 ... 2

Standards and Regulations

Standards/regulationsEN 50539-11 2013

Classifications

Datasheet - PDF

Title: Size: Type:
PDF CATALOG PHOENIX PROTECTION EN.pdf 27 Mbytes

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.