VAL-CP-N/PE-175-ST 2859709 PHOENIX CONTACT Type 2 surge protection plug View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

VAL-CP-N/PE-175-ST 2859709 PHOENIX CONTACT Type 2 surge protection plug

VAL-CP-N/PE-175-ST

2859709

PHOENIX_CONTACT

10

Type 2 surge protection plug

More details


Trabtech (TT)

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Key Commercial Data

Orderkey2859709
Packing unit10 pc
Minimum order quantity10 pc
NoteMade to Order (non-returnable)
Catalog pagePage 30 (TT-2007)
GTIN4046356045513
Weight per Piece (excluding packing)50.350 g
Custom tariff number85369010
Country of originDE (Germany)

Dimensions

Height46.4 mm
Width11.7 mm
Depth56.4 mm

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

General

IEC test classificationII
T2
EN typeT2
Mode of protectionN-PE
Mounting typeon base element
Colorgray/blue
Housing materialPBT-FR
Degree of pollution2
Flammability rating according to UL 94V-0
TypeDIN rail module, two-section, divisible
Number of positions1
Surge protection fault messageoptical

Protective circuit

Nominal voltage UN120 V AC (TN - only N-PE)
120 V AC (TT - only N-PE)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC(N-PE)150 V AC
Residual current IPE≤ 1 µA
Nominal discharge current In(8/20) µs (N-PE)20 kA
Maximum discharge current Imax(8/20) µs (N-PE)40 kA
Follow current interrupt rating Ifi(N-PE)100 A (150 V AC)
Voltage protection level Up(N-PE)≤ 0.95 kV
Residual voltage Ures(N-PE)≤ 0.4 kV (at In)
≤ 0.4 kV (at 10 kA)
≤ 0.4 kV (at 5 kA)
≤ 0.4 kV (at 4 kA)
≤ 0.4 kV (at 2 kA)
TOV behavior at UT(N-PE)1200 V AC (200 ms / withstand mode)
Response time tA(N-PE)≤ 100 ns

UL specifications

SPD Type4CA
Maximum continuous operating voltage MCOV (N-G)150 V AC
Mode of protectionN-G
Power distribution systemSingle phase
Nominal frequency50/60 Hz
Measured limiting voltage MLV (N-G)560 V
Nominal discharge current In(N-G)20 kA

Classifications

Datasheet - PDF

Title: Size: Type:
PDF CATALOG PHOENIX PROTECTION EN.pdf 27 Mbytes

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.