Orderkey | 2702192 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 251 (C-6-2017) |
GTIN | 4055626010199 |
Weight per Piece (excluding packing) | 69.000 g |
Custom tariff number | 85371098 |
Country of origin | DE (Germany) |
Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
---|
Ambient temperature (operation) | -40 °C ... 60 °C (observe derating) |
---|---|
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
Maximum altitude | ≤ 2000 m (Above sea level) |
Rated control circuit supply voltage US | 24 V DC -20 % / +25 % (at A1) |
---|---|
19.2 V DC ... 30 V DC | |
Rated control supply current IS | typ. 35 mA |
Power consumption at US | typ. 840 mW |
Inrush current | 150 mA (Δt = 25 ms at Us) |
Filter time | 2.5 ms (at A1 in the event of voltage dips at Us) |
max. 3 ms (at A1; test pulse width; blanking pulses/dark test) | |
1 s (at A1; test pulse rate; blanking pulses/dark test) | |
Where test pulse width ≤ 1 ms: test pulse rate = 5 x test pulse width | |
max. 1 ms (at A1; test pulse width; switch-on pulses/light test) | |
100 ms (at A1; test pulse rate; switch-on pulses/light test) | |
Unless switch-on pulses/light tests are safety-related, they should be disabled. | |
Protective circuit | Surge protection Suppressor diode |
Protection against polarity reversal for rated control circuit supply voltage |
Inrush current | < 10 mA (with Us/Ixto S35) |
---|---|
Current consumption | < 2 mA (with Us/Ixto S35) |
Voltage at input/start and feedback circuit | 24 V DC -20 % / +25 % |
Max. permissible overall conductor resistance | 150 Ω |
Output name | Enabling current path |
---|---|
Output description | safety-related N/O contacts |
Number of outputs | 1 (undelayed) |
Contact type | 1 enabling current path |
Contact material | AgSnO2 |
Switching voltage | min. 12 V AC/DC |
max. 250 V AC/DC (Observe the load curve) | |
Limiting continuous current | 6 A (observe derating) |
Inrush current | min. 3 mA |
max. 6 A | |
Sq. Total current | 36 A2(observe derating) |
Switching capacity | min. 60 mW |
Switching frequency | max. 0.5 Hz |
Mechanical service life | 10x 106cycles |
Output fuse | 6 A gL/gG (N/O contact) |
4 A gL/gG (for low-demand applications) |
Output description | non-safety-related |
---|---|
Number of outputs | 1 (digital, PNP) |
Voltage | typ. 21 V DC (Voltage at terminal block “24V” - 3 V) |
Current | max. 100 mA |
Maximum inrush current | 500 mA (Δt = 1 ms at Us) |
Short-circuit protection | Yes |
Typical pickup time at US | < 250 ms (when controlled via A1) |
---|---|
Typical response time at US | < 150 ms (automatic start) |
Typical release time at US | < 20 ms (when controlled via A1) |
Restart time | < 1 s |
Recovery time | < 500 ms |
Relay type | Electromechanical relay with forcibly guided contacts in accordance with IEC/EN 61810-3 (EN 50205) |
---|---|
Nominal operating mode | 100% operating factor |
Net weight | 69 g |
Mounting position | vertical or horizontal |
Mounting type | DIN rail mounting |
Assembly instructions | See derating curve |
Degree of protection | IP20 |
Min. degree of protection of inst. location | IP54 |
Housing material | PBT |
Housing color | yellow |
Operating voltage display | 1 x green LED |
Status display | 2 x green LEDs |
Connection method | Screw connection |
---|---|
pluggable | no |
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 26 |
Conductor cross section AWG max. | 12 |
Stripping length | 12 mm |
Screw thread | M3 |
Stop category | 0 |
---|---|
Designation | IEC 61508 - High demand |
Safety Integrity Level (SIL) | 3 (4 A DC13; 5 A AC15; 8760 switching cycles/year) |
Designation | IEC 61508 - Low demand |
Safety Integrity Level (SIL) | 3 |
Designation | EN ISO 13849 |
Performance level (PL) | e (4 A DC13; 5 A AC15; 8760 switching cycles/year) |
Category | 4 |
Designation | EN 62061 |
Safety Integrity Level Claim Limit (SIL CL) | 3 (4 A DC13; 5 A AC15; 8760 switching cycles/year) |
Designation | Air clearances and creepage distances between the power circuits |
---|---|
Standards/regulations | DIN EN 50178 |
Rated insulation voltage | 250 V AC |
250 V AC | |
Rated surge voltage/insulation | Safe isolation, reinforced insulation 6 kV between input circuit and enabling current path (13/14) Basic insulation 4 kV between all current paths and housing |
Degree of pollution | 2 |
Overvoltage category | III |
Shock | 15g |
Vibration (operation) | 10 Hz ...150 Hz, 2g |
Conformance | CE-compliant |
China RoHS | Environmentally Friendly Use Period = 50 |
---|---|
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
Title: | Size: | Type: |
---|---|---|
PDF CATALOG PHOENIX AUTOMATION EN.pdf | 35 Mbytes |
No customer reviews for the moment.
Rating: | |
Name: | |
Email: | |
Subject: | |
Text: | |
Do you recommend this product to buy? | |
Add review |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.