MINI MCR-RTD-UI-SP-NC
2902850
PHOENIX_CONTACT
1
Resistance thermometer measuring transducer
INTERFACE Components (IF)
* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
Orderkey | 2902850 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 103 (C-7-2015) |
GTIN | 4046356689250 |
Weight per Piece (excluding packing) | 90.900 g |
Custom tariff number | 85437090 |
Country of origin | DE (Germany) |
Ambient temperature (operation) | -20 °C ... 65 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Configurable/programmable | Yes |
---|---|
Sensor types (RTD) that can be used | Pt, Ni, Cu sensors: 2, 3, 4-wire |
Linear resistance measuring range | 0 Ω ... 4000 Ω (Minimum measuring span: 10% of the selected measuring range) |
Sensor input current | approx. 200 µA |
Temperature measuring range | -200 °C ... 850 °C (Range depends on sensor type, range can be set freely via software or in increments from -150°C to 850°C via DIP switches) |
Connection technology | 2, 3, 4-wire |
Number of outputs | 1 |
---|---|
Configurable/programmable | Yes |
Voltage output signal | 0 V ... 10 V |
10 V ... 0 V | |
0 V ... 5 V | |
1 V ... 5 V | |
Current output signal | 0 mA ... 20 mA |
4 mA ... 20 mA | |
20 mA ... 0 mA | |
20 mA ... 4 mA | |
Max. output voltage | approx. 12.3 V |
Max. output current | 24.6 mA |
Load/output load voltage output | 10 kΩ |
Load/output load current output | 500 Ω (at 20 mA) |
Ripple | < 20 mVPP |
< 20 mVPP(at 500 Ω) |
Supply voltage range | 9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715)) |
---|---|
Typical current consumption | < 27 mA (at 24 V DC) |
Power consumption | ≤ 700 mW (at IOUT= 20 mA, 9.6 V DC, load 500 Ω) |
Connection method | Spring-cage connection |
---|---|
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Stripping length | 8 mm |
Transmission error resistance thermometer | 0.1 % * 350 K / set measuring range; 0.1 % > 350 K (Pt/Ni) |
---|---|
0.3 % * 200 K / set measuring range; 0.3 % > 200 K (Cu) | |
Transmission error resistance-type sensor | 2 Ω |
Maximum temperature coefficient | 0.01 %/K |
Status display | LED red |
Protective circuit | Transient protection |
Electrical isolation | Basic insulation according to EN 61010 |
Overvoltage category | II |
Degree of pollution | 2 |
Rated insulation voltage | 50 V AC/DC |
Test voltage, input/output/supply | 1.5 kV (50 Hz, 1 min.) |
Electromagnetic compatibility | Conformance with EMC directive |
Noise emission | EN 61000-6-4 |
Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
Color | green |
Mounting position | any |
Assembly instructions | The T connector can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715. |
Conformance | CE-compliant |
ATEX | II 3 G Ex nA IIC T4 Gc X |
UL, USA/Canada | UL 508 Listed |
Class I, Div. 2, Groups A, B, C, D T4 | |
Class I, Zone 2, Group IIC | |
Certificate of classification | DNV GL 14085-15HH |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
Designation | Electromagnetic RF field |
---|---|
Standards/regulations | EN 61000-4-3 |
Typical deviation from the measuring range final value | 0.04 % |
Designation | Fast transients (burst) |
Standards/regulations | EN 61000-4-4 |
Typical deviation from the measuring range final value | 0.1 % |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Typical deviation from the measuring range final value | 0.02 % |
Electromagnetic compatibility | Conformance with EMC directive |
---|---|
Noise emission | EN 61000-6-4 |
Standards/regulations | EN 61000-4-2 |
Designation | Electromagnetic RF field |
Standards/regulations | EN 61000-4-3 |
EN 61000-4-4 | |
EN 61000-4-5 | |
Designation | Conducted interferences |
Standards/regulations | EN 61000-4-6 |
Electrical isolation | Basic insulation according to EN 61010 |
Conformance | CE-compliant |
ATEX | II 3 G Ex nA IIC T4 Gc X |
UL, USA/Canada | UL 508 Listed |
Class I, Div. 2, Groups A, B, C, D T4 | |
Class I, Zone 2, Group IIC | |
Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 2 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 2 |
China RoHS | Environmentally Friendly Use Period = 50 |
---|---|
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
Title: | Size: | Type: |
---|---|---|
PDF CATALOG PHOENIX INTERFACE TECHNOLOGY AND SWITCHING DEVICES EN.pdf | 27 Mbytes | |
PHOENIX CONTACT-2902850-MINI MCR-RTD-UI-SP-NC | 117 Kbytes |
No customer reviews for the moment.
Rating: | |
Name: | |
Email: | |
Subject: | |
Text: | |
Do you recommend this product to buy? | |
Add review |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.