Key Commercial Data

Orderkey2906484
Packing unit1 pc
Catalog pagePage 59 (C-4-2017)
GTIN4055626081601
Weight per Piece (excluding packing)293.700 g
Custom tariff number85366990
Country of originDE (Germany)

Dimensions

Height98.7 mm
Width71 mm
Depth51.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch4 Div.

Ambient conditions

Degree of protectionIP20 (only when all terminal points are used)
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

General

IEC test classificationII
T2
EN typeT2
Mounting typeDIN rail: 35 mm
Colorjet black RAL 9005
Housing materialPBT
Degree of pollution2
Flammability rating according to UL 94V-0
TypeBase element, DIN rail mounting
Number of positions4
Surge protection fault messageRemote indication contact

Additional descriptions

NoteFor installation into a touch protected cabinet. For applications with UC> 500 V distances at the side and distances at the connection area must be minimum of 5 mm between different active parts including earthed parts.

Protective circuit

Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC800 V AC
Rated load current IL80 A
Short-circuit current rating ISCCR25 kA
Max. backup fuse with V-type through wiring80 A (gG)
Max. backup fuse with branch wiring125 A (gG)

Indicator/remote signaling

Switching functionPDT contact
Operating voltage5 V AC ... 250 V AC
30 V DC
Operating current5 mA AC ... 750 mA AC
1 A DC
Connection methodPlug-in/screw connection via COMBICON
Screw threadM2
Tightening torque0.25 Nm
Stripping length7 mm
Conductor cross section flexible0.14 mm² ... 1.5 mm²
Conductor cross section solid0.14 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16

Connection data

Connection methodScrew connection
Screw threadM5
Tightening torque3 Nm (1,5 mm² ... 16 mm²)
4.5 Nm (25 mm² ... 35 mm²)
Stripping length16 mm
Conductor cross section flexible1.5 mm² ... 25 mm²
Conductor cross section solid1.5 mm² ... 35 mm²
Conductor cross section AWG15 ... 2
Connection methodFork-type cable lug
Conductor cross section flexible1.5 mm² ... 16 mm²

UL specifications

SPD Type4CA
Nom. voltage690 V AC
Nominal frequency50/60 Hz

UL indicator/remote signaling

Operating voltage125 V AC
Operating current1 A AC
Tightening torque4 lbf-in.
Conductor cross section AWG30 ... 14

UL connection data

Conductor cross section AWG10 ... 2
Tightening torque30 lbf-in.

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.