Axioline F temperature module, 4 inputs for connecting resistance temperature detectors (including bus base module and connectors)

More details


AUTOMATION Industrial Automation - PHOENIX CONTACT

I/O systems. Connectors - PHOENIX CONTACT

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Quantity Price
1+$380.57
2+$369.55
3+$364.27
4+$363.74
*This price is per unit and is the net value (not including taxes if applicable).

Related products

More info



Product description

The module is designed for use within an Axioline F station.

It is used to acquire signals from resistive temperature sensors.

The module supports all common platinum and nickel sensors according to DIN EN 60751 and SAMA. Cu10, Cu50, Cu53 sensors as well as various KTY8x sensor types are also supported.

Dimensions

Width35 mm
Height126.1 mm
Depth54 mm
Note on dimensionsThe depth is valid when a TH 35-7.5 DIN rail is used (according to EN 60715).

Ambient conditions

Ambient temperature (operation)-25 °C ... 60 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)5 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)5 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protectionIP20

Connection data

DesignationAxioline F connector
Connection methodPush-in connection
Note on connection methodPlease observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.1.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.1.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.16
Stripping length8 mm

General

Net weight144 g
Note on weight specificationswith connectors and bus base module
Mounting typeDIN rail

Interfaces

DesignationAxioline F local bus
Connection methodBus base module
Transmission speed100 MBit/s

Axioline potentials

Communications power UBus5 V DC (via bus base module)
Current consumption from UBusmax. 140 mA
Supply for analog modules UA24 V DC
Current consumption from UAmax. 17 mA

Analog inputs

Number of inputs4 (for resistance temperature detectors)
Input nameAnalog inputs
Description of the inputInputs for resistive temperature sensors
Connection methodSpring-cage connection with direct connector-in method
2, 3, 4-wire (shielded)
Sensor types (RTD) that can be usedPt, Ni, KTY, Cu sensors
Linear resistance measuring range0 Ω ... 500 Ω
0 kΩ ... 5 kΩ
Nominal value of the current sources1 mA (Pt 100, Ni 100, RLin 500 Ω; pulse current, the specification is valid during the sampling phase)
Measured value representation16 bits (15 bits + sign bit)
Resolution A/D24 bit
Protective circuitShort-circuit protection, overload protection of the inputs
Data formatsIB IL, S7-compatible
PrecisionSee Tables under tolerance values
Input filter time40 ms

Datasheet - PDF

Title: Language: Size: Type:
PHOENIX CONTACT-2688556-AXL F RTD4 1H English 200 Kbytes PHOENIX CONTACT-2688556-AXL F RTD4 1H

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

Últimas Opiniones de Nuestros Clientes

Todas las valoraciones que recibimos de los artículos que ofrecemos son reales y están verificadas. Un pequeño gesto, pero de mucho valor. Por eso, te agradecemos ese minuto que inviertes en dejarnos tu opinión y calificación sobre los productos, porque nos ayuda a seguir mejorando y a ofrecerte un servicio de todavía mayor calidad.