AXL F AO4 1H 2688527 PHOENIX CONTACT Axioline F analog output module, 4 outputs: 0 10 V, ±10 V, 0 5 V, ±5 V,.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

AXL F AO4 1H 2688527 PHOENIX CONTACT Axioline F analog output module, 4 outputs: 0 10 V, ±10 V, 0 5 V, ±5 V,..

AXL F AO4 1H

2688527

PHOENIX_CONTACT

Available

Ship on today

Axioline F analog output module, 4 outputs: 0 - 10 V, ±10 V, 0 - 5 V, ±5 V, 0 - 20 mA, 4 - 20 mA, 2-wire connection technology (including bus base module and connectors)

More details


Programmable Logic Controllers Plcs

AUTOMATION Industrial Automation - PHOENIX CONTACT

I/O systems - PHOENIX CONTACT

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

* This article is obsolete. Please ask us for a quotation and we will check if there are units available or we will offer you an alternative product.

Related products

More info



Product description

The module is designed for use within an Axioline F station.

It is used to output analog voltage and current signals.

Dimensions

Width35 mm
Height126.1 mm
Depth54 mm
Note on dimensionsThe depth is valid when a TH 35-7.5 DIN rail is used (according to EN 60715).

Ambient conditions

Ambient temperature (operation)-25 °C ... 60 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)5 % ... 95 % (non-condensing)
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protectionIP20

Connection data

DesignationAxioline F connector
Connection methodPush-in connection
Note on connection methodPlease observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.1.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.1.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.16
Stripping length8 mm

General

Net weight145 g
Note on weight specificationswith connectors and bus base module
Mounting typeDIN rail

Interfaces

DesignationAxioline F local bus
Connection methodBus base module
Transmission speed100 MBit/s

Axioline potentials

Communications power UBus5 V DC (via bus base module)
Current consumption from UBustyp. 120 mA
max. 150 mA
Supply for analog modules UA24 V DC
Current consumption from UAtyp. 40 mA (induced current consumption; no load, 0 V output)
typ. 60 mA (4 voltage channels, 10 V output)
max. 110 mA (4 current channels, 20 mA output, 500 Ω load)

Analog outputs

Number of outputs4
Connection methodPush-in connection
2-wire (shielded, twisted pair)
Output nameAnalog outputs
D/A resolution16 bit
Type of protectionShort-circuit and overload protection
Transient protection
Protective circuit/componentElectronic
Suppressor diode
Data formatsIB IL, S7-compatible
Representation of output values16 bits (15 bits + sign)
Process data update140 µs
Current output signal0 mA ... 20 mA
4 mA ... 20 mA
Load/output load current output≤ 500 Ω
Voltage output signal0 V ... 5 V
-5 V ... 5 V
0 V ... 10 V
-10 V ... 10 V
Load/output load voltage output> 1 kΩ
Precisiontyp. 0.1 % (of output range final value)
typ. 0.1 % (of output range final value)

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2688527-AXL F AO4 1HEnglish164 KbytesPHOENIX CONTACT-2688527-AXL F AO4 1H

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review