Standards
IEC/EN 61131-2
IEC/EN 61000-6-2
IEC/EN 61000-6-4
ApprovalsApprovals
CE, cULus
EAC
Approvalsshipping classification
DNV GL
Electromagnetic compatibility (EMC)ESD [Air/contact discharge]
8 / 4 kV
Electromagnetic compatibility (EMC)Electromagnetic fields [(0.08…1) / (1,4…2) / (2…2,7) GHz ]
10 / 3 / 1 V/m
Electromagnetic compatibility (EMC)BurstSupply cable
2 kV
Electromagnetic compatibility (EMC)BurstSignal cable
1 kV
Electromagnetic compatibility (EMC)SurgeSupply cable (balanced / unbalanced)
0,5 / 0,5 kV
Electromagnetic compatibility (EMC)SurgeSignal cable (unbalanced)
1 kV
Electromagnetic compatibility (EMC)Radiated RFI
10 V
Electromagnetic compatibility (EMC)Emitted interference (radiated, high frequency) [(30...230 MHz) / (230...1000 MHz)]
40 / 47 class A dB
Electromagnetic compatibility (EMC)Voltage fluctuations/voltage dips
Yes / 10 ms
Ambient conditionsClimatic conditionsClimatic proofing
Dry heat to IEC 60068-2-2
Damp heat as per EN 60068-2-3
Ambient conditionsClimatic conditionsAir pressure (operation)
795 - 1080 hPa
Ambient conditionsClimatic conditionsRelative humidity
0 - 95%, non condensing
Ambient conditionsClimatic conditionsCondensation
prevent with suitable measures
Ambient conditionsTemperatureOperation
0 - +55 °C
Ambient conditionsTemperatureStorage, transport [ϑ]
-20 - +85 °C
Mounting position
Horizontal
Free fall, packaged (IEC/EN 60068-2-32)
1 m
Vibrations [3,5 mm / 1 g]
5 - 8.4 / 8.4 -150 Hz
Mechanical shock resistance [Semisinusoidal 15 g/11 ms]
18 Impacts
Rated operational dataInsulating material group
I
Rated operational dataOvervoltage category / pollution degree
III / 3
Rated operational dataRated operating voltage
160 V
Rated operational dataMaximum load current/cross-sectional area
X (not specified by plug manufacturer) A / mm²
Connection design in TOP direction
Push-in spring-cage terminal (plug-in connection)
Gauge pin IEC/EN 60947-1
A1
Connection specifications"e" solid H07V-U
0.2 - 1.5 mm2
Connection specifications"f" flexible H 07V-K
0.2 - 1.5 mm2
Connection specifications"f" with ferrules without plastic collar according to DIN 46228-1 (ferrules crimped gas-tight)
0.25-1,5 mm2
Connection specifications"f" with ferrules with plastic collar according to DIN 46228-1 (ferrules crimped gas-tight)
0.25-1,5 mm2
Connection specificationsCable size
24 - 16 AWG
Power supply - InputPower supplyCurrent consumption for +5 V power supply (internal) [I]
(typ.)45 mA
Power supply - InputPower supplyCurrent consumption for +24 V power supply [I]
(typ.)none mA
Power supply - InputPower supplyPotential isolation [PE (polyethylene)]
no
Power supply - InputPower supplyRated operating voltage [Ue]
24 (terminal +1) V
Power supply - InputPower supplyRated operational current [Ie]
3.4 A
Power supply - InputPower supplyPotential isolation
no
Power supply - InputPower supplyRated operating voltage [Ue]
24 (terminal +2) V
Power supply - InputPower supplyRated operational current [Ie]
3.4 A
Power supply - InputPower supplyPotential isolation
no
Power supply - InputPower supplyRated operating voltage [Ue]
24 (terminal +3) V
Power supply - InputPower supplyRated operational current [Ie]
3.4 A
Power supply - InputPower supplyPotential isolation
no
Heat dissipationHeat dissipation (without active channels)
0.25 W
Heat dissipationMax. heat dissipation
3.529 W
Heat dissipationNotes on heat dissipation
The max. heat dissipation is specified as the maximum power produced inside the device's housing.
Output voltageOutput voltage, nominal value [Ua]
24 V DC
Output voltageLow level [UaL]
0V < UaL< 1V V
Output voltageHigh level [UaH]
Ue - 1V < UaH< Ue V
Output currentOutput current, nominal value [IaL]
1.7 A
Output currentLow signal [IA]
0 < IaL< 0.5 mA
Output currentHigh level [IaH]
0 ≤ IaH≤ 1700 mA
Potential isolation
no Output against output
Heat dissipation (internal, per active channel)
0.383 W
Utilization factor [%]
50% (Ʃ IAmax = 10.2A) g
Delay on signal change and resistive loadfrom Low to High level
< 200 µs
Delay on signal change and resistive loadFrom High to Low signal
< 200 µs
Resistive loadResistive load
> 14,1 Ω
Notes on digital outputs
Protective devices must be installed directly at the inductive load in order to prevent interference.