Product name
Eaton xEffect CS enclosure single door
Product Length/Depth
200 millimetre
Product height
700 millimetre
Product width
500 millimetre
Product weight
21.33 kilogram
Compliances
UL CSA09 (may be provided with metal sub-panel, no back mounted components are allowed between sub-panel and the back sheet metal enclosure)
UL 508A; CSA-C22.2 No.14; IEC/EN 62208; CE marking
RoHS conform
Certifications
UL (File No. E336299)
IEC/EN 62208
UL (Category Control Number NITW)
UL CSA08 (request filed)
In accordance with Directive 2015/863/EU of the European Parliament and Council
Product Tradename
xEffect CS
Product Sub Type
Single door
Type
Wall-mounting housing CSWall-mounting housing with mounting plate
Color
Gray
Light gray (RAL 7035)
Technical Data - Mechanical
Design type
Canted and seam welded, including two M6 threaded bolts for earth conductor connections inside the enclosure.
Surface finishing
Gloss
Semi-textured
Structured powder spray polyester based paint finish
Powder coating
Surface treatment
Structured powder spray polyester based paint finish
Mounting method
9 mm drilling dimensions for wall mounting (Back plate)
Wall fastening
Intermediate mounting
Mounting plate height
670 mm
Mounting plate material
Sheet steel, hot-galvanized
Mounting plate width
450 mm
Material thickness (body)
1.5 mm
Material thickness (bottom plate)
2 mm
Material thickness (door)
1.5 mm
Degree of protection
IK09 (impact resistance)
IEC: IP66, indoor; UL/CSA Types 1, 12, indoor only.
IP23 (with ventilating plates)
IP66
IK09
12 (NEMA)
Number of connector holes
0
Load capacity (door)
25 kg
Load capacity (mounting plate)
500 kg payload, when brackets fitted in all four enclosure corners (vertically or horizontally) and the weights are symmetrically distributed within the enclosure.
250 kg
Permissible load of the door(s) according to IEC 62208 - max
250 N
Permissible load of the enclosure according to IEC 62208 - max
2750 N
Permissible load of the mounting plate according to IEC 62208 - max
2500 N
Weight of mounted components - max
275 kg
Cover/door angle
120° door opening angle
Cover/door profile
2 door profiles
Cover/door type
Door hinges on the right, can be converted by user
Closed
Standard closure 3 mm double-ward key (door interlock)
Flange plate dimensions
172 mm x 432 mm
Installation site
Indoor installation
Installation type
Floor standing wall model
Thickness of mounting plate
2 mm
Climatic proofing
Damp heat, constant, to IEC 60068-2-78; Damp heat, cyclical, to IEC 60068-2-30
Temperature-rise verification as per IEC 60890
Heat diss. ambient 35°C delta T: 20°C wall mount middle encl. top (IEC 60890)
47 W
Heat diss. ambient 35°C delta T: 35°C wall mount middle encl. top (IEC 60890)
93 W
Heat diss. ambient 35°C delta T:20°C wall mount individ. encl. top (IEC 60890)
53 W
Heat diss. ambient 35°C delta T:20°C wall mount starting encl. top (IEC 60890)
50 W
Heat diss. ambient 35°C delta T:35°C wall mount individ. encl. top (IEC 60890)
105 W
Heat diss. ambient 35°C delta T:35°C wall mount starting encl. top (IEC 60890)
99 W
Heat diss. wall mount individual encl. top
53 W
Heat diss. wall mount middle encl. top
47 W
Heat diss. wall mount starting encl. top
50 W
Thermal dissipation (Delta T = 20 K) according to IEC/TR 60890
53 W
Design verification as per IEC/EN 61439 - technical data
Ambient operating temperature details
-25 °C - 40 °C
Design verification as per IEC/EN 61439
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply to enclosures without lifting aids.
10.2.6 Mechanical impact
IK09
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
IP66
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
< 0.1 Ω; meets the product standard's requirements.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Ui = 1000 V AC
10.9.3 Impulse withstand voltage
Does not apply to basic enclosures as defined in EN 62208.
10.9.4 Testing of enclosures made of insulating material
Does not apply to metal enclosures.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.
Features
Wall build in
Pole fastening
Fitted with:
Including M6 threaded welded studs for earth conductor connections in the door:
Mounting plate
Cover
Door
Functions
Floor standing enclosure
Special features
Bottom plate enclosed, foamed gasket, can be unscrewed for F3A-… flanges or for assembly by userFoamed polyurethane sealing throughout.Impact resistance category IK09 to EN 62262.Sheet steel mounting plateBottom plate with foamed gasket.Single door, door stop on the right, door opening angle 120°Door hinge pins with quick change technology.Standardized locking system with sash fastener.Powder coating RAL 7035 inside and outsideLock, 3 mm double ward keyIncluding M6 threaded welded studs for earth conductor connections in the doorSide plates without aperturesTop plate without apertures
Suitable for
Metrical mounting
Used with