DMV-1600N/4 1814597 EATON ELECTRIC Switch-disconnector, 4 pole, 1600 A, Without rotary handle and drive shaf.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

DMV-1600N/4 1814597 EATON ELECTRIC Switch-disconnector, 4 pole, 1600 A, Without rotary handle and drive shaf..

DMV-1600N/4

1814597

EATON-MOELLER

Switch-disconnector, 4 pole, 1600 A, Without rotary handle and drive shaft, surface mounting

DMV-1600N/4

Switch-disconnector, DMV, 1600 A, 4 pole, Stop Function optional, Without rotary handle and drive shaft

More details


Low-voltage industrial components > Switch disconnector

DUMECO Switch-Disconnectors

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

Total price: $2,237.13
Unit price: $2,237.13

*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Switch-disconnector, DMV, 1600 A, 4 pole, Stop Function optional, Without rotary handle and drive shaft
Switch-disconnector, Product range: Switch-disconnector, Main switch, maintenance switch, Part group reference: DMV, Stop Function: optional, Without rotary handle and drive shaft, Notes: visible contacts, Information about equipment supplied: auxiliary contact fitted by user., including connection materials, 4 pole, Degree of Protection: IP00, IP20 with terminal cover, Design: surface mounting, Motor rating AC-23A, 50 - 60 Hz 400 V: P = 750 kW, Rated uninterrupted current: Iu = 1600 A, Standards: IEC/EN 60947, VDE 0660, IEC/EN 60204, Switch-disconnector according to IEC/EN 60947-3

Delivery program

Product range
Switch-disconnector
Main switch
maintenance switch
Part group reference
DMV
Stop Function
optional
Without rotary handle and drive shaft
Notes
visible contacts
Information about equipment supplied
auxiliary contact fitted by user.
including connection materials
Number of poles
4 pole
Auxiliary contacts
0 N/O
0 N/C
Degree of Protection
IP00
IP20 with terminal cover
Design
surface mounting
000Z428
Contact sequence
1150SWI-38
Motor rating AC-23A, 50 - 60 Hz [P]
400 V [P]
750 kW
Rated uninterrupted current [Iu]
1600 A
Note on rated uninterrupted current !u
Rated uninterrupted current Iuis specified for max. cross-section.

Technical data

General
Standards
IEC/EN 60947, VDE 0660, IEC/EN 60204
Switch-disconnector according to IEC/EN 60947-3
Certifications
CE, RoHs, KEMA, EAC, Lloyds
Ambient temperatureOperation [ϑ]
-25 - +55 °C
Ambient temperatureStorage [ϑ]
-30 - +80 °C
Overvoltage category/pollution degree
III/3
Rated impulse withstand voltage [Uimp]
12 kV
Rated insulation voltage [Ui]
1000 V
Mounting position
As required
Contacts
Mechanical variablesNumber of poles
4 pole
Mechanical variablesAuxiliary contacts
0 N/O
Mechanical variablesAuxiliary contacts
0 N/C
Electrical characteristicsRated operational voltage [Ue]
690 V AC
Electrical characteristicsRated uninterrupted current [Iu]
1600 A
Electrical characteristicsNote on rated uninterrupted current !u
Rated uninterrupted current Iuis specified for max. cross-section.
Rated short-time withstand current (1 s current) [Icw]
50000 Arms
Note on rated short-time withstand current lcw
Current for a time of 1 second
Heat dissipation per pole, current-dependent [Pvid]
45 W
Switching capacity
Rated breaking capacity cos ϕ to IEC 60947-3400/415 V
10000 A
Rated breaking capacity cos ϕ to IEC 60947-3500 V
7272 A
Rated breaking capacity cos ϕ to IEC 60947-3690 V
4050 A
Safe isolation to EN 61140Current heat loss per contact at Ie
44.75 W
Lifespan, mechanical [Operations]
5000
ACAC-21ARated operational current switch400 V 415 V [Ie]
1600 A
ACAC-21ARated operational current switch500 V [Ie]
1600 A
ACAC-21ARated operational current switch690 V [Ie]
1600 A
ACAC-22ARated operational current switch400 V 415 V [Ie]
1600 A
ACAC-22ARated operational current switch500 V [Ie]
1600 A
ACAC-22ARated operational current switch690 V [Ie]
1600 A
ACAC-23ARated operational current switch400 V 415 V [Ie]
1250 A
ACAC-23ARated operational current switch500 V [Ie]
909 A
ACAC-23ARated operational current switch690 V [Ie]
630 A
ACAC-23AMotor rating AC-23A, 50 - 60 Hz [P]400 V 415 V [P]
750 kW
ACAC-23AMotor rating AC-23A, 50 - 60 Hz [P]500 V [P]
630 kW
ACAC-23AMotor rating AC-23A, 50 - 60 Hz [P]690 V [P]
630 kW
Terminal capacities
Flat conductor connection with busbars
1000 mm2
Terminal screw
M12 x 50 (2 x)
Tightening torque for terminal screw
40 Nm
Technical safety parameters:
Notes
B10dvalues as per EN ISO 13849-1, table C1

Design verification as per IEC/EN 61439

Technical data for design verification
Rated operational current for specified heat dissipation [In]
1600 A
Heat dissipation per pole, current-dependent [Pvid]
45 W
Equipment heat dissipation, current-dependent [Pvid]
0 W
Static heat dissipation, non-current-dependent [Pvs]
0 W
Heat dissipation capacity [Pdiss]
0 W
Operating ambient temperature min.
-25 °C
Operating ambient temperature max.
+55 °C
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 7.0

Low-voltage industrial components (EG000017) / Switch disconnector (EC000216)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Off-load switch, circuit breaker, control switch / Switch disconnector ([email protected] [AKF060013])
Version as main switch
Yes
Version as maintenance-/service switch
Yes
Version as safety switch
No
Version as emergency stop installation
Yes
Version as reversing switch
No
Number of switches
1
Max. rated operation voltage Ue AC
690 V
Rated operating voltage
690 - 690 V
Rated permanent current Iu
1600 A
Rated permanent current at AC-23, 400 V
1250 A
Rated permanent current at AC-21, 400 V
1600 A
Rated operation power at AC-3, 400 V
0 kW
Rated short-time withstand current lcw
50 kA
Rated operation power at AC-23, 400 V
750 kW
Switching power at 400 V
710 kW
Conditioned rated short-circuit current Iq
0 kA
Number of poles
4
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Motor drive optional
No
Motor drive integrated
No
Voltage release optional
No
Device construction
Complete device in housing
Suitable for ground mounting
Yes
Suitable for front mounting 4-hole
No
Suitable for front mounting centre
No
Suitable for distribution board installation
Yes
Suitable for intermediate mounting
No
Colour control element
Other
Type of control element
Other
Interlockable
No
Type of electrical connection of main circuit
Screw connection
Degree of protection (IP), front side
IP20
Degree of protection (NEMA)
Other

Dimensions

1150DIM-57

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.