FRCMM-63/4/03-A-NA 167106 EATON ELECTRIC Residual current circuit breaker (RCCB), 63A, 4p, 300mA, type A View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

FRCMM-63/4/03-A-NA 167106 EATON ELECTRIC Residual current circuit breaker (RCCB), 63A, 4p, 300mA, type A

FRCMM-63/4/03-A-NA

167106

EATON-MOELLER

Residual current circuit breaker (RCCB), 63A, 4p, 300mA, type A

FRCMM-63/4/03-A-NA

More details


Modular Switchgear – Industrial

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

Total price: $429.66
Unit price: $429.66

*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Residual current circuit breaker (RCCB), 63A, 4p, 300mA, type A
Residual current circuit-breaker FRCmM-NA, 4 pole, Rated current In: 63 A, Rated short-circuit strength Icn: 10 with back-up fuse kA, Rated fault current IΔN: 0.3 A, Switchgear for export to North America (UL-listed)

Delivery program

Basic function
Residual current circuit-breakers
Number of poles
4 pole
Application
Switchgear for export to North America (UL-listed)
Rated current [In]
63 A
Rated short-circuit strength [Icn]
10 with back-up fuse kA
Rated fault current [IΔN]
0.3 A
Type
Type A
Tripping
non-delayed s…
Product range
FRCmM-NA
Sensitivity
Pulse-current sensitive
Impulse withstand current
Partly surge-proof 250 A
Contact sequence
PFIM_4p

Technical data

Electrical
Types conform to
IEC/EN 61008
Current test marks
As per inscription
Tripping
non-delayed s…
Rated voltage according to IEC/EN 60947-2 [Un]
240/415 V AC
Rated frequency [f]
50/60 Hz
Limit values of the operating voltageTest circuit
184 - 440 V AC
Rated fault current [IΔn]
300 mA
Sensitivity
Pulse-current sensitive
Rated insulation voltage [Ui]
440 V
Rated impulse withstand voltage [Uimp]
4 (1.2/50μs) kV
Rated short-circuit strength [Icn]
10 with back-up fuse kA
Impulse withstand current
250 A (8/20 μs) surge-proof
Max. admissible back-up fuseShort-circuit [gG/gL]
63 A
Max. admissible back-up fuseOverload [gG/gL]
40 A
Rated making and breaking capacity / Rated residual making and breaking capacity [Im/ IΔm]
630 A
lifespanElectrical [Operations]
≧ 4000
lifespanMechanical [Operations]
≧ 10000
Electrical
Types conform to
UL1053
Current test marks
As per inscription
Tripping
non-delayed
Rated voltage according to UL [Un]
480Y/277 V, 60 Hz V AC
Limit values of the operating voltageTest circuit
196 - 528 V AC
Pick-up current
200 mA
Sensitivity
Pulse-current sensitive
Overvoltage-tested
530 V
Rated impulse withstand voltage [Uimp]
4 (1.2/50μs) kV
Rated short-circuit strength [Icn]
5 as per CSA kA
Max. admissible back-up fuseShort-circuit
70 A class J fuse
Max. admissible back-up fuseOverload
The maximum operating current must not exceed the residual current circuit-breaker's rated operational current
Rated making and breaking capacity / Rated residual making and breaking capacity [Im/ IΔm]
630 A
lifespanElectrical [Operations]
≧ 4000
lifespanMechanical [Operations]
≧ 10000
Mechanical
Standard front dimension
45 mm
Device height
80 mm
Built-in width
70 (4TE) mm
Mounting
Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715
Degree of Protection
IP40, IP54 (with moisture-proof enclosure)
Terminals top and bottom
Lift terminals
Terminal protection
Busbar tag shroud to BGV A3, ÖVE-EN 6
Terminal cross-sectionSolid
1.5 - 35 mm2
Terminal cross-sectionStranded
2 x 16 mm2
Terminal cross-section
M5 (with cross-recessed screw as defined in EN ISO 4757-Z2, Pozidriv PZ2)
Admissible ambient temperature range
-25 - +40 °C
Permissible storage and transport temperatures
-35 - +60 °C
Climatic proofing
25-55°C/90-95% relative humidity according to IEC 60068-2
Humidity
5 - 95 %
Pollution degree
2
Mounting position
As required
Contact position indicator
red / green
Trip indication
white / blue

Design verification as per IEC/EN 61439

Technical data for design verification
Rated operational current for specified heat dissipation [In]
63 A
Heat dissipation per pole, current-dependent [Pvid]
2.625 W
Equipment heat dissipation, current-dependent [Pvid]
10.5 W
Operating ambient temperature min.
-25 °C
Operating ambient temperature max.
+75 °C
Starting at 40 °C, the max. permissible continuous current decreases by 1.8% for every 1 °C
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 7.0

Circuit breakers and fuses (EG000020) / Residual current circuit breaker (RCCB) (EC000003)
Electric engineering, automation, process control engineering / Electrical installation, device / Residual current protection system / Residual current circuit breaker (RCCB) ([email protected] [AAB906014])
Number of poles
4
Rated voltage
480 V
Rated current
63 A
Rated fault current
300 mA
Rated insulation voltage Ui
440 V
Rated impulse withstand voltage Uimp
4 kV
Mounting method
DIN rail
Leakage current type
A
Selective protection
No
Short-time delayed tripping
No
Short-circuit breaking capacity (Icw)
10 kA
Surge current capacity
0.25 kA
Frequency
50/60 Hz
Additional equipment possible
Yes
With interlocking device
Yes
Degree of protection (IP)
IP20
Width in number of modular spacings
4
Built-in depth
70.5 mm
Ambient temperature during operating
-25 - 40 °C
Pollution degree
2
Connectable conductor cross section multi-wired
1.5 - 16 mm²
Connectable conductor cross section solid-core
1.5 - 35 mm²

Dimensions

Mas_frcmm

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.