Product name
Eaton xEnergy Safety Ci empty enclosure insulated
Product Length/Depth
225 millimetre
Product height
250 millimetre
Product width
375 millimetre
Product weight
3.046 kilogram
Compliances
IEC/EN 60439-1, VDE 0660 Part 500
RoHS conform
Certifications
EN 62208
EN 61439-2
Product Tradename
xEnergy Safety Ci
Product Type
Empty enclosure
Product Sub Type
Insulated
Type
Basic enclosurePanel enclosure with gland plates fittedxEnergy Safety Ci
Color
Gray
Light gray (RAL 7035, base)
Transparent, smoky gray (cover)
Technical Data - Electrical
Operating altitude without derating - max
2000 mm
Technical Data - Mechanical
Unit type
Stand-alone device
Surface finishing
Passivated
Galvanized
Enclosure material
Plastic
Width in number of modular spacings
15
Mounting depth with mounting plate
200 mm
Mounting grid
25 mm (DIN 43660)
Mounting method
Surface mounted (plaster)
Degree of protection
Other
IP00 (cable entry open)
IP64 (KST cable entries from above)
IP65
IP65 (KST cable entries from below)
IK10
IP65 (enclosure)
Number of conduit inlets
76
Number of openings (flange plates)
4
Relative humidity
90 % (at 20 °C)
50 % (at 40 °C)
Cable entry type
14 - 68 mm (3x)
Cover/door color
Transparent
Creepage and clearance distances
III/3 to IEC/EN 60439-1 (standard)
Plate thickness (cabinet)
6 mm
Plate thickness (cover/door)
6 mm
Temperature-rise verification as per IEC 60890
Heat diss. ambient 35°C delta T: 20°C wall mount middle encl. top (IEC 60890)
22 W
Heat diss. ambient 35°C delta T: 35°C wall mount middle encl. top (IEC 60890)
45 W
Heat diss. ambient 35°C delta T:20°C wall mount individ. encl. top (IEC 60890)
25 W
Heat diss. ambient 35°C delta T:20°C wall mount starting encl. top (IEC 60890)
24 W
Heat diss. ambient 35°C delta T:35°C wall mount individ. encl. top (IEC 60890)
51 W
Heat diss. ambient 35°C delta T:35°C wall mount starting encl. top (IEC 60890)
48 W
Design verification as per IEC/EN 61439 - technical data
Ambient operating temperature - min
-5 °C
Ambient operating temperature - max
40 °C
Mean ambient operating temperature (24 hours)
35 °C
Design verification as per IEC/EN 61439
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Lower part: 960 °C / cover: 850 °C
10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2.5 Lifting
10 kg per enclosure with support frame and lifting aid met; assembled and secured as per the latest applicable instruction leaflet.
10.2.6 Mechanical impact
IK10
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
IP65
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
Protection class 2, therefore not applicable.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Ui = 1000 V AC
10.9.3 Impulse withstand voltage
8 kV
10.9.4 Testing of enclosures made of insulating material
Meets the product standard's requirements.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.
Features
Cover with overpressure release
Flammability characteristics of glow rod test
VDE 0304 Part 3 level IIb, level IIb to IEC 60707
Functions
Extension possible
Special features
Low-voltage fuses (IEC/EN 60269, VDE 0636)Sealable cover fastenersSides closed, but with full area knockoutOpen topFitting of cable supports in the distribution board with wedge-lock fastenerGland plate can be split, cables can be inserted from the front
Suitable for
Lightning protection
Outdoor use
Used with
The reference values indicated in the table apply to the basic elements of the distribution board. As far as devices, terminals etc. fitted into the enclosures are concerned, their own specific technical data and rated values apply.