NZMN3-ME220-SVE 168483 EATON ELECTRIC Circuit-breaker, 3p, 220A, plug-in module View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

NZMN3-ME220-SVE 168483 EATON ELECTRIC Circuit-breaker, 3p, 220A, plug-in module

NZMN3-ME220-SVE

168483

EATON-MOELLER

Circuit-breaker, 3p, 220A, plug-in module

NZMN3-ME220-SVE

More details


Low-voltage industrial components > Motor protection circuit-breaker

Circuit Breakers NZM

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

Total price: $1,944.32
Unit price: $1,944.32

*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



EL-Nummer (Norway)
0004357585
Circuit-breaker, 3p, 220A, plug-in module
Circuit-breakers of the NZM..-ME series cover all applications with only four compact sizes and are suitable for the IEC market. The mounting is always flexible due to the modular function groups. With electronic release for the motor protection with phase failure sensitivity. Notes: IEC/EN 60947-4-1, IEC/EN 60947-2, r.m.s. value measurement and thermal memory, adjustable time delay setting to overcome current peaks tr:2-20 at 6xIr as well as infinity (without overload release)

Design verification as per IEC/EN 61439

Technical data for design verification
Rated operational current for specified heat dissipation [In]
220 A
Equipment heat dissipation, current-dependent [Pvid]
14.52 W
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 7.0

Low-voltage industrial components (EG000017) / Motor protection circuit-breaker (EC000074)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Motor protection circuit-breaker ([email protected] [AGZ529016])
Overload release current setting
110 - 220 A
Adjustment range undelayed short-circuit release
440 - 3080 A
With thermal protection
Yes
Phase failure sensitive
Yes
Switch off technique
Electronic
Rated operating voltage
690 - 690 V
Rated permanent current Iu
220 A
Rated operation power at AC-3, 230 V
55 kW
Rated operation power at AC-3, 400 V
110 kW
Type of electrical connection of main circuit
Screw connection
Type of control element
Rocker lever
Device construction
Built-in device plug-in technique
With integrated auxiliary switch
No
With integrated under voltage release
No
Number of poles
3
Rated short-circuit breaking capacity lcu at 400 V, AC
50 kA
Degree of protection (IP)
IP20
Height
215.2 mm
Width
140 mm
Depth
335 mm

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.