PLZM-D6/1N-MW 242353 EATON MOELLER Over current switch, 6A, 1pole+N, type D characteristic View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

PLZM-D6/1N-MW 242353 EATON MOELLER Over current switch, 6A, 1pole+N, type D characteristic

PLZM-D6/1N-MW

242353

EATON - MOELLER

Available

Ship on today

Over current switch, 6A, 1pole+N, type D characteristic

More details


Circuit Breakers Electrical Power

Miniature Circuit Breakers PLSM, PLZM - EATON - MOELLER

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON - MOELLER

Quantity Price
1+$43.76
7+$37.75
13+$36.58
19+$35.99
25+$35.66
*This price is per unit and is the net value (not including taxes if applicable).

Related products

More info



Design verification as per IEC/EN 61439(Show features)(Hide features)
Technical data for design verification
   
Rated operational current for specified heat dissipation
InA6
Heat dissipation per pole, current-dependent
PvidW0
Equipment heat dissipation, current-dependent
PvidW1.6
Static heat dissipation, non-current-dependent
PvsW0
Heat dissipation capacity
PdissW0
Operating ambient temperature min.
 °C-25
Operating ambient temperature max.
 °C75
 
  linear, per +1 °C, results in a 0.5% reduction of current carrying capacity
IEC/EN 61439 design verification
   
10.2 Strength of materials and parts
   
10.2.2 Corrosion resistance
  Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
  Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
  Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
  Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
  Meets the product standard's requirements.
10.2.5 Lifting
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
  Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
  Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
  Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
  Meets the product standard's requirements.
10.5 Protection against electric shock
  Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
  Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
  Is the panel builder's responsibility.
10.8 Connections for external conductors
  Is the panel builder's responsibility.
10.9 Insulation properties
   
10.9.2 Power-frequency electric strength
  Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
  Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
  Is the panel builder's responsibility.
10.10 Temperature rise
  The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
  Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
  The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 6.0
Circuit breakers and fuses (EG000020) / Miniature circuit breaker (MCB) (EC000042)
Electric engineering, automation, process control engineering / Electrical installation, device / Miniature circuit breaker system (MCB) / Miniature circuit breaker (MCB) ([email protected] [AAB905011])
Release characteristic
  D
Number of poles (total)
  2
Number of protected poles
  2
Nominal rated current
 A6
Nominal rated voltage
 V230
Rated short-circuit breaking capacity Icn EN 60898 at 230 V
 kA10
Rated short-circuit breaking capacity Icn EN 60898 at 400 V
 kA10
Rated short-circuit breaking capacity Icu IEC 60947-2 at 230 V
 kA0
Rated short-circuit breaking capacity Icu IEC 60947-2 at 400 V
 kA0
Voltage type
  AC
Current limiting class
  3
Frequency
 Hz50 - 60
Concurrently switching N-neutral
  Yes
Suitable for flush-mounted installation
  No
Over voltage category
  3
Pollution degree
  2
Width in number of modular spacings
  2
Built-in depth
 mm70.5
Additional equipment possible
  Yes
Degree of protection (IP)
  IP20

Datasheet - PDF

Title: Language: Size: Type:
EATON-242353-PLZM-D6/1N-MW English 137 Kbytes EATON-242353-PLZM-D6/1N-MW

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.