Dimensions
  mm
C  
Technical data for design verification
     
Heat dissipation, at an ambient temperature of 35°C, delta T: 20 degrees, calculated as per IEC 60890
     
Individual enclosure for wall mounting
PV CO 19
Starting enclosure for wall mounting
PV CO 17
Middle enclosure for wall mounting
PV CO 16
Heat dissipation, at an ambient temperature of 35°C, delta T: 35 degrees, calculated as per IEC 60890
     
Individual enclosure for wall mounting
PV CO 38
Starting enclosure for wall mounting
PV CO 35
Middle enclosure for wall mounting
PV CO 32
IEC/EN 61439 design verification
     
10.2 Strength of materials and parts
     
10.2.2 Corrosion resistance
    Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
    Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
    Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
    Lower part: 960 °C / cover: 850 °C; meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
    Not relevant to indoor installations.
10.2.5 Lifting
    10 kg per enclosure with support frame and lifting aid met; assembled and secured as per the latest applicable instruction leaflet.
10.2.6 Mechanical impact
    IK10
10.2.7 Inscriptions
    Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
    IP65
10.4 Clearances and creepage distances
    Is the panel builder's responsibility.
10.5 Protection against electric shock
    Protection class 2, therefore not applicable.
10.6 Incorporation of switching devices and components
    Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
    Is the panel builder's responsibility.
10.8 Connections for external conductors
    Is the panel builder's responsibility.
10.9 Insulation properties
     
10.9.2 Power-frequency electric strength
    Ui = 1000 V AC
10.9.3 Impulse withstand voltage
    8 kV
10.9.4 Testing of enclosures made of insulating material
    Meets the product standard's requirements.
10.10 Temperature rise
    The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
    Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
    Is the panel builder's responsibility.
10.13 Mechanical function
    Meets the product standard's requirements.
Dimensions
>>

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

Últimas Opiniones de Nuestros Clientes

Todas las valoraciones que recibimos de los artículos que ofrecemos son reales y están verificadas. Un pequeño gesto, pero de mucho valor. Por eso, te agradecemos ese minuto que inviertes en dejarnos tu opinión y calificación sobre los productos, porque nos ayuda a seguir mejorando y a ofrecerte un servicio de todavía mayor calidad.