Standards
IEC/EN 60947, VDE 0660, IEC/EN 60204
Switch-disconnector according to IEC/EN 60947-3
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperatureOpen
-25 - +50 °C
Ambient temperatureEnclosed
-25 - +40 °C
Overvoltage category/pollution degree
III/3
Rated impulse withstand voltage [Uimp]
6000 V AC
Mechanical shock resistance
15 g
Mounting position
As required
Mechanical variablesNumber of poles
8-pole
Electrical characteristicsRated operational voltage [Ue]
690 V AC
Electrical characteristicsRated uninterrupted current [Iu]
100 A
Electrical characteristicsNote on rated uninterrupted current !u
Rated uninterrupted current Iuis specified for max. cross-section.
Load rating with intermittent operation, class 12AB 25 % DF
2 x Ie
Load rating with intermittent operation, class 12AB 40 % DF
1.6 x Ie
Load rating with intermittent operation, class 12AB 60 % DF
1.3 x Ie
Short-circuit ratingFuse
100 A gG/gL
Rated short-time withstand current (1 s current) [Icw]
1700 Arms
Note on rated short-time withstand current lcw
Current for a time of 1 second
Rated conditional short-circuit current [Iq]
2 kA
cos ϕ rated making capacity as per IEC 60947-3
950 A
Rated breaking capacity cos ϕ to IEC 60947-3230 V
760 A
Rated breaking capacity cos ϕ to IEC 60947-3400/415 V
740 A
Rated breaking capacity cos ϕ to IEC 60947-3500 V
590 A
Rated breaking capacity cos ϕ to IEC 60947-3690 V
420 A
Safe isolation to EN 61140between the contacts
440 V AC
Safe isolation to EN 61140Current heat loss per contact at Ie
7.5 W
Safe isolation to EN 61140Current heat loss per auxiliary circuit at Ie(AC-15/230 V)
7.5 CO
Lifespan, mechanical [Operations]
> 0.5 x 106
Maximum operating frequency [Operations/h]
1200
ACAC-3Rating, motor load switch [P]220 V 230 V [P]
22 kW
ACAC-3Rating, motor load switch [P]230 V Star-delta [P]
30 kW
ACAC-3Rating, motor load switch [P]400 V 415 V [P]
30 kW
ACAC-3Rating, motor load switch [P]400 V Star-delta [P]
45 kW
ACAC-3Rating, motor load switch [P]500 V [P]
30 kW
ACAC-3Rating, motor load switch [P]500 V Star-delta [P]
45 kW
ACAC-3Rating, motor load switch [P]690 V [P]
15 kW
ACAC-3Rating, motor load switch [P]690 V Star-delta [P]
22 kW
ACAC-3Rated operational current motor load switch230 V [Ie]
71 A
ACAC-3Rated operational current motor load switch230 V star-delta [Ie]
100 A
ACAC-3Rated operational current motor load switch400V 415 V [Ie]
55 A
ACAC-3Rated operational current motor load switch400 V star-delta [Ie]
95.3 A
ACAC-3Rated operational current motor load switch500 V [Ie]
44 A
ACAC-3Rated operational current motor load switch500 V star-delta [Ie]
76.2 A
ACAC-3Rated operational current motor load switch690 V [Ie]
17 A
ACAC-3Rated operational current motor load switch690 V star-delta [Ie]
29.4 A
ACAC-21ARated operational current switch440 V [Ie]
100 A
ACAC-23AMotor rating AC-23A, 50 - 60 Hz [P]230 V [P]
30 kW
ACAC-23AMotor rating AC-23A, 50 - 60 Hz [P]400 V 415 V [P]
55 kW
ACAC-23AMotor rating AC-23A, 50 - 60 Hz [P]500 V [P]
37 kW
ACAC-23AMotor rating AC-23A, 50 - 60 Hz [P]690 V [P]
30 kW
ACAC-23ARated operational current motor load switch230 V [Ie]
100 A
ACAC-23ARated operational current motor load switch400 V 415 V [Ie]
100 A
ACAC-23ARated operational current motor load switch500 V [Ie]
55 A
ACAC-23ARated operational current motor load switch690 V [Ie]
32 A
DCDC-1, Load-break switches L/R = 1 msRated operational current [Ie]
80 A
DCDC-1, Load-break switches L/R = 1 msVoltage per contact pair in series
60 V
Control circuit reliability at 24 V DC, 10 mA [Fault probability]
< 10-5,< 1 failure in 100,000 switching operations HF
Solid or stranded
1 x (2,5 - 35)
2 x (2,5 - 16) mm2
Flexible with ferrules to DIN 46228
1 x (1 - 25)
2 x (1.5 - 10) mm2
Tightening torque for terminal screw
4 Nm
Technical safety parameters:
Notes
B10dvalues as per EN ISO 13849-1, table C1
Rating data for approved types
ContactsRated operational voltage [Ue]
600 V AC
ContactsRated uninterrupted current max.Main conducting pathsGeneral use
65 A
Terminal capacityTerminal screw
M6
Terminal capacityTightening torque
35.32 lb-in