Product name
Eaton DX Mains choke
Product Length/Depth
110 millimetre
Product height
160 millimetre
Product width
220 millimetre
Product weight
7.3 kilogram
Certifications
UL 508C
EN 61800-3
IEC 61800-5
CSA Std. C22.2 No. 14
VDE
IEC/EN61800-3
UL
UL File No.: E167225
CSA-C22.2 No. 14
VDE 0570 Part 2-20/2001-04
IEC/EN 61558-2-20-2000
IEC/EN61800-5
UL Category Control No.: XPTQ2, XPTQ8
CE
CSA
Certified by UL for use in Canada
UL report applies to both US and Canada
Product Sub Type
Mains choke
Fitted with:
Connection lugs
PE stud
Number of poles
Three-pole
Degree of protection
IP00
NEMA Other
Product Category
Accessories
Suitable as
Net reactance coil
Suitable for
Branch circuits, (UL/CSA)
Used with
SPX
DL1
DA1
SVX
DA1, DM1
Ambient conditions, mechanical
Mounting position
Suspended horizontally
Standing vertically
Free surrounding areas > 50 mm
Shock resistance
3 shocks
Shock duration: 11 ms
Vibration resistance
10 - 55 Hz, 0.35 mm
0 - 150 Hz, 1 g
Climatic environmental conditions
Altitude
Max. 1000 m
Max. 5000 m with current reduction
Ambient operating temperature - max
40 °C
Ambient operating temperature - min
-25 °C
Ambient storage temperature - max
85 °C
Ambient storage temperature - min
-25 °C
Operating temperature details
-25 - 40 °C (up to 70 °C with current derating)
Tightening torque
6 Nm, Screw terminals
Connection lug
Cu 20 x 3 mm²
Permissible connection voltage
Max. 550 V AC (50/60 Hz)
Rated current (Ith) at rated voltage DC - max
80 A
Rated frequency - min
50 Hz
Rated frequency - max
60 Hz
Rated operational current (Ie) - min
80 A
Rated operational current (Ie) - max
80 A
Rated operational voltage (Ue) - max
550 V
Relative short-circuit voltage
2.5 %
Voltage rating - max
480 V
Heat dissipation capacity Pdiss
0 W
Rated operational current for specified heat dissipation (In)
80 A
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.